HRP-450 450W Single Output with PFC Function series Features : Universal AC input / Full range Built-in active PFC function, PF>0.95 High efficiency up to 89.5% Withstand 300VAC surge input for 5 seconds Protections: Short circuit / Overload / Over voltage / Over temperature Built-in constant current limiting circuit Built-in cooling Fan ON-OFF control Built-in DC OK signal Built-in remote sense function 5 years warranty SPECIFICATION MODEL OUTPUT HRP-450-3.3 HRP-450-5 HRP-450-7.5 HRP-450-12 HRP-450-15 HRP-450-24 HRP-450-36 DC VOLTAGE 3.3V 5V 7.5V 12V 15V 24V 36V 48V RATED CURRENT 90A 90A 60A 37.5A 30A 18.8A 12.5A 9.5A CURRENT RANGE 0 ~ 90A 0 ~ 90A 0 ~ 60A 0 ~ 37.5A 0 ~ 30A 0 ~ 18.8A 0 ~ 12.5A 0 ~ 9.5A RATED POWER 297W 450W 450W 450W 450W 451.2W 450W 456W RIPPLE & NOISE (max.) Note.2 80mVp-p 80mVp-p 100mVp-p 120mVp-p 150mVp-p 150mVp-p 240mVp-p 240mVp-p VOLTAGE ADJ. RANGE 4.3 ~ 5.8V 2.0% 6.8 ~ 9V 2.0% 10.2 ~ 13.8V 1.0% 13.5 ~ 18V 1.0% 21.6 ~ 28.8V 1.0% 28.8 ~ 39.6V 1.0% 40.8 ~ 55.2V 1.0% VOLTAGE TOLERANCE Note.3 2.8 ~ 3.8V 2.0% LINE REGULATION 0.5% 0.5% 0.5% 0.3% 0.3% 0.2% 0.2% 0.2% LOAD REGULATION 1.0% 1.0% 1.0% 0.5% 0.5% 0.5% 0.5% 0.5% SETUP, RISE TIME 1000ms, 100ms/230VAC HOLD UP TIME (Typ.) 16ms/230VAC 120 ~ 370VDC POWER FACTOR (Typ.) PF>0.95/230VAC EFFICIENCY (Typ.) 80% 83% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 5A/115VAC 35A/115VAC 2.4A/230VAC 70A/230VAC LEAKAGE CURRENT <1.5mA / 240VAC OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE FUNCTION 2500ms, 100ms/115VAC at full load 16ms/115VAC at full load VOLTAGE RANGE Note.5 85 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz INPUT HRP-450-48 PF>0.99/115VAC at full load 86.5% 88% 89% 88% 105 ~ 135% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 6 ~ 7V 9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V 3.96 ~ 4.62V 89% 89.5% 41.4 ~ 48.6V 57.6 ~ 67.2V Protection type : Shut down o/p voltage, re-power on to recover 90 5 (70 5 5V only) (TSW1 : detect on heatsink of power transistor) ; 90 5 (TSW2 : detect on heatsink of power doide ) DC OK SIGNAL Protection type : Shut down o/p voltage, recovers automatically after temperature goes down PSU turn on : 3.3 ~ 5.6V ; PSU turn off : 0 ~ 1V FAN CONTROL (Typ.) Load 20 10% or RTH2 WORKING TEMP. -40 ~ +70 50 Fan on (Refer to output load derating curve) 20 ~ 90% RH non-condensing WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH TEMP. COEFFICIENT 0.03%/ (0 ~ 50 ) VIBRATION 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes SAFETY STANDARDS WITHSTAND VOLTAGE SAFETY & EMC (Note 4) ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B HARMONIC CURRENT OTHERS / 70% RH EMS IMMUNITY Compliance to EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2, heavy industry level, criteria A MTBF 139.9K hrs min. DIMENSION 218*105*41mm (L*W*H) 1.19Kg; 12pcs/15.3Kg/0.82CUFT PACKING NOTE UL60950-1, TUV EN60950-1 approved I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC MIL-HDBK-217F (25 ) 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com) 5. Derating may be needed under low input voltages. Please check the derating curve for more details. 6. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time. File Name:HRP-450-SPEC 2010-11-29 HRP-450 450W Single Output with PFC Function Mechanical Specification Case No. 995A Unit:mm 32.8 20.75 152.4 series O/P 11 1 2 4 I/P 105 3 63.5 FAN 9.2 Air flow direction 8.2 5 6 1 10 2 13 4-M4 L=5 3 218 32.8 152.4 18max. LED (Vo ADJ.)SVR1 CN100 24 12.5 41 18 12max. AC Input Terminal Pin No. Assignment Pin No. 1 2 3 8-M4 L=4 (Both Sides) Connector Pin No. Assignment(CN100) : HRS DF11-4DP-2DS or equivalent DC Output Terminal Pin No. Assignment Pin No. 1~3 4~6 Assignment AC/L AC/N FG Pin No. 1 2 Assignment -V +V Assignment DC-OK GND +S -S 3 4 Mating Housing Terminal HRS DF11-4DS HRS DF11-**SC or equivalent or equivalent Block Diagram PMW fosc : 70KHz I/P +S ACTIVE INRUSH CURRENT LIMITING EMI FILTER RECTIFIERS & PFC RECTIFIERS & FILTER POWER SWITCHING +V -V -S DETECTION CIRCUIT O.L.P. O.T.P. FG PFC CONTROL O.T.P. PWM CONTROL Derating Curve DC OK O.V.P. Output Derating VS Input Voltage Ta = 25 100 125 90 100 80 70 LOAD(%) LOAD (%) 80 50 20 -40 0 10 20 30 40 50 AMBIENT TEMPERATURE ( ) 60 70 (HORIZONTAL) 60 50 40 85 100 125 135 155 264 INPUT VOLTAGE (V) 60Hz File Name:HRP-450-SPEC 2010-11-29 HRP-450 450W Single Output with PFC Function series Function Description of CN100 Pin No. Function Description DC-OK DC-OK Signal is a TTL level signal, referenced to pin2(DC-OK GND). High when PSU turns on. 1 GND This pin connects to the negative terminal(-V). Return for DC-OK signal output. 2 Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to 3 +S minimize noise pick-up effect. The maximum line drop compensation is 0.5V. 4 -S Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V. Function Manual 1.Remote Sense The remote sensing compensates voltage drop on the load wiring up to 0.5V. CN100 2 4 CN100 1 3 2 GND DC-OK 1 4 +S (Pin3) - + LOAD Fig 1.1 2.DC-OK Signal DC-OK signal is a TTL level signal. High when PSU turns on. Between DC-OK(pin5) and GND(pin6) Output Status 3.3 ~ 5.6V ON 0 ~ 1V OFF -S +S 3 -S (Pin4) Sense lines should be twisted in pairs CN100 2 4 CN100 1 3 2 4 GND DC-OK -S +S 1 3 Fig 2.1 File Name:HRP-450-SPEC 2010-11-29