MTU ADG152DGB Diesel generator set Datasheet

A TOGNUM GROUP BRAND
DIESEL GENERATOR SET
TYPE ADG152D
144 kVA/Prime/50Hz
(152 kVA/LTP/50Hz)
Optional equipment shown. Standard equipment may vary.
BENEFITS
// Most compact design
// Air cooled engine — trouble-free
// Lowest maintenance cost
// High
user-friendlyness
cooling system
SYSTEM RATINGS➀
Prime (LTP)➁
ADG152D
ADG152D
ADG152D
Voltage (L-L)
Phase
PF
Hz
kWe
kVA
AMPS
Generator model
Temp rise
Load acceptance
380V
3
0.8
50
115.2 (121.6)
144 (152)
219
ACG-0152-4-400
125°C (150°C)
52%
400V
3
0.8
50
115.2 (121.6)
144 (152)
208
ACG-0152-4-400
125°C (150°C)
52%
415V
3
0.8
50
115.2 (121.6)
144 (152)
200
ACG-0152-4-400
125°C (150°C)
52%
➀ Power available up to 25°C/100 m
➁ Technical data for prime power
2 / // / 50 Hz 144 kVA
CERTIFICATIONS AND STANDARDS
// Engine-generator
set is designed and manufactured in
facilities certified to standards ISO 9001:2008
// Performance Assurance Certification (PAC)
- Engine-generator set tested to ISO 8528-5 for
transient response
- Verified product design, quality and performance integrity
- All generator sets are type and factory tested
// Power
Rating
- Permissible average power output during 24 hours of
operation is approved up to 75% for prime power rating
- Permissible average power output during 24 hours of
operation is approved up to 100% for limited time power
rating. Operating hours are limited to 500 hours per year.
STANDARD EQUIPMENT➀
// Engine
// Generator
Air cleaners
Oil pump
Oil drain extension & S/O valve
Full pre-filter with water seperator
Full flow oil filters
Exhaust manifold – dry
Blower fan & fan drive
Electric starting motor – 12V
Governor – mechanical
SAE flywheel
Flexible fuel connectors
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
VDE 0530, IEC 34.1, BS5000, CSA C22.2-100, AS1359
Self-ventilated
Superior voltage waveform
No load to full load regulation
125°C prime temperature rise (insulation class H)
1 bearing, sealed
Full amortisseur windings
125% rotor balancing
3-phase voltage sensing
Automatic voltage regulator ± 0,5%
➀ Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.
3 / // / 50 Hz 144 kVA
STANDARD FEATURES➀
// The generator set complies to G2
// Engine-generator set tested to ISO
// Self-exited
generator
- Brushless, rotating field generator
- 300% short circuit capability
- 2/3 pitch windings
// Cooling system 50°C
- Integral set-mounted
- Engine driven fan
8528-5 for transient
response
// MTU Onsite Energy is a single source
// Global product support
// 2 year standard warranty
// BF6L 914C diesel engine — 4-cycle
// Engine-generator resilient mounted
supplier
APPLICATION DATA
// Engine
// Fuel
Manufacturer
Model➁
Type
Arrangement
Displacement
Bore: cm
Stroke: cm
Compression ratio
Rated RPM (speed)
Engine governor
Gross power: kWm➁
Aspiration
// Lubrication
Deutz
BF6L 914C
4-cycle
6/in-line
6.47 l
10.2
13.2
18 :1
1,500
Mechanical
127.6 kW
Turbo charged with charge air cooler
Consumption and Fuel Tank Capacity
At 100% load
At 75% load
At 50% load
At 25% load
Capacity of base frame fuel tank (open set)
Capacity of base frame fuel tank (sound proof)
// Cooling
System
Max. ambient temperature: °C
Fan power consumption: kW
Cooling air flow: m3/h
Air pressure loss: mbar
Oil capacity (sump) min./max.
Lube oil consumption (in % of fuel cons.)
Oil pressure min. (warning): bar
Oil pressure min. (shut-down): bar
Max. oil temperature: °C
16 l
0.5
1.5
1.5
135
System
Recommended fuel
// Heat
PRIME➁
50
1.6
4475
10
System
// Combustion
// Fuel
PRIME➁
31.8 l/h (211 g/kWh)
23.7 l/h (210 g/kWh)
16.4 l/h (218 g/kWh)
9.7 l/h (259 g/kWh)
240 l
240 l
Rejection
Engine radiation and ronvection: kW
Heat rejection of generator: kW
3/
Combustion air volume: m h
Max. air intake restriction: mbar
Air cleaner type
// Exhaust
see MTU fluids & lubrication spec.
Air
PRIME➁
453
20
Dry, replaceable element
with safety catridge
System
Max. exhaust gas temperature: °C
Max. exhaust back pressure: mbar
Exhaust Gas Flow: m3/h
PRIME➁
approx. 63
approx. 11.5
➀ Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.
➁ Technical data for prime power
PRIME➁
560
30
1287
4 / // / 50 Hz 144 kVA
WEIGHTS AND DIMENSIONS
1110
1874
2487
Drawing above for illustration purposes only, based on standard sound proof 400 volt engine-generator set. Do not use for installation design. See website for unit specific template
drawings.
System
Sound Proof Unit (SPU)
Dimensions (L x W x H)
2487 x 1110 x 1874 mm
Weight (dry/less tank)
approx. 1767 kg
NOISE EMISSION (SOUND PROOF)
Sound power LWA: dB(A)
Sound power LPA@1m: dB(A)
Sound power LPA@7m: dB(A)
95
78
66
RATING DEFINITIONS AND CONDITIONS
power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO 3046-1, BS 5514, AS 2789, and DIN 6271.
// Limited time power ratings apply to installations served by a reliable utility source. The standby rating is applicable to constant
or varying loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with
ISO 8528-1, ISO 3046-1, BS 5514, AS 2789 and DIN 6271.
// Deration factor:
Altitude: Consult your local MTU Onsite Energy distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy distributor for temperature derations.
Materials and specifications subject to change without notice.
// A Tognum Group Company: MTU Onsite Energy Systems GmbH / 94099 Ruhstorf / Germany / Phone + 49 8531 97 82-0 / Fax + 49 8531 97 82-1510 /
[email protected] /www.mtuonsiteenergy.com
Subject to change. | 3236421 | Edition 01/13 | VMC 2013-06.
// Prime
Similar pages