FLLD3 … PV High current 3-phase EMC Filter Overview The three phase filter series is intended to be used in energy conversion inverter systems (e.g. photo voltaic and wind power), between the inverter and the line or in motor drive systems. The filters are optimized for geometry and power loss. Technical specifications Rated voltage Rated frequency Rated current Leakage current Rated temperature Temperature range Climate category Voltage test 520 VAC 50-60 Hz 250 – 2500 A < 5 mA *) 50°C -40°C to +100°C 40/100/21 P -> P 2250 VDC (520 VAC) P -> E 3000 VDC (520 VAC) The FLLD3…PV series is designed according to IEC/EN 60939 and UL 1283. *) Maximum leakage current under normal operating conditions. If two phases are interrupted, leakage current can be much higher. Filters without Y-capacitors have no leakage current. Rated current @ 50°C (A) 250 320 400 600 800 1000 1600 2500 Part Number FLLD3250AP-I1 FLLD3320AP-I1 FLLD3400AP-I1 FLLD3600AP-I1 FLLD3800AP-I1 FLLD31K0AP-I1 FLLD31K6AP-I1 FLLD32K5AP-I1 Power loss @ 25°C/50Hz (W) 15 15 25 40 50 75 130 230 Weight (kg) 7 10 10 11 17 17 26 55 V = 520VAC X = 520VAC without Y-capacitors Typical insertion loss 250 to 1000 A Asym Sym Asym no Y-cap 100 100 90 90 80 80 70 70 Attenuation (db) Attenuation (db) Sym 1600 and 2500 A 60 50 40 30 Asym no Y-cap 60 50 40 30 20 20 10 10 0 0 0.01 Asym 0.1 1 Frequency (MHz) November 2015 10 100 0.01 0.1 1 Frequency (MHz) 10 100 KEMET EMC Filters 1 FLLD3 … PV High current 3-phase EMC Filter Mechanical dimensions Z L Z W M U U ØN ØN H Y ØN K K I X J I 250 to 1000 A J I 1600 A 2500 A W1 W2 L1 Part Number FLLD3250APVI1 FLLD3320APVI1 FLLD3400APVI1 FLLD3600APVI1 FLLD3800APVI1 FLLD31K0APVI1 FLLD31K6APVI1 FLLD32K5APVI1 L1 L 300 300 300 300 350 350 400 450 Ø12 (x6) W 180 210 210 210 230 230 250 300 H 125 115 115 135 170 170 160 220 L1 120 120 120 120 145 145 170 200 W1 205 235 235 235 255 255 275 330 Dimensions in mm W2 U X Y 230 55 5 20 260 60 6 25 260 60 6 25 260 60 8 25 280 60 8 40 280 60 8 40 300 60 10 60 370 100 15 80 Z 45 45 45 45 55 55 95 110 I 15 15 15 15 20 20 17 20 J K 26 35 26 35 N 9 10.5 10.5 10.5 14 14 14 14 M M10 M12 M12 M12 M12 M12 M12 M12 Tolerances, if not stated, according to: ISO 2768-m Legal disclaimer notice All product specifications, statements, information and data (collectively, the “information”) are subject to change without notice. products is given gratis, and we assume no obligation or liability for the advice given or results obtained. All information given herein is believed to be accurate and reliable, but is presented without guarantee, warranty, or responsibility of any kind, expressed or implied. Although we design and manufacture our products to the most stringent quality and safety standards, given the current state of the art, isolated component failures may still occur. Accordingly, customer applications which require a high degree of reliability or safety should employ suitable designs or other safeguards (such as installation of protective circuitry or redundancies) in order to ensure that failure of an electrical component does not result in a risk of personal injury or property damage. Statements of suitability for certain applications are based on our knowledge of typical operating conditions for such applications, but are not intended to constitute – and we specifically disclaim – any warranty concerning suitability for a specific customer application or use. This information is intended for use only by customers who have the requisite experience and capability to determine the correct products for their applications. Any technical advice inferred from this information or otherwise provided by us with reference to the use of our November 2015 Although all product-related warnings, cautions and notes must be observed, the customer should not assume that all safety measures are indicated or that other measures may not required KEMET EMC Filters 2