20W Single Output Industrial DIN Rail Power Supply MDR-20 series Features : Universal AC input/Full range Protections: Short circuit / Overload / Over voltage Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 NEC class 2 / LPS compliant Built in DC OK active signal LED indicator for power on No load power consumption<0.75W 100% full load burn-in test 3 years warranty SPECIFICATION MODEL MDR-20-5 MDR-20-12 MDR-20-15 MDR-20-24 DC VOLTAGE 5V 12V 15V 24V RATED CURRENT 3A 1.67A 1.34A 1A CURRENT RANGE 0 ~ 3A 0 ~ 1.67A 0 ~ 1.34A 0 ~ 1A RATED POWER 15W RIPPLE & NOISE (max.) Note.2 80mVp-p OUTPUT 20W 24W 120mVp-p 150mVp-p 10.8 ~ 13.2V 13.5 ~ 16.5V 21.6 ~ 26.4V VOLTAGE TOLERANCE Note.3 2.0% 1.0% 1.0% 1.0% LINE REGULATION 1.0% 1.0% 1.0% 1.0% LOAD REGULATION 1.0% 1.0% 1.0% 1.0% SETUP, RISE TIME INPUT 4.75 ~ 5.5V VOLTAGE ADJ. RANGE 20W 120mVp-p Note.5 500ms, 30ms/230VAC HOLD UP TIME (Typ.) 50ms/230VAC VOLTAGE RANGE 85 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz 1000ms, 30ms/115VAC at full load 20ms/115VAC at full load 120 ~ 370VDC EFFICIENCY (Typ.) 76% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 0.55A/115VAC 0.35A/230VAC COLD START 20A/115VAC 40A/230VAC <1mA / 240VAC LEAKAGE CURRENT OVERLOAD PROTECTION 80% 81% 84% 105 ~ 160% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 13.8 ~ 16.2V 17.25 ~ 20.25V 27.6 ~ 32.4V 5.75 ~ 6.75V OVER VOLTAGE FUNCTION Protection type : Shut down o/p voltage, re-power on to recover 9 ~ 13.5V / 40mA DC OK ACTIVE SIGNAL (max.) 3.75 ~ 6V / 50mA WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE SAFETY & EMC (Note 4) OTHERS 18 ~ 27V / 20mA -40 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC ISOLATION RESISTANCE EMI CONDUCTION & RADIATION Compliance to EN55011,EN55022 (CISPR22), EN61204-3 Class B Compliance to EN61000-3-2,-3 HARMONIC CURRENT EMS IMMUNITY Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024,EN61000-6-1,EN61204-3, light industry level, criteria A MTBF 236.9K hrs min. MIL-HDBK-217F (25 22.5*90*100mm (W*H*D) 0.19Kg; 72pcs/14.7Kg/0.91CUFT DIMENSION PACKING NOTE 11.5 ~ 16.5V / 40mA -20 ~ +70 (Refer to output load derating curve) 20 ~ 90% RH non-condensing ) 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. File Name:MDR-20-SPEC 2007-07-09 MDR-20 20W Single Output Industrial DIN Rail Power Supply Mechanical Specification Case No. 956 series Unit:mm 100 22.5 5 5 35 +V -V DC OK DC OK + 90 +V ADJ N L Install DIN rail TS35/7.5 or TS35/15 5 5 Block Diagram fosc : 60KHz DC OK RECTIFIERS & FILTER EMI FILTER I/P POWER SWITCHING DC OK RECTIFIERS & FILTER +V -V DETECTION CIRCUIT O.L.P. CONTROL O.V.P. Application of DC OK Active Signal (a) 5V signal (b) LED DC OK Model 5V 12V 15V 24V R 5.1V (c) Relay DC OK R 200 1.5K 2K 3.9K R Model 5V 12V 15V 24V DC OK R 1K 2.4K 3K 4.7K Relay RL RL 120 700 700 1.2K V- V- V- Model 5V 12V 15V 24V Output Derating VS Input Voltage Derating Curve Ta=25 100 100 90 80 80 70 LOAD (%) LOAD (%) 60 40 20 -20 0 10 20 30 40 50 AMBIENT TEMPERATURE ( ) 60 70 (VERTICAL) 60 50 40 85 95 100 115 120 140 160 180 200 220 240 264 INPUT VOLTAGE (VAC) 60Hz File Name:MDR-20-SPEC 2007-07-09