Littelfuse ARP41S The arp series is used in systems where equal run time for two motors is desirable Datasheet

Protection Relays
Alternating Relays
ARP SERIES
Alternating Relay
Description
8-PIN
11-PIN
Wiring Diagram
SPDT 8-PIN
DPDT 11-PIN
L1
L1
N/L2
N/L2
The ARP Series is used in systems where equal run time for
two motors is desirable. The selector switch allows selection
of alternation or for continuous operation of either load. LED’s
indicate the status of the output relay. This versatile series may
be front panel mounted (BZ1 accessory required) or 35 mm DIN
rail mounted with an accessory socket.
Operation
Alternating: When the rotary switch is in the “alternate”
position, alternating operation of Load A and Load B occurs upon
the opening of the control switch S1. To terminate alternating
operation and cause only the selected load to operate, rotate
the switch to position “A” to lock Load A or position “B” to lock
Load B. The LEDs indicate the status of the internal relay and
which load is selected to operate.
Note: Input voltage must be applied at all times for proper
alternation. The use of a solid-state control switch for S1 may
not initiate alternation correctly. S1 voltage must be from
the same supply as the unit’s input voltage (see connection
diagrams). Loss of input voltage resets the unit; Load A
becomes the lead load for the next operation.
Duplexing (Cross Wired): Duplexing models operate the same
as alternating relays and when both the Control (S1) and Lag
Load (S2) Switches are closed, Load A and Load B energize
simultaneously.
Relay contacts in above are isolated.
DPDT 8-PIN CROSS WIRED
L1
N/L2
Features & Benefits
V = VOLTAGE
LA = LOAD A
LB = LOAD B
S1 = PRIMARY CONTROL SWITCH
S2 = LAG LOAD SWITCH
Ordering Information
FEATURES
BENEFITS
Alternating or
electrically locked
operation
Flexibility to run unit alternating between the two
loads as normal or lock the relay to one specific load.
Low profile
selector switch
Prevents accidental actuation
LED status indication
Visual indication of which load is engaged
Industry standard
base connection
Flexibility to use in many applications
OUTPUT
FORM
DESCRIPTION
AR120A-3095 120VAC
SPDT
8 pin for alternating applications. Rotary switch allows user to lock internal relay to one specific load.
ARP23S
24VAC
DPDT
8 pin cross wired for duplexing applications. Rotary switch allows user to lock internal relay to one specific load.
ARP41
120VAC
SPDT
8 pin for alternating applications.
ARP41S
120VAC
SPDT
8 pin for alternating applications. Rotary switch allows user to lock internal relay to one specific load.
ARP42S
120VAC
DPDT
11 pin for alternating applications. Rotary switch allows user to lock internal relay to one specific load.
ARP43
120VAC
DPDT
8 pin cross wired for duplexing applications.
ARP43S
120VAC
DPDT
8 pin cross wired for duplexing applications. Rotary switch allows user to lock internal relay to one specific load.
ARP61S
230VAC
SPDT
8 pin for alternating applications. Rotary switch allows user to lock internal relay to one specific load.
ARP62S
230VAC
DPDT
8 pin cross wired for duplexing applications. Rotary switch allows user to lock internal relay to one specific load.
ARP63S
230VAC
DPDT
8 pin cross wired for duplexing applications. Rotary switch allows user to lock internal relay to one specific load.
MODEL
LINE
VOLTAGE
The DPDT 8-pin, cross-wired option, allows extra system load
capacity through simultaneous operation of both motors when
needed. Relay contacts are not isolated.
If you don’t find the part you need, call us for a custom product 800-843-8848
© 2016 Littelfuse Protection Relays & Controls
www.littelfuse.com/
www.littelfuse.com/arp
Rev: 1-A-062116
Protection Relays
Alternating Relays
ARP SERIES
Accessories
BZ1 Front Panel Mount Kit
Provides an easy method of through-the-panel
mounting of 8- or 11-pin plug-in timers, flashers,
and other controls.
NDS-8 Octal 8-pin Socket
8-pin 35mm DIN rail or surface mount. Rated
at 10A @ 300VAC. Surface mounted with two
#6 (M 3.5 x 0.6) screws or snaps onto a 35 mm
DIN rail. Uses PSC8 hold-down clips.
NDS-11 11-pin Socket
11-pin 35mm DIN rail or surface mount. Surface
mounted with two #6 (M 3.5 x 0.6) screws or
snaps onto a 35 mm DIN rail. Uses PSC11 holddown clips.
PSC8 or PSC11 Hold-down Clips
Securely mounts plug-in controls in any position.
Provides protection against vibration. Use PSC8
with NDS-8 Octal Socket or PSC11 with NDS-11
Socket. Sold in sets of two.
C103PM (AL) DIN Rail
35 mm aluminum DIN rail available in a 36 in.
(91.4 cm) length.
Specifications
Input
Tolerance
24VAC
120 & 230VAC
AC Line Frequency
Output
Type
Form
Rating
Maximum Voltage
Life
Protection
Isolation Voltage
Mechanical
Mounting
Dimensions
Termination
Environmental
Operating/Storage
Temperature
Weight
-15% to 20%
-20% to 10%
50/60Hz
Electromechanical relay
SPDT, DPDT, or cross wired DPDT
10A resistive @ 120/240VAC & 28 VDC;
1/3 hp @ 120/240VAC
250VAC
Mechanical - 1 x 107; Electrical - 1 x 10 6
≥ 1500V RMS input to output
Plug-in socket
H 81.3 mm (3.2”); W 60.7 mm (2.39”);
D 45.2 mm (1.78”)
Octal 8-pin or magnal 11-pin
-20° to 60°C / -30° to 85°C
5.6 oz (159 g) approx.
NOTE: Unit does not have debounce time delay.
© 2016 Littelfuse Protection Relays & Controls