Cooper LPS-RK-500SP Dual-element, time-delay fus Datasheet

Bussmann®
LOW-PEAK®
LPS-RK
Dual-Element, Time-Delay Fuses
Class RK1 –– 600 Vac/300 Vdc
70-600A
NEW
Dimensional Data
DES
A
IGN
B
Dimensions (inches)
Ampere Ratings
70-100
110-200
225-400
450-600
Catalog Symbol: LPS-RK_SP (600V)
Ampere Rating: 70 to 600A
Voltage Rating:
ac: 600V (or less)
dc: 300V (or less)
Interrupting Rating:
ac: 300,000A RMS Sym.
dc: 100,000A
Agency Information:
UL Listed–Special Purpose**, Guide JFHR, File E56412
CSA Certified, (200,000 AIR) Class 1422-02, File 53787,
Class RK1 per CSA C22.2 No. 248.12
Catalog Numbers
LPS-RK-70SP
LPS-RK-150SP
LPS-RK-350SP
LPS-RK-80SP
LPS-RK-175SP
LPS-RK-400SP
LPS-RK-90SP
LPS-RK-200SP
LPS-RK-450SP
LPS-RK-100SP
LPS-RK-225SP
LPS-RK-500SP
LPS-RK-110SP
LPS-RK-250SP
LPS-RK-600SP
LPS-RK-125SP
LPS-RK-300SP
—
7.88
9.63
11.63
13.38
“A”
(± 0.062)
(± 0.062)
(± 0.094)
(± 0.094)
1.11
1.61
2.36
2.88
“B”
(± 0.020)
(± 0.020)
(± 0.020)
(± 0.020)
Features:
• High degree of current-limitation for maximum short-circuit
protection.
• Type 2 protection for IEC and NEMA starters when
properly sized.
• High inrush current motor protection.
• Time-delay permits 130% FLA sizing for back-up motor overload protection, and single-phasing protection.
• Low watt loss power consumption.
• Electrically isolated end caps.
• 300Vdc, UL Listed.
Applications:
• Branch distribution
• Motors
• Transformers
• Solenoids
• General purpose circuits
Recommended fuseblocks for
Class R 600V fuses
See Data Sheet: 1111
Available with tin plate option. Add suffix “-TP”. (Ex.: LPS-RK-100SP-TP)
Carton Quantity and Weight—LPS-RK (600Vac)
Weight*
Ampere
Ratings
Qty.
Carton
Lbs.
Kg.
70–100
1
2.20
1.0
110–200
1
1.10
0.5
Equipment
Fuse Clips
225–400
1
2.36
1.1
200A
450–600
1
3.44
1.5
Fuse Reducers For Class R Fuses
400A
*Weight per carton.
** Meets all performance requirements of UL Standard 248-12 for Class RK1
fuses.
600A
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
10-2-02
SB02295
Desired
Fuse (Case)
Size
Catalog Number
(Pairs)
600V
100A
No. 2621-R
100A
No. 2641-R
200A
No. 642-R
100A
No. 2661-R
200A
No. 2662-R
400A
No. 2664-R*
*Single reducer only (pair not required).
For additional information, see Data Sheet: 1118.
Form No. LPS-RK 70-600
Page 1 of 3
Data Sheet: 1002
Bussmann®
LOW-PEAK®
Dual-Element, Time-Delay Fuses
Class RK1 –– 600 Vac/300 Vdc
LPS-RK
70-600A
Time-Current Characteristic Average Melt
10-2-02
SB02295
Form No. LPS-RK 70-600
Page 2 of 3
Data Sheet: 1002
Bussmann®
LOW-PEAK®
LPS-RK
Dual-Element, Time-Delay Fuses
Class RK1 –– 600 Vac/300 Vdc
70-600A
Current-Limitation Curves
B
AMPERE
RATING
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
400,000
100,000
600A
400A
200A
100A
10,000
A
300,000
200,000
100,000
10,000
1,000
1,000
RMS SYMMETRICAL CURRENTS IN AMPERES
A-B=ASYMMETRICAL AVAILABLE PEAK (2.3 x SYMM RMS AMPS)
Current-Limiting Effects
Prosp.
S.C.C.
5,000
10,000
15,000
20,000
25,000
30,000
35,000
40,000
50,000
60,000
80,000
100,000
150,000
200,000
250,000
300,000
100A
2,200
2,700
3,050
3,300
3,500
3,700
3,900
4,050
4,300
4,550
4,950
5,250
5,900
6,450
6,850
7,250
Let-Through Current (Apparent RMS
Symmetrical) Versus Fuse Rating
200A
400A
600A
3,250
5,000
5,000
4,100
7,150
9,600
4,650
7,950
10,650
5,100
8,650
11,500
5,500
9,200
12,200
5,800
9,650
12,750
6,100
10,100
13,300
6,400
10,450
13,750
6,850
11,100
14,600
7,250
11,700
15,300
7,950
12,650
16,450
8,550
13,450
17,450
9,750
15,050
19,400
10,700
16,300
20,900
11,500
17,350
22,100
12,200
18,250
23,200
*Values derived from curve data.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
10-2-02
SB02295
Form No. LPS-RK 70-600
Page 3 of 3
Data Sheet: 1002
Similar pages