Mean Well DRP-480S 480w single output din rail with pfc function Datasheet

D R P - 4 8 0 S series
480W Single Output DIN RAIL with PFC Function
Features :
AC input range selectable by switch
Built-in passive PFC function compliance to EN61000-3-2
High efficiency 89% and low dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
OUTPUT
DRP-480S-24
DRP-480S-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
RIPPLE & NOISE (max.) Note.2 120mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
0.5%
LOAD REGULATION
1.0%
1.0%
SETUP, RISE TIME
1200ms, 40ms/230VAC,115VAC at full load
HOLD UP TIME (Typ.)
23ms/230VAC,115VAC at full load
VOLTAGE RANGE
90 ~ 132VAC/180 ~ 264VAC by switch
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
INPUT
89%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
8A/115VAC
3.2A/230VAC
COLD START 27A/115VAC
45A/230VAC
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
NOTE
0.7/230VAC only
EFFICIENCY (Typ.)
LEAKAGE CURRENT
OTHERS
254 ~ 370VDC
<3.5mA / 240VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
59 ~66V
30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
100
5 (TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
EMC IMMUNITY
MTBF
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
187.9Khrs min. MIL-HDBK-217F (25 )
DIMENSION
PACKING
227*125.2*100mm (W*H*D)
2.6Kg; 6pcs / 16.6Kg / 1.75CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DRP-480S-SPEC 2011-06-17
D R P - 4 8 0 S series
480W Single Output DIN RAIL with PFC Function
Mechanical Specification
Case No.930
100
Unit:mm
56.6
227
125.2
12
10 6
230VAC
115VAC
TB1
3 2 1
LED
TB2
4 3 2 1
+V ADJ.
Terminal Pin No. Assignment (TB1)
Pin No.
1
2
3
35
ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
Block Diagram
fosc : 70KHz
EMI
FILTER
RECTIFIERS
&
FILTER
PASSIVE
PFC
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
O.L.P.
O.T.P.
CURRENT
LIMIT
PWM
CONTROL
Derating Curve
O.V.P.
Output Derating VS Input Voltage
100
100
180 ~ 264VAC
90 ~ 132VAC
90
80
80
70
LOAD (%)
60
LOAD (%)
Assignment
DC OUTPUT +V
DC OUTPUT -V
230
115
I/P
40
20
-20
Assignment
AC/L(DC+)
AC/N(DC-)
FG
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
60
50
40
90
180
100
190
115
230
132
264
INPUT VOLTAGE (V) 60Hz
File Name:DRP-480S-SPEC 2011-06-17
Similar pages