Cooper FNM-1.8 13/32 x 1-1/2 250vac time-delay supplemental fus Datasheet

Effective April 2014
Supersedes September 2009
Technical Data 2028
FNM Series
13⁄32˝ x 1-1⁄2˝ 250Vac Time-delay supplemental fuses
Description
Dimensions - in (mm)
Time-delay supplemental fuse.
For superior protection, Bussmann recommends
upgrading to Low-Peak Class CC fuses. See data
sheet # 1023.
Catalog symbol / color code
•
Ratings
250Vac
1/10 to 30A
1.5"
(38.1)
Features
FNM - Green (250Vac maximum voltage)
Interrupting Rating
at System Voltage
Agency
Information
250Vac
125Vac
UL
CSA
1/10 to 1
35A
10kA
X
X
1-1/8 to 3-1/2
100A
10kA
X
X
4 to 10
200A
10kA
X
X
12 to 30
10kA
-
X
X
Fuse
Amp
Range
0.41"
(10.3)
Agency information
•
Color coded green for 250Vac maximum
voltage rating
•
Melamine tube construction
•
Nickel-plated brass endcaps
Typical applications
•
Circuits with high inrush currents
(motor/transformer loads)
•
Supplemental protection for 125Vac and
250Vac inductive circuits.
Recommended fuse blocks/fuse holders
•
CE
•
UL Listed, Std. 248-14, Guide JDYX;
File E19180
•
CSA Certified, Class 1422-01, File 53787
Series
Description
Data Sheet #
Blocks
Catalog numbers (amps)
1-, 2- & 3-Pole modular
blocks with optional
10235
covers
BMM Series
BM Series
1-, 2- & 3-Pole blocks
1104
FNM-1⁄10
FNM-8⁄10
FNM-2-1⁄2
FNM-6-1⁄4
FNM-1⁄8
FNM-1
FNM-2-8⁄10
FNM-7
CCP-_-30M
1-, 2- & 3-Pole switch
1157
FNM-15⁄100
FNM-1-1⁄8
FNM-3
FNM-8
CHM Series
1-, 2- & 3-Pole
3185
FNM-2⁄10
FNM-1-1⁄4
FNM-3-2⁄10
FNM-9
FNM-1⁄4
FNM-1-4⁄10
FNM-3-1⁄2
FNM-10
Optima NG
3-Pole protection
module
1109
FNM-3⁄10
FNM-1-1⁄2
FNM-4
FNM-12
Optima
3-Pole holder
1102
FNM-4⁄10
FNM-1-6⁄10
FNM-4-1⁄2
FNM-15
Optima
3-Pole holder + switch
1103
DIN-Rail Holders / Switches
Panel Mount Holders
FNM-1⁄2
FNM-1-8⁄10
FNM-5
FNM-20
FNM-6⁄10
FNM-2
FNM-5-6⁄10
FNM-25
HPM & HPM-D
1-Pole holder
2112
FNM-3⁄4
FNM-2-1⁄4
FNM-6
FNM-30
HPC-D
1-Pole holder
2109
HPS2
2-Pole holder
2140
HPF, HPF-C &
HPF-WT
1-Pole holder
2114
HPS
1-Pole holder
2113
HPG & HPD
1-Pole holder
2108
Carton quantity
Amps
Qty.
1/10 to 30
10
In-line Holders
HEB
1-Pole holder
2127
HEX
2-Pole holder
2126
Fuseclips
1A3400, 5956 &
5960 Series
PCB Fuseclips
SAMI-7
Finger-safe fuse cover
2132
Fuse Covers
1204



Technical Data 2028
Effective April, 2014
Time-current characteristic curves – total clearing
10A
5A
Time in Seconds
2A
Amp Rating
Current in Amps



Technical Data 2028
Effective April, 2014
Time-current characteristic curves – average melt
Time in Seconds
12A
15A
20A
25A
30A
Amp Rating
Current in Amps
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the
end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue
or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this
bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Eaton’s Bussmann Business
114 Old State Road
Ellisville, MO 63021
United States
www.Bussmann.com
© 2014 Eaton
All Rights Reserved
Publication No. 2028 - BU-SB14291
April 2014
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Similar pages