Lineage Power EP0300 300w output at 48-58vdc Datasheet

EP0300AC48TEZ
300W Output at 48-58Vdc
Product Description
Key Features
The rectifier EP0300AC48TE is a compact, single phase, hotpluggable, fan-cooled rectifier and battery charger for standalone use or for working in parallel as part of a DC power system
equipped with advanced digital controller. The constant output
power (300W i.e. 5.5A at 54V) characteristic supplies the specified
power over the full output voltage range (48 to 58Vdc).
Efficient rectifier
There is a digital communication (RS-485 bus) between rectifier
and controller which allows flexible system design.
>90%
Rugged rectifier
Exclusively designed to take care of wide line fluctuations and harsh
conditions
¾ Can withstand up to 300Vac (Line-Neutral) without any
damage
¾ Can work up to +75°C
Optimum power performance
Constant power between 90V … 290V ac
Compact and light
3 rectifiers can be accommodated in one row (19” shelf) with
controller and distribution
Applications
The typical applications for this rectifier are both in indoor and
outdoor environments and include:
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
SCADA/ DMS System
EPBAX
Broadband
IP telephony
Cable Television
LTE
GPON
Enterprise solution
See reverse side for specifications
Technical Specifications
Input Parameters
Operating Voltage range
Full Power input voltage
Range
Other Parameters
90-290 Vac
Disconnect: < 90Vac & > 290Vac
No damage up to 300Vac
90-290 Vac
Isolation
Visual Indications
Frequency
Maximum Current
45 to 65Hz
4A (rms) 230Vac,100% load
Power Factor
> 0.99 at 230Vac,100% load
Total Current Harmonic
Distortion (THD)
Efficiency
Input protection
< 10% at 230Vac,100% load
≥ 90%. 230Vac,100% load
In built surge protection (2kV/3kA)
Inline fuse
Operating temp
3.0 kVac – I/P & O/P
1.5 kVac – input & earth
0.5 kVac – output & earth
Normal LED (Green):
3 status (Blink, OFF, ON)
Fault LED (Red):
3 status (Blink, OFF, ON)
-25°C to +75°C
Power De-rating
+60°C to +75°C
Operating Humidity
5% to 95% RH non-condensing
> 150k hours Telcordia SR-332,
Method 1, Case 3 (Ambient
Temperature.: 25°C)
< 60dBA at an ambient noise level of
45dBA, and at ambient temperature
of 25°C
MTBF
Audible Noise
Mechanical
Width
50.4 mm (2”)
Output Parameters
Height
45 mm (1.75”)
Voltage, nominal
48 Vdc
Depth
228.6mm (9”)
Voltage adjust range
42 … 57 Vdc (controller)
300W
Weight
0.5 kg (1.1 lbs)
Rated output Power
Output Current @...V
5.5A@54V
Maximum current
6.25A
Static Voltage regulation
±1% from 10% to 100% load
Noise (Ripple + spikes)
≤ 100 mVrms
Load sharing
10%
I/P and O/P connector
Rear side
Over voltage shutdown
Blocking diode
Short circuit proof
Over temperature protection
Output protection
Note: As a result of continuous product improvement, all specifications are subject to change without prior notice. All performance parameters are valid at Nominal input (230Vac) and nominal output
(48Vdc) conditions unless otherwise specified.
Applicable Standards
Electrical safety
EMI
EMC
Harmonics
Environment
IEC 60950-1
UL 60950-1
CSA 22.2
As per CISPR-22
IEC 61000-4-5, (Surge immunity limits)
IEC 61000-4-6, (RF Conducted susceptibility immunity limits)
IEC 61000-4-3, (Radiated Electromagnetic Field immunity limits)
IEC 61000-4-4, (EFT/ Burst immunity limits)
IEC 61000-4-2, (ESD Immunity limits)
EN 61000-3-2
RoHS compliant
Ordering Information
Product
EP0300AC48TEZ
Description
48V, 300W rectifier
Comcode
150022411
Country of Sale
South Asia
SE Asia
NA
CALA
European
India
-
GE Critical Power reserves the right to make changes to the product (s) or information contained herein without notice. No liability is assumed as a result of their use or
application. No rights under any patent accompany the sale of any such product(s) or information.
© 2013 GE Critical Power (Bangalore, India) All Rights Reserved.
Document Rev No: R0.1 Date: 5th February 2013
PDF name: EP0300AC48TEZ PDS.pdf
Similar pages