AD ADE7760ARSRL Energy metering ic with on-chip fault detection Datasheet

Energy Metering IC with
On-Chip Fault Detection
ADE7760
FEATURES
GENERAL DESCRIPTION
High accuracy active energy measurement IC, supports
IEC 687/61036
Less than 0.1% error over a dynamic range of 500 to 1
Supplies active power on the frequency outputs F1 and F2
High frequency output CF is intended for calibration and
supplies instantaneous active power
Continuous monitoring of the phase and neutral current
allows fault detection in 2-wire distribution systems
Current channels input level best suited for current
transformer sensors
Uses the larger of the two currents (phase or neutral) to
bill—even during a fault condition
Two logic outputs (FAULT and REVP) can be used to indicate
a potential miswiring or fault condition
Direct drive for electromechanical counters and 2-phase
stepper motors (F1 and F2)
Proprietary ADCs and DSP provide high accuracy over large
variations in environmental conditions and time
Reference 2.5 V ± 8% (drift 30 ppm/°C typical) with external
overdrive capability
Single 5 V supply, low power
The ADE7760 is a high accuracy, fault tolerant, electrical energy
measurement IC intended for use with 2-wire distribution
systems. The part specifications surpass the accuracy requirements as quoted in the IEC61036 standard.
The only analog circuitry used on the ADE7760 is in the ADCs
and reference circuit. All other signal processing (such as multiplication and filtering) is carried out in the digital domain. This
approach provides superior stability and accuracy over extremes
in environmental conditions and over time.
The ADE7760 incorporates a fault detection scheme similar to
the ADE7751 by continuously monitoring both the phase and
neutral currents. A fault is indicated when these currents differ
by more than 6.25%.
The ADE7760 supplies average active power information on the
low frequency outputs F1 and F2. The CF logic output gives
instantaneous active power information.
The ADE7760 includes a power supply monitoring circuit on
the VDD supply pin. Internal phase-matching circuitry ensures
that the voltage and current channels are matched. An internal
no-load threshold ensures that the ADE7760 does not exhibit
any creep when there is no load.
FUNCTIONAL BLOCK DIAGRAM
AGND
FAULT
VDD
8
15
1
POWER
SUPPLY MONITOR
V1A 2
ADC
ADE7760
SIGNAL PROCESSING BLOCK
HPF
A>B
V1N 4
ADC
V1B 3
B>A
A<>B
LPF
V2P 6
ADC
V2N 5
INTERNAL
OSCILLATOR
DIGITAL-TO-FREQUENCY CONVERTER
9
14
17
10
11
12
18
19
20
REFIN/OUT
RCLKIN
DGND
SCF
S1
S0 REVP CF
16
F2
F1
04434-0-001
4kΩ
2.5V
REFERENCE
Figure 1.
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable.
However, no responsibility is assumed by Analog Devices for its use, nor for any
infringements of patents or other rights of third parties that may result from its use.
Specifications subject to change without notice. No license is granted by implication
or otherwise under any patent or patent rights of Analog Devices. Trademarks and
registered trademarks are the property of their respective owners.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
Tel: 781.329.4700
www.analog.com
Fax: 781.326.8703
© 2004 Analog Devices, Inc. All rights reserved.
ADE7760
TABLE OF CONTENTS
Specifications..................................................................................... 3
Active Power Calculation .......................................................... 13
Timing Characteristics..................................................................... 5
Digital-to-Frequency Conversion ............................................ 15
Absolute Maximum Ratings............................................................ 6
Transfer Function....................................................................... 16
ESD Caution.................................................................................. 6
Fault Detection ........................................................................... 17
Terminology ...................................................................................... 7
Applications..................................................................................... 19
Pin Configuration and Function Descriptions............................. 8
Interfacing to a Microcontroller for Energy Measurement .. 19
Typical Performance Characteristics ........................................... 10
Selecting a Frequency for an Energy Meter Application....... 19
Operation......................................................................................... 11
Negative Power Information..................................................... 20
Power Supply Monitor ............................................................... 11
Outline Dimensions ....................................................................... 21
Analog Inputs.............................................................................. 11
Ordering Guide .......................................................................... 21
Internal Oscillator ...................................................................... 12
Analog-to-Digital Conversion.................................................. 12
REVISION HISTORY
Revision 0: Initial Version
Rev. 0 | Page 2 of 24
ADE7760
SPECIFICATIONS
VDD = 5 V ± 5%, AGND = DGND = 0 V, on-chip reference, on-chip oscillator, TMIN to TMAX = –40°C to +85°C.
Table 1.
Parameter
ACCURACY1
Measurement Error2
Phase Error between Channels
(PF = 0.8 Capacitive)
(PF = 0.5 Inductive)
AC Power Supply Rejection2
Output Frequency Variation
DC Power Supply Rejection2
Output Frequency Variation
FAULT DETECTION2, 3
Fault Detection Threshold
Inactive Input <> Active Input
Input Swap Threshold
Inactive Input <> Active Input
Accuracy Fault Mode Operation
V1A Active, V1B = AGND
V1B Active, V1A = AGND
Fault Detection Delay
Swap Delay
ANALOG INPUTS
Maximum Signal Levels
Input Impedance (DC)
Bandwidth (–3 dB)
ADC Offset Error2
Gain Error
REFERENCE INPUT
REFIN/OUT Input Voltage Range
Input Impedance
Input Capacitance
ON-CHIP REFERENCE
Reference Error
Temperature Coefficient
Current Source
ON-CHIP OSCILLATOR
Oscillator Frequency
Oscillator Frequency Tolerance
Temperature Coefficient
LOGIC INPUTS4
SCF, S1, and S0
Input High Voltage, VINH
Input Low Voltage, VINL
Input Current, IIN
Input Capacitance, CIN
Value
Unit
Test Conditions/Comments
0.1
% of reading, typ
Over a dynamic range of 500 to 1
±0.05
±0.05
Degrees, max
Degrees, max
Phase lead 37°
Phase lag 60°
0.01
%, typ
V1A = V1B = V2P = ±100 mV rms
0.01
%, typ
V1A = V1B = V2P = ±100 mV rms
See the Fault Detection section
6.25
%, typ
(V1A or V1B active)
6.25
% of larger, typ
(V1A or V1B active)
0.1
0.1
3
3
% of reading, typ
% of reading, typ
Seconds, typ
Seconds, typ
Over a dynamic range of 500 to 1
Over a dynamic range of 500 to 1
±660
400
7
10
±4
mV peak, max
kΩ, min
kHz, typ
mV, max
%, typ
2.7
2.3
4
10
V, max
V, min
kΩ, min
pF, max
±200
30
20
mV, max
ppm/°C, typ
µA, min
450
±12
30
kHz
% of reading, typ
ppm/°C, typ
2.4
0.8
±3
10
V, min
V, max
µA, max
pF, max
See footnotes on next page.
Rev. 0 | Page 3 of 24
V1A – V1N, V1B – V1N, V2P – V2N
Differential input
Uncalibrated error, see the Terminology section for details
External 2.5 V reference
2.5 V + 8%
2.5 V – 8%
VDD = 5 V ± 5%
VDD = 5 V ± 5%
Typical 10 nA, VIN = 0 V to VDD
ADE7760
Parameter
LOGIC OUTPUTS4
CF, REVP, and FAULT
Output High Voltage, VOH
Output Low Voltage, VOH
F1 and F2
Output High Voltage, VOH
Output Low Voltage, VOH
POWER SUPPLY
VDD
VDD
Value
Unit
Test Conditions/Comments
4
1
V, min
V, max
VDD = 5 V ± 5%
VDD = 5 V ± 5%
4
1
V, min
V, max
4.75
5.25
4
V, min
V, max
mA, max
VDD = 5 V ± 5%, Isource = 10 mA
VDD = 5 V ± 5%, Isink = 10 mA
For specified performance
5 V – 5%
5 V + 5%
1
See plots in the Typical Performance Characteristics section.
See the Terminology section for explanation of specifications.
3
See the Fault Detection section for explanation of fault detection functionality.
4
Sample tested during initial release and after any redesign or process change that may affect this parameter.
2
Rev. 0 | Page 4 of 24
ADE7760
TIMING CHARACTERISTICS
VDD = 5 V ± 5%, AGND = DGND = 0 V, on-chip reference, on-chip oscillator, TMIN to TMAX = –40°C to +85°C.
Sample tested during initial release and after any redesign or process change that may affect this parameter.
See Figure 2.
Table 2.
Parameter
t11
t2
t3
t41
t5
t6
Unit
ms
s
s
ms
s
s
Test Conditions/Comments
F1 and F2 Pulse Width (Logic High).
Output Pulse Period. See the Transfer Function section.
Time between F1 Falling Edge and F2 Falling Edge.
CF Pulse Width (Logic High).
CF Pulse Period. See the Transfer Function section.
Minimum Time between F1 and F2 Pulse.
The pulse widths of F1, F2, and CF are not fixed for higher output frequencies. See the Transfer Function section.
t1
F1
t6
t2
t3
F2
t4
t5
04434-0-002
1
Value
120
See Table 6
1/2 t2
90
See Table 7
CLKIN/4
CF
Figure 2. Timing Diagram for Frequency Outputs
Rev. 0 | Page 5 of 24
ADE7760
ABSOLUTE MAXIMUM RATINGS
TA = 25°C, unless otherwise noted.
Table 3.
Parameter
VDD to AGND
Analog Input Voltage to AGND
V1AP, V1BP, V1N, V2N, V2P
Reference Input Voltage to AGND
Digital Input Voltage to DGND
Digital Output Voltage to DGND
Operating Temperature Range
Industrial
Storage Temperature Range
Junction Temperature
20-Lead SSOP, Power Dissipation
θJA Thermal Impedance
Lead Temperature, Soldering
Vapor Phase (60 s)
Infrared (15 s)
Rating
–0.3 V to +7 V
–6 V to +6 V
–0.3 V to VDD + 0.3 V
–0.3 V to VDD + 0.3 V
–0.3 V to VDD + 0.3 V
Stresses above those listed under Absolute Maximum Ratings
may cause permanent damage to the device. This is a stress
rating only; functional operation of the device at these or any
other conditions above those listed in the operational sections
of this specification is not implied. Exposure to absolute
maximum rating conditions for extended periods may affect
device reliability.
–40°C to +85°C
–65°C to +150°C
150°C
450 mW
112°C/W
215°C
220°C
ESD CAUTION
ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulate on
the human body and test equipment and can discharge without detection. Although this product features
proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy
electrostatic discharges. Therefore, proper ESD precautions are recommended to avoid performance
degradation or loss of functionality.
Rev. 0 | Page 6 of 24
ADE7760
TERMINOLOGY
Measurement Error
The error associated with the energy measurement made by the
ADE7760 is defined by the following formula:
Percentage Error =
⎛ Energy registered by ADE7760 − True Energy
⎞
⎜
× 100% ⎟
⎜
⎟
True Energy
⎝
⎠
Phase Error between Channels
The high-pass filter (HPF) in the current channel has a phase
lead response. To offset this phase response and equalize the
phase response between channels, a phase correction network is
also placed in the current channel. The phase correction network ensures a phase match between the current channels and
voltage channels to within ±0.1° over a range of 45 Hz to 65 Hz
and ±0.2° over a range 40 Hz to 1 kHz.
Power Supply Rejection
This quantifies the ADE7760 measurement error as a percentage of reading when the power supplies are varied. For the ac
PSR measurement, a reading at nominal supplies (5 V) is taken.
A second reading is obtained with the same input signal levels
when an ac (175 mV rms/100 Hz) signal is introduced onto the
supplies. Any error introduced by this ac signal is expressed as a
percentage of reading (see the Measurement Error definition
above).
For the dc PSR measurement, a reading at nominal supplies
(5 V) is taken. A second reading is obtained with the same input
signal levels when the power supplies are varied ±5%. Any error
introduced is again expressed as a percentage of reading.
ADC Offset Error
This refers to the dc offset associated with the analog inputs to
the ADCs. It means that with the analog inputs connected to
AGND the ADCs still see a dc analog input signal. The magnitude of the offset depends on the input range selection (see the
Typical Performance Characteristics section). However, when
HPFs are switched on, the offset is removed from the current
channels and the power calculation is not affected by this offset.
Gain Error
The gain error in the ADE7760 ADCs is defined as the difference between the measured output frequency (minus the offset)
and the ideal output frequency. The difference is expressed as a
percentage of the ideal frequency. The ideal frequency is
obtained from the transfer function (see the Transfer Function
section).
Rev. 0 | Page 7 of 24
ADE7760
PIN CONFIGURATION AND FUNCTION DESCRIPTIONS
VDD
1
20 F1
V1A
2
19 F2
V1B
3
18 CF
V1N
4
V2N
5
V2P
6
NC
7
14 RCLKIN
AGND
8
13 INT
REFIN/OUT
9
12 S0
SCF 10
11 S1
17 DGND
TOP VIEW
(Not to Scale)
16 REVP
15 FAULT
04434-0-003
ADE7760
NC = NO CONNECT
Figure 3. Pin Configuration (SSOP)
Table 4. Pin Function Descriptions
Pin No.
1
Mnemonic
VDD
2, 3
V1A, V1B
4
V1N
5
V2N
6
V2P
7
8
NC
AGND
9
REFIN/OUT
10
SCF
11, 12
S1, S0
13
14
INT
RCLKIN
Description
Power Supply. This pin provides the supply voltage for the digital circuitry in the ADE7760. The supply
voltage should be maintained at 5 V ± 5% for specified operation. This pin should be decoupled with a
10 µF capacitor in parallel with a ceramic 100 nF capacitor.
Analog Inputs for Channel 1 (Current Channel). These inputs are fully differential voltage inputs with
maximum differential input signal levels of ±660 mV with respect to V1N for specified operation. The
maximum signal level at these pins is ±1 V with respect to AGND. Both inputs have internal ESD
protection circuitry, and an overvoltage of ±6 V can also be sustained on these inputs without risk of
permanent damage.
Negative Input Pin for Differential Voltage Inputs V1A and V1B. The maximum signal level at this pin is
±1 V with respect to AGND. The input has internal ESD protection circuitry, and an overvoltage of ±6 V
can also be sustained on these inputs without risk of permanent damage. The input should be directly
connected to the burden resistor and held at a fixed potential, that is, AGND. See the Analog Inputs
section.
Negative Input Pin for Differential Voltage Input V2P. The maximum signal level at this pin is ±1 V with
respect to AGND. The input has internal ESD protection circuitry, and an overvoltage of ±6 V can also be
sustained on these inputs without risk of permanent damage. The input should be held at a fixed
potential, that is, AGND. See the Analog Inputs section.
Analog Inputs for Channel 2 (Voltage Channel). This input is fully differential voltage input with
maximum differential input signal levels of ±660 mV with respect to V2N for specified operation. The
maximum signal level at these pins is ±1 V with respect to AGND. This input has internal ESD protection
circuitry, and an overvoltage of ±6 V can also be sustained on these inputs without risk of permanent
damage.
Not Connected. Nothing should be connected to this pin.
This pin provides the ground reference for the analog circuitry in the ADE7760, that is, ADCs and
reference. This pin should be tied to the analog ground plane of the PCB. The analog ground plane is the
ground reference for all analog circuitry such as antialiasing filters, and current and voltage transducers.
For good noise suppression, the analog ground plane should be connected only to the digital ground
plane at the DGND pin.
This pin provides access to the on-chip voltage reference. The on-chip reference has a nominal value of
2.5 V ± 8% and a typical temperature coefficient of 30 ppm/°C. An external reference source can also be
connected at this pin. In either case, this pin should be decoupled to AGND with a 1 μF ceramic
capacitor and 100 nF ceramic capacitor.
Select Calibration Frequency. This logic input is used to select the frequency on the calibration output
CF. Table 6 shows how the calibration frequencies are selected.
These logic inputs are used to select one of four possible frequencies for the digital-to-frequency
conversion. This offers the designer greater flexibility when designing the energy meter. See the
Selecting a Frequency for an Energy Meter Application section.
This pin is internally used and should be connected to DGND.
To enable the internal oscillator as a clock source on the chip, a precise low temperature drift resistor at
nominal value of 6.2 kΩ must be connected from this pin to DGND.
Rev. 0 | Page 8 of 24
ADE7760
Pin No.
15
Mnemonic
FAULT
16
REVP
17
DGND
18
CF
19, 20
F2, F1
Description
This logic output goes active high when a fault condition occurs. A fault is defined as a condition under
which the signals on V1A and V1B differ by more than 6.25%. The logic output is reset to zero when a fault
condition is no longer detected. See the Fault Detection section.
This logic output goes logic high when negative power is detected, that is, when the phase angle
between the voltage and current signals is greater than 90°. This output is not latched and is reset when
positive power is once again detected. The output goes high or low at the same time as a pulse is issued
on CF.
This pin provides the ground reference for the digital circuitry in the ADE7760, that is, multiplier, filters,
and digital-to-frequency converter. This pin should be tied to the digital ground plane of the PCB. The
digital ground plane is the ground reference for all digital circuitry such as counters (mechanical and
digital), MCUs, and indicator LEDs. For good noise suppression, the analog ground plane should be
connected only to the digital ground plane at the DGND pin.
Calibration Frequency Logic Output. The CF logic output, active high, gives instantaneous active power
information. This output is intended to be used for operational and calibration purposes. See the Digitalto-Frequency Conversion section.
Low Frequency Logic Outputs. F1 and F2 supply average active power information. The logic outputs
can be used to directly drive electromechanical counters and 2-phase stepper motors.
Rev. 0 | Page 9 of 24
ADE7760
TYPICAL PERFORMANCE CHARACTERISTICS
1.0
0.8
1.0
PF = 1
ON-CHIP REFERENCE
0.8
–40°C
PF = 1
ON-CHIP REFERENCE
5.25V
0.6
0.6
0.4
0.4
+25°C
–0.2
+85°C
0
–0.4
–0.4
–0.6
–0.6
–0.8
–0.8
–1.0
0.1
1.0
10.0
CURRENT (% of Full Scale)
100.0
4.75V
–1.0
0.1
Figure 4. Active Power Error as a Percentage of Reading with
Internal Reference
1.5
5.00V
–0.2
1.0
10.0
CURRENT (% of Full Scale)
Figure 6. Active Power Error as a Percentage of Reading over
Power Supply with Internal Reference
PF = 0.5
ON-CHIP REFERENCE
1.0
–40°C; PF = 0.5
+25°C; PF = 1
0
+25°C; PF = 0.5
–0.5
–1.0
0.1
1.0
10.0
CURRENT (% of Full Scale)
100.0
04434-0-038
Figure 5. Active Power Error as a Percentage of Reading over
Power Factor with Internal Reference
VDD
10µF
+
100nF
1
40A TO 80mA
I
1kΩ
RB
CF 18
VDD
2kΩ
PS2501-1
1
2 V1A
33nF
TO FREQ.
COUNTER
2
1kΩ
RB
3 V1B
FAULT 15
33nF
RCLKIN 14
1kΩ
RB = 18Ω
4
ADE7760
3
2kΩ
6.2kΩ
4 V1N
33nF
10kΩ
1kΩ
5 V2N
S0 12
33nF
S1 11
SCF 10
1MΩ
220V
1kΩ
REFIN/OUT 9
6 V2P
33nF
INT
13
AGND DGND
8
100nF
17
Figure 7. Test Circuit for Performances Curves
Rev. 0 | Page 10 of 24
+
10µF
04434-0-036
% ERROR
0.5
+85°C; PF = 0.5
100.0
04434-0-039
% ERROR
0.2
0
04434-0-037
% ERROR
0.2
ADE7760
OPERATION
POWER SUPPLY MONITOR
Channel V2 (Voltage Channel)
The ADE7760 contains an on-chip power supply monitor. The
power supply (VDD) is continuously monitored by the ADE7760.
If the supply is less than 4 V ± 5%, the ADE7760 goes into an
inactive state, that is, no energy is accumulated and the CF, F1,
and F2 outputs is disabled. This is useful to ensure correct
device operation at power-up and during power-down. The
power supply monitor has built-in hysteresis and filtering. This
gives a high degree of immunity to false triggering due to noisy
supplies.
The output of the line voltage transducer is connected to the
ADE7760 at this analog input. Channel V2 is a single-ended
voltage input. The maximum peak differential signal on
Channel 2 is ±660 mV with respect to V2N. Figure 10 shows the
maximum signal levels that can be connected to Channel 2.
DIFFERENTIAL INPUT
±660mV MAX PEAK
V2
V2N
VCM
COMMON MODE
±100mV MAX
–660mV + VCM
VCM
Figure 10. Maximum Signal Levels, Channel 2
VDD
The differential voltage V2P–V2N must be referenced to a
common mode (usually AGND). The analog inputs of the
ADE7760 can be driven with common-mode voltages of up to
100 mV with respect to AGND. However, the best results are
achieved using a common mode equal to AGND.
04434-0-010
TIME
ADE7760
REVP - FAULT - CF - INACTIVE
F1 - F2 OUTPUTS
ACTIVE
INACTIVE
Figure 8. On-Chip Power Supply Monitoring
ANALOG INPUTS
Channel V1 (Current Channel)
The voltage outputs from the current transducers are connected
to the ADE7760 here. Channel V1 has two voltage inputs, V1A
and V1B. These inputs are fully differential with respect to V1N.
However, at any one time, only one is selected to perform the
power calculation (see the Fault Detection section).
The maximum peak differential signal on V1A–V1N and V1B–V1N
is ±660 mV. Figure 9 shows the maximum signal levels on V1A,
V1B, and V1N. The differential voltage signal on the inputs must
be referenced to a common mode such as AGND.
V1A, V1B
DIFFERENTIAL INPUT A
±660mV MAX PEAK
IN
CF
AGND
V1N
RB
CF
CT
RF
V1B
Figure 11. Typical Connection for Channel 1
VCM
V1
V1B
Figure 9. Maximum Signal Levels, Channel 1
04434-0-011
VCM
AGND
RB
IP
V1A
RF
CT
V1
V1N
DIFFERENTIAL INPUT B
±660mV MAX PEAK
Figure 11 shows a typical connection diagram for Channel V1.
The analog inputs are being used to monitor both the phase and
neutral currents. Because of the large potential difference
between the phase and neutral, two current transformers (CTs)
must be used to provide the isolation. Note that both CTs are
referenced to AGND (analog ground); the common-mode
voltage is, therefore, 0 V. The CT turns ratio and burden resistor
(RB) are selected to give a peak differential voltage of ±660 mV.
V1A
+660mV + VCM
COMMON MODE
±100mV MAX
Typical Connection Diagrams
04434-0-014
0V
NEUTRAL
4V
PHASE
5V
–660mV + VCM
V2P
04434-0-012
The power supply and decoupling for the part should be such
that the ripple at VDD does not exceed 5 V ± 5% as specified for
normal operation.
V2
+660mV + VCM
Figure 12 shows two typical connections for Channel V2. The
first option uses a potential transformer (PT) to provide
complete isolation from the main voltage. In the second option,
the ADE7760 is biased around the neutral wire, and a resistor
divider is used to provide a voltage signal that is proportional to
the line voltage. Adjusting the ratio of RA and RB + VR is a
convenient way of carrying out a gain calibration on the meter.
Rev. 0 | Page 11 of 24
ADE7760
V2P
NEUTRAL
RF
CF
MCLK
ANALOG
LOW-PASS FILTER
V2N
CF
AGND
RB*
CF
VREF
DIGITAL
LOW-PASS FILTER
1
....10100101....
1-BIT DAC
V2P
NEUTRAL
LATCHED
COMPARATOR
24
C
RA*
VR*
Figure 14. First-Order Σ-∆ ADC
V2N
RF
04434-0-015
PHASE
INTEGRATOR
∫
R
04434-0-019
PHASE
RF
±660mV
CT
*RB + VR = RF
Figure 12. Typical Connection for Channel 2
INTERNAL OSCILLATOR
The nominal internal oscillator frequency is 450 kHz when
used with the recommended ROSC resistor value of 6.2 kΩ
between RCLKIN and DGND (see Figure 13).
The internal oscillator frequency is inversely proportional to the
value of this resistor. Although the internal oscillator operates
when used with a ROSC resistor value between 5 kΩ and 12 kΩ, it
is recommended to choose a value within the range of the
nominal value.
The output frequencies on CF, F1, and F2 are directly
proportional to the internal oscillator frequency; thus, the
resistor ROSC must have a low tolerance and low temperature
drift. A low tolerance resistor limits the variation of the internal
oscillator frequency. Small variation of the clock frequency and
consequently of the output frequencies from meter to meter
contributes to a smaller calibration range of the meter. A low
temperature drift resistor directly limits the variation of the
internal clock frequency over temperature. The stability of the
meter to external variation is then better ensured by design.
A Σ-Δ modulator converts the input signal into a continuous
serial stream of 1s and 0s at a rate determined by the sampling
clock. In the ADE7760, the sampling clock is equal to CLKIN.
The 1-bit DAC in the feedback loop is driven by the serial data
stream. The DAC output is subtracted from the input signal. If
the loop gain is high enough, the average value of the DAC
output (and, therefore, the bit stream) approaches that of the
input signal level. For any given input value in a single sampling
interval, the data from the 1-bit ADC is virtually meaningless.
Only when a large number of samples are averaged is a
meaningful result obtained. This averaging is carried out in the
second part of the ADC, the digital low-pass filter. By averaging
a large number of bits from the modulator, the low-pass filter
can produce 24-bit data words that are proportional to the input
signal level.
The Σ-Δ converter uses two techniques to achieve high resolution from what is essentially a 1-bit conversion technique. The
first is oversampling, which means that the signal is sampled at
a rate (frequency) that is many times higher than the bandwidth
of interest. For example, the sampling rate in the ADE7760 is
CLKIN (450 kHz) and the band of interest is 40 Hz to 1 kHz.
Oversampling has the effect of spreading the quantization noise
(noise due to sampling) over a wider bandwidth. With the noise
spread more thinly over a wider bandwidth, the quantization
noise in the band of interest is lowered (see Figure 15).
ADE7760
4kΩ
2.5V
REFERENCE
However, oversampling alone is not an efficient enough method
to improve the signal-to-noise ratio (SNR) in the band of interest. For example, an oversampling ratio of 4 is required just to
increase the SNR by only 6 dB (1 bit). To keep the oversampling
ratio at a reasonable level, it is possible to shape the quantization
noise so that the majority of the noise lies at the higher frequencies. This is what happens in the Σ-Δ modulator; the noise is
shaped by the integrator, which has a high-pass type response
for the quantization noise. The result is that most of the noise is
at the higher frequencies where it can be removed by the digital
low-pass filter. This noise shaping is also shown in Figure 15.
INTERNAL
OSCILLATOR
14
17
RCLKIN
DGND
ROSC
04434-0-017
9
REFIN/OUT
Figure 13. ADE7760 Internal Oscillator Connection
ANALOG-TO-DIGITAL CONVERSION
The analog-to-digital conversion in the ADE7760 is carried out
using second-order Σ-Δ ADCs. Figure 14 shows a first-order
(for simplicity) Σ-Δ ADC. The converter is made up of two
parts, the Σ-Δ modulator and the digital low-pass filter.
Rev. 0 | Page 12 of 24
ADE7760
ANTIALIAS FILTER (RC)
DIGITAL FILTER
SIGNAL
ACTIVE POWER CALCULATION
SAMPLING FREQUENCY
The ADCs digitize the voltage signals from the current and
voltage transducers. A high-pass filter in the current channel
removes any dc component from the current signal. This
eliminates any inaccuracies in the active power calculation due
to offsets in the voltage or current signals (see the HPF and
Offset Effects section).
SHAPED NOISE
NOISE
0
1kHz
225kHz
450kHz
FREQUENCY (Hz)
HIGH RESOLUTION
OUTPUT FROM
DIGITAL LFP
SIGNAL
0
1kHz
225kHz
04434-0-020
NOISE
450kHz
FREQUENCY (Hz)
Figure 15. Noise Reduction Due to Oversampling and
Noise Shaping in the Analog Modulator
Antialias Filter
Figure 15 also shows an analog low-pass filter (RC) on input to
the modulator. This filter is present to prevent aliasing. Aliasing
is an artifact of all sampled systems, which means that frequency components in the input signal to the ADC that are
higher than half the sampling rate of the ADC appear in the
sampled signal frequency below half the sampling rate.
Figure 16 illustrates the effect.
In Figure 16, frequency components (arrows shown in black)
above half the sampling frequency (also known as the Nyquist
frequency), that is, 225 kHz get imaged or folded back down
below 225 kHz (arrows shown in gray). This happens with all
ADCs no matter what the architecture. In the example shown, it
can be seen that only frequencies near the sampling frequency
(450 kHz) move into the band of interest for metering (40 Hz to
1 kHz). This fact allows the use of a very simple low-pass filter
to attenuate these frequencies (near 250 kHz) and thereby
prevent distortion in the band of interest. A simple RC filter
(single pole) with a corner frequency of 10 kHz produces an
attenuation of approximately 33 dB at 450 kHz (see Figure 16).
This is sufficient to eliminate the effects of aliasing.
The active power calculation is derived from the instantaneous
power signal. The instantaneous power signal is generated by a
direct multiplication of the current and voltage signals. To
extract the active power component (dc component), the
instantaneous power signal is low-pass filtered. Figure 17
illustrates the instantaneous active power signal and shows how
the active power information can be extracted by low-pass
filtering the instantaneous power signal. This scheme correctly
calculates active power for nonsinusoidal current and voltage
waveforms at all power factors. All signal processing is carried
out in the digital domain for superior stability over temperature
and time.
The low frequency output of the ADE7760 is generated by
accumulating this active power information. This low frequency
inherently means a long accumulation time between output
pulses. The output frequency is, therefore, proportional to the
average active power. This average active power information can
in turn be accumulated (for example, by a counter) to generate
active energy information. Because of its high output frequency
and therefore shorter integration time, the CF output is proportional to the instantaneous active power. This is useful for
system calibration purposes that would take place under steady
load conditions.
ADC
CH1
DIGITAL-TOFREQUENCY
F1
F2
HPF
MULTIPLIER
LPF
ADC
CH2
DIGITAL-TOFREQUENCY
CF
INSTANTANEOUS
POWER SIGNAL –p(t)
INSTANTANEOUS
ACTIVE POWER SIGNAL
V×I
1kHz
225kHz
FREQUENCY (Hz)
450kHz
TIME
04434-0-021
IMAGE
FREQUENCIES
0
p(t) = i(t).v(t)
WHERE:
V×I
v(t) = V × cos(ϖt)
2
i(t) = I × cos(ϖt)
p(t) = V × I {1 + cos (2ϖt)}
2
SAMPLING
FREQUENCY
Figure 17. Signal Processing Block Diagram
Figure 16. ADC and Signal Processing in Current Channel or Voltage Channel
Rev. 0 | Page 13 of 24
04434-0-022
ANTIALIASING EFFECTS
ADE7760
Power Factor Considerations
where:
The method used to extract the active power information from
the instantaneous power signal (by low-pass filtering) is still
valid even when the voltage and current signals are not in
phase. Figure 18 displays the unity power factor condition and
a displacement power factor (DPF = 0.5), that is, current signal
lagging the voltage by 60°. If one assumes the voltage and
current waveforms are sinusoidal, the active power component
of the instantaneous power signal (dc term) is given by
(V × I/2) × cos(60°). This is the correct active power calculation.
INSTANTANEOUS
POWER SIGNAL
i(t) is the instantaneous current.
IO is the dc component.
Ih is the rms value of current harmonic h.
βh is the phase angle of the current harmonic.
Using Equations 1 and 2, the active power P can be expressed in
terms of its fundamental active power (P1) and harmonic active
power (PH):
P = P1 + PH
INSTANTANEOUS
ACTIVE POWER SIGNAL
where:
P1 = V1 × I 1 cos(Φ 1 )
V×I
2
Φ 1 = α 1 − β1
0V
and
CURRENT
VOLTAGE
∞
PH = ∑ Vh × I h × cos(Φ h )
INSTANTANEOUS
POWER SIGNAL
V×I
2
(3)
h=2
INSTANTANEOUS
ACTIVE POWER SIGNAL
Φ h = α h − βh
× cos(60°)
04434-0-023
0V
VOLTAGE
CURRENT
60°
Figure 18. Active Power Calculation over PF
Nonsinusoidal Voltage and Current
The active power calculation method also holds true for
nonsinusoidal current and voltage waveforms. All voltage and
current waveforms in practical applications have some harmonic content. Using the Fourier transform, instantaneous
voltage and current waveforms can be expressed in terms of
their harmonic content:
∞
V (t ) = Vo + 2 × ∑ Vh × sin(hωt + α h )
h≠0
(1)
As can be seen from Equation 4, a harmonic active power
component is generated for every harmonic, provided that
harmonic is present in both the voltage and current waveforms.
The power factor calculation has previously been shown to be
accurate in the case of a pure sinusoid; therefore, the harmonic
active power must also correctly account for power factor,
because it is made up of a series of pure sinusoids.
Note that the input bandwidth of the analog inputs is 7 kHz
with the internal oscillator frequency of 450 kHz.
HPF and Offset Effects
Equation 5 shows the effect of offset on the active power
calculation. Figure 19 shows the effect of offsets on the active
power calculation in the frequency domain.
V (t ) × I (t ) =
(V0 + V1 × cos(ωt )) × (I 0 + I 1 × cos(ωt )) =
V0 × I 1 +
where:
v(t) is the instantaneous voltage.
Vh is the rms value of voltage harmonic h.
αh is the phase angle of the voltage harmonic.
∞
i(t ) = I o + 2 × ∑ I h × sin(hωt + β h )
h≠0
(4)
(2)
V1 × I 1
2
(5)
+ V0 × I 1 × cos(ωt ) + V1 × I 0 × cos(ωt )
As can be seen from Equation 5 and Figure 19, an offset on
Channel 1 and Channel 2 contributes a dc component after
multiplication. Because this dc component is extracted by the
LPF and used to generate the active power information, the
offsets contribute a constant error to the active power calculation. This problem is easily avoided in the ADE7760 with the
HPF in Channel 1. By removing the offset from at least one
channel, no error component can be generated at dc by the
multiplication. Error terms at cos(ωt) are removed by the LPF
and the digital-to-frequency conversion (see the Digital-toFrequency Conversion section).
Rev. 0 | Page 14 of 24
ADE7760
The HPF in Channel 1 has an associated phase response that is
compensated for on-chip. Figure 20 and Figure 21 show the
phase error between channels with the compensation network
activated. The ADE7760 is phase compensated up to 1 kHz as
shown, which ensures correct active harmonic power
calculation even at low power factors.
DC COMPONENT (INCLUDING ERROR TERM)
IS EXTRACTED BY THE LPF FOR ACTIVE
POWER CALCULATION
DIGITAL-TO-FREQUENCY CONVERSION
As previously described, the digital output of the low-pass filter
after multiplication contains the active power information.
However, because this LPF is not an ideal “brick wall” filter
implementation, the output signal also contains attenuated
components at the line frequency and its harmonics, that is,
cos(hωt), where h = 1, 2, 3, ..., and so on. The magnitude
response of the filter is given by
H( f ) =
V1 × I1
2
04434-0-024
2v
0v
FREQUENCY (RAD/S)
Figure 22 shows the instantaneous active power signal output of
the LPF, which still contains a significant amount of instantaneous power information, cos(2ωt). This signal is then passed to
the digital-to-frequency converter, where it is integrated
(accumulated) over time to produce an output frequency. This
accumulation of the signal suppresses or averages out any nondc components in the instantaneous active power signal. The
average value of a sinusoidal signal is zero. Therefore, the
frequency generated by the ADE7760 is proportional to the
average active power.
Figure 19. Effect of Channel Offsets on the Active Power Calculation
0.30
0.25
0.20
0.15
0.10
0.05
0
0
100
200
300
400 500 600 700
FREQUENCY (Hz)
800
900
1000
Figure 20. Phase Error between Channels (0 Hz to 1 kHz)
F1
0.30
DIGITAL-TOFREQUENCY
F1
F2
0.25
V
TIME
0.15
MULTIPLIER
LPF
I
0.10
LPF TO EXTRACT
ACTIVE POWER
(DC TERM)
0.05
0
DIGITAL-TOFREQUENCY
CF
FOUT
TIME
–0.10
40
45
50
55
60
FREQUENCY (Hz)
65
70
04434-0-026
–0.05
0
ϖ
2ϖ
FREQUENCY (Rad/s)
INSTANTANEOUS ACTIVE POWER SIGNAL (FREQUENCY DOMAIN)
Figure 21. Phase Error between Channels (40 Hz to 70 Hz)
Figure 22. Active Power to Frequency Conversion
Rev. 0 | Page 15 of 24
04434-0-027
PHASE (Degrees)
0.20
FREQUENCY
–0.10
04434-0-025
–0.05
Figure 22 also shows the digital-to-frequency conversion for
steady load conditions: constant voltage and current. As can be
seen in Figure 22, the frequency output CF varies over time,
even under steady load conditions. This frequency variation is
primarily due to the cos(2ωt) component in the instantaneous
active power signal.
FREQUENCY
PHASE (Degrees)
(6)
1 = ( f / 4.5 Hz) 2
For a line frequency of 50 Hz, this gives an attenuation of the 2ω
(100 Hz) component of approximately –26.9 dB. The dominating harmonic is at twice the line frequency, that is, cos(2ωt), due
to the instantaneous power signal.
V1 × I 0
V0 × I 1
1
ADE7760
The output frequency on CF can be up to 2048 times higher
than the frequency on F1 and F2. This higher output frequency
is generated by accumulating the instantaneous active power
signal over a much shorter time while converting it to a
frequency. This shorter accumulation period means less
averaging of the cos(2ωt) component. As a consequence, some
of this instantaneous power signal passes through the digital-tofrequency conversion. This is not a problem in the application.
Where CF is used for calibration purposes, the frequency
should be averaged by the frequency counter, which removes
any ripple. If CF is being used to measure energy, such as in a
microprocessor-based application, the CF output should also be
averaged to calculate power. Because the outputs F1 and F2
operate at a much lower frequency, a lot more averaging of the
instantaneous active power signal is carried out. The result is a
greatly attenuated sinusoidal content and a virtually ripple-free
frequency output.
TRANSFER FUNCTION
Frequency Outputs F1 and F2
The ADE7760 calculates the product of two voltage signals (on
Channel 1 and Channel 2) and then low-pass filters this product
to extract active power information. This active power
information is then converted to a frequency. The frequency
information is output on F1 and F2 in the form of active high
pulses. The pulse rate at these outputs is relatively low, for
example, 0.34 Hz maximum for ac signals with S0 = S1 = 0
(see Table 7). This means that the frequency at these outputs is
generated from active power information accumulated over a
relatively long period of time. The result is an output frequency
that is proportional to the average active power. The averaging
of the active power signal is implicit to the digital-to-frequency
conversion. The output frequency or pulse rate is related to the
input voltage signals by the following equation:
F1 − F2 Frequency =
5.70 × V1rms × V2 rms × F1− 4
V REF 2
(7)
Table 5. F1–4 Frequency Solution
S1
0
0
1
1
1
2
F1–4 (Hz)1
1.72
3.44
6.86
13.7
S0
0
1
0
1
OSC/CLKIN2
OSC/218
OSC/217
OSC/216
OSC/215
Values are generated using the nominal frequency of 450 kHz.
F1–4 are a binary fraction of the master clock and, therefore, varies, if the
internal oscillator frequency (OSC).
Frequency Output CF
The pulse output calibration frequency (CF) is intended for use
during calibration. The output pulse rate on CF can be up to
2048 times the pulse rate on F1 and F2. The lower the F1–4
frequency selected, the higher the CF scaling. Table 6 shows
how the two frequencies are related, depending on the states of
the logic inputs S0, S1, and SCF. Because of its relatively high
pulse rate, the frequency at this logic output is proportional to
the instantaneous active power. As with F1 and F2, the frequency is derived from the output of the low-pass filter after
multiplication. However, because the output frequency is high,
this active power information is accumulated over a much
shorter time. Therefore, less averaging is carried out in the
digital-to-frequency conversion. With much less averaging of
the active power signal, the CF output is much more responsive
to power fluctuations (see Figure 17).
Table 6. Relationship between CF and F1, F2 Frequency
Outputs
SCF
1
0
1
0
1
0
1
0
S1
0
0
0
0
1
1
1
1
S0
0
0
1
1
0
0
1
1
F1–4 (Hz)
1.72
1.72
3.44
3.44
6.86
6.86
13.7
13.7
CF Frequency output
128 × F1, F2
64 × F1, F2
64 × F1, F2
32 × F1, F2
32 × F1, F2
16 × F1, F2
16 × F1, F2
2048 × F1, F2
where:
Example
F1 − F2 Frequency is the output frequency on F1 and F2 (Hz).
V1rms is the differential rms voltage signal on Channel 1 (V).
V2rms is the differential rms voltage signal on Channel 2 (V).
VREF is the reference voltage (2.5 V ± 8%) (V).
F1–4 is one of four possible frequencies selected by using the
logic inputs S0 and S1 (see Table 5).
In this example, if ac voltages of ±660 mV peak are applied to
V1 and V2, then the expected output frequency on CF, F1, and
F2 is calculated as follows:
F1–4 = 1.7 Hz, SCF = S1 = S0 = 0
V1rms = rms of 660 mV peak ac = 0.66/√2 V
V2rms = rms of 660 mV peak ac = 0.66/√2 V
VREF = 2.5 V (nominal reference value)
Rev. 0 | Page 16 of 24
ADE7760
Fault with Active Input Greater than Inactive Input
5.70 × 0.66 × 0.66 × 1.72 Hz
2 × 2 × 2. 5 2
CF Frequency = F1 − F2 × 64 = 22.0 Hz
= 0.34 Hz
As can be seen from these two example calculations, the
maximum output frequency for ac inputs is always half of that
for dc input signals. Table 7 shows a complete listing of all
maximum output frequencies for ac signals.
Table 7. Maximum Output Frequency on CF, F1, and F2 for
AC inputs
SCF
1
0
1
0
1
0
1
0
S1
0
0
0
0
1
1
1
1
S0
0
0
1
1
0
0
1
1
F1, F2 Maximum
Frequency
(Hz)
0.34
0.34
0.68
0.68
1.36
1.36
2.72
2.72
CF Maximum
Frequency
(Hz)
43.52
21.76
43.52
21.76
43.52
21.76
43.52
5570
CF to
F1
Ratio
128
64
64
32
32
16
16
2048
V1A
V1A
V1B
A
V1A
FAULT
FILTER
AND
COMPARE
TO
MULTIPLIER
0V
V1N
AGND
V1B
V1B < 93.75% OF V1A
B
V1B
FAULT
<0
>0
ACTIVE POINT – INACTIVE INPUT
6.25% OF ACTIVE INPUT
Figure 23. Fault Conditions for Active Input Greater than Inactive Input
FAULT DETECTION
Fault with Inactive Input Greater than Active Input
The ADE7760 incorporates a novel fault detection scheme that
warns of fault conditions and allows the ADE7760 to continue
accurate billing during a fault event. The ADE7760 does this by
continuously monitoring both the phase and neutral (return)
currents. A fault is indicated when these currents differ by more
than 6.25%. However, even during a fault, the output pulse rate
on F1 and F2 is generated using the larger of the two currents.
Because the ADE7760 looks for a difference between the voltage
signals on V1A and V1B, it is important that both current
transducers be closely matched.
On power-up, the output pulse rate of the ADE7760 is proportional to the product of the voltage signals on V1A and
Channel 2. If there is a difference of greater than 6.25% between
V1A and V1B on power-up, the fault indicator (FAULT) becomes
active after about 1 s. In addition, if V1B is greater than V1A, the
ADE7760 selects V1B as the input. The fault detection is
automatically disabled when the voltage signal on Channel 1 is
less than 0.3% of the full-scale input range. This eliminates false
detection of a fault due to noise at light loads.
Figure 24 illustrates another fault condition. If the difference
between V1B, the inactive input, and V1A, the active input (used
for billing), becomes greater than 6.25% of V1B, the FAULT
indicator goes active, and there is also a swap over to the V1B
input. The analog input V1B becomes the active input. Again,
there is a time constant of about 3 s associated with this swap.
V1A does not swap back to being the active channel until V1A is
greater than V1B and the difference between V1A and V1B—in this
order—becomes greater than 6.25% of V1A. The FAULT
indicator, however, becomes inactive as soon as V1A is within
6.25% of V1B. This threshold eliminates potential chatter
between V1A and V1B.
V1A
V1A
V1B
A
V1A
FILTER FAULT
AND
COMPARE
TO
MULTIPLIER
0V
V1N
AGND
V1A < 93.75% OF V1B
V1B
B
V1B
FAULT + SWAP
<0
>0
ACTIVE POINT – INACTIVE INPUT
6.25% OF INACTIVE INPUT
Figure 24. Fault Conditions for Inactive Input Greater than Active Input
Rev. 0 | Page 17 of 24
04434-0-029
F1 − F2 Frequency =
If V1A is the active current input (that is, is being used for
billing), and the voltage signal on V1B (inactive input) falls below
93.75% of V1A, the fault indicator becomes active. Both analog
inputs are filtered and averaged to prevent false triggering of
this logic output. As a consequence of the filtering, there is a
time delay of approximately 3 s on the logic output FAULT after
the fault event. The FAULT logic output is independent of any
activity on outputs F1 or F2. Figure 23 shows one condition
under which FAULT becomes active. Because V1A is the active
input and it is still greater than V1B, billing is maintained on V1A,
that is, no swap to the V1B input occurs. V1A remains the active
input.
04434-0-028
Note that if the on-chip reference is used, actual output
frequencies may vary from device to device due to reference
tolerance of ±8%.
ADE7760
Calibration Concerns
Typically, when a meter is being calibrated, the voltage and
current circuits are separated as shown in Figure 25. This means
that current passes through only the phase or neutral circuit.
Figure 25 shows current being passed through the phase circuit.
This is the preferred option, because the ADE7760 starts billing
on the input V1A on power-up. The phase circuit CT is connected to V1A in the diagram. Because there is no current in the
neutral circuit, the FAULT indicator comes on under these
conditions. However, this does not affect the accuracy of the
calibration and can be used as a means to test the functionality
of the fault detection.
IB
V1A
RF
CT
If the neutral circuit is chosen for the current circuit in the
arrangement shown in Figure 25, this may have implications for
the calibration accuracy. The ADE7760 powers up with the V1A
input active as normal. However, because there is no current in
the phase circuit, the signal on V1A is zero. This causes a fault to
be flagged and the active input to be swapped to V1B (neutral).
The meter can be calibrated in this mode, but the phase and
neutral CTs might differ slightly. Because under no-fault conditions all billing is carried out using the phase CT, the meter
should be calibrated using the phase circuit. Of course, both
phase and neutral circuits can be calibrated.
RB
V1A
CF
RB
0V
CF
AGND
CT
RF
RA*
RB*
V1B
CF
V2P
VR*
V2N
RF
V
04434-0-030
PHASE
TEST
CURRENT
NEUTRAL
V1N
IB
CT
240V RMS
*RB + VR = RF
Figure 25. Fault Conditions for Inactive Input Greater than Active Input
Rev. 0 | Page 18 of 24
ADE7760
APPLICATIONS
INTERFACING TO A MICROCONTROLLER FOR
ENERGY MEASUREMENT
The easiest way to interface the ADE7760 to a microcontroller
is to use the CF high frequency output with the output frequency scaling set to 2048 × F1, F2. This is done by setting
SCF = 0 and S0 = S1 = 1 (see Table 7). With full-scale ac signals
on the analog inputs, the output frequency on CF is approximately 5.5 kHz. Figure 26 illustrates one scheme that could be
used to digitize the output frequency and carry out the
necessary averaging mentioned in the previous section.
CF
FREQUENCY
RIPPLE
AVERAGE
FREQUENCY
TIME
MCU
COUNTER
CF
FAULT**
Table 8. F1 and F2 Frequency at 100 Impulses/kWh
UP/DOWN
LOGIC
*REVP MUST BE USED IF THE METER IS BIDIRECTIONAL OR
DIRECTION OF ENERGY FLOW IS NEEDED.
**FAULT MUST BE USED TO RECORD ENERGY IN FAULT CONDITION.
04434-0-035
REVP*
Figure 26. Interfacing the ADE7760 to an MCU
As shown, the frequency output CF is connected to an MCU
counter or port, which counts the number of pulses in a given
integration time, determined by an MCU internal timer. The
average power, proportional to the average frequency, is given
by
Average Frequency = Average Active Power =
Counter
Timer
The energy consumed during an integration period is given by
Energy = Average Power × Time =
SELECTING A FREQUENCY FOR AN ENERGY
METER APPLICATION
As shown in Table 5, the user can select one of four frequencies.
This frequency selection determines the maximum frequency
on F1 and F2. These outputs are intended to be used to drive the
energy register (electromechanical or other). Because only four
different output frequencies can be selected, the available
frequency selection has been optimized for a meter constant of
100 impulses/kWh with a maximum current of between 10 A
and 120 A. Table 8 shows the output frequency for several
maximum currents (IMAX) with a line voltage of 240 V. In all
cases, the meter constant is 100 impulses/kWh.
±10%
ADE7760
For the purpose of calibration, this integration time could be
10 s to 20 s in order to accumulate enough pulses to ensure
correct averaging of the frequency. In normal operation, the
integration time could be reduced to 1 s or 2 s depending, for
example, on the required update rate of a display. With shorter
integration times on the MCU, the amount of energy in each
update might still have a small amount of ripple, even under
steady load conditions. However, over a minute or more, the
measured energy has no ripple.
Counter
× Time = Counter
Time
IMAX
12.5 A
25 A
40 A
F1 and F2 (Hz)
0.083
0.166
0.266
60 A
80 A
0.4
0.533
120 A
0.8
The F1–4 frequencies allow complete coverage of this range of
output frequencies on F1 and F2. When designing an energy
meter the nominal design voltage on Channel 2 (voltage)
should be set to half-scale to allow for calibration of the meter
constant. The current channel should also be no more than halfscale when the meter sees maximum load. This accommodates
overcurrent signals and signals with high crest factors. Table 9
shows the output frequency on F1 and F2 when both analog
inputs are half-scale. The frequencies listed in Table 9 align well
with those listed in Table 8 for maximum load.
Rev. 0 | Page 19 of 24
ADE7760
No-Load Threshold
Table 9. F1 and F2 Frequency with Half-Scale AC Inputs
S0
0
0
1
1
S1
0
1
0
1
F1-4
1.72
3.44
6.86
13.5
Frequency on F1 and F2,
CH1 and CH2,
Half-Scale AC Inputs
0.085 Hz
0.17 Hz
0.34 Hz
0.68 Hz
When selecting a suitable F1–4 frequency for a meter design, the
frequency output at IMAX (maximum load) with a meter constant
of 100 impulses /kWh should be compared with Column 4 of
Table 9. The frequency that is closest in Table 9 determines the
best choice of frequency (F1–4). For example, if a meter with a
maximum current of 40 A is being designed, the output
frequency on F1 and F2 with a meter constant of
100 impulses /kWh is 0.266 Hz at 40 A and 240 V (from
Table 8). Looking at Table 9, the closest frequency to 0.266 Hz
in Column 4 is 0.17 Hz. Therefore, F2 (3.4 Hz; see Table 5) is
selected for this design.
Frequency Outputs
Figure 2 shows a timing diagram for the various frequency
outputs. The high frequency CF output is intended to be used
for communications and calibration purposes. CF produces a
90 ms wide, active high pulse (t4) at a frequency that is proportional to active power. The CF output frequencies are given in
Table 7. As in the case of F1 and F2, if the period of CF (t5) falls
below 180 ms, the CF pulse width is set to half the period. For
example, if the CF frequency is 20 Hz, the CF pulse width is
25 ms.
The ADE7760 also includes a no-load threshold and startup
current feature that eliminates any creep effects in the
meter. The ADE7760 is designed to issue a minimum output
frequency. Any load generating a frequency lower than this
minimum frequency does not cause a pulse to be issued on F1,
F2, or CF. The minimum output frequency is given as 0.0045%
of the full-scale output frequency. (See Table 7 for maximum
output frequencies for ac signals.)
For example, an energy meter with a meter constant of
100 impulses /kWh on F1, F2 using SCF = 1, S1 = 0, and S0 = 1,
the maximum output frequency at F1 or F2 would be 0.68 Hz
and 43.52 Hz on CF. The minimum output frequency at F1 or
F2 would be 0.0045% of 0.68 Hz or 3.06 × 10–5 Hz. This would
be 1.96 × 10–3 Hz at CF (64 × F1 Hz). In this example, the noload threshold would be equivalent to 1.1 W of load or a startup
current of 4.6 mA at 240 V. Compare this value to the IEC61036
specification, which states that the meter must start up with a
load equal to or less than 0.4% IB. For a 5 A (IB) meter, 0.4% of IB
is equivalent to 20 mA.
Note that the no-load threshold is not enabled when using the
high CF frequency mode: SCF = 0, S1 = S0 = 1.
NEGATIVE POWER INFORMATION
The ADE7760 detects when the current and voltage channels
have a phase shift greater than 90°. This mechanism can detect
wrong connection of the meter or generation of negative power.
The REVP pin output goes active high when negative power is
detected and active low, when positive power is detected. The
REVP pin output changes state as a pulse is issued on CF.
Rev. 0 | Page 20 of 24
ADE7760
OUTLINE DIMENSIONS
7.50
7.20
6.90
20
11
1
10
2.00 MAX
0.65
BSC
0.05 MIN
COPLANARITY
0.10
1.85
1.75
1.65
0.38
0.22
5.60
5.30
5.00 8.20
7.80
7.40
0.25
0.09
SEATING
PLANE
8°
4°
0°
0.95
0.75
0.55
COMPLIANT TO JEDEC STANDARDS MO-150AE
Figure 27. 20-Lead Shrink Small Outline Package [SSOP]
(RS-20)
Dimensions shown in millimeters
ORDERING GUIDE
Model
ADE7760ARS
ADE7760ARSRL
Temperature Range
–40°C to +85°C
–40°C to +85°C
Package Description
20-Lead Shrink Small Outline Package [SSOP]
20-Lead Shrink Small Outline Package [SSOP]
Rev. 0 | Page 21 of 24
Package Option
RS-20
RS-20
ADE7760
NOTES
Rev. 0 | Page 22 of 24
ADE7760
NOTES
Rev. 0 | Page 23 of 24
ADE7760
NOTES
© 2004 Analog Devices, Inc. All rights reserved. Trademarks and
registered trademarks are the property of their respective owners.
D04434–0–1/04(0)
Rev. 0 | Page 24 of 24
Similar pages