POWER HPS3000 Series 3000 Watts Data Sheet Distributed Power Bulk Front-End Single Output SPECIAL FEATURES 3000 W output power 40 W/cu-in Optional customer provided air 1U x 3U form factor N+1 redundant Internal OR-ing 5 V housekeeping High efficiency 89% @ 200 Vac, 100% load Variable speed “smart fans” Two year warranty COMPLIANCE EMI Class A - EN55022 EN61000 Immunity SAFETY UL/cUL CSA Nemko CB Report 60950 60950 TUV Electrical Specifications Input Input range (operating) 180 - 264 Vac 90 - 140 Vac Nominal input 200 Vac 110 Vac Frequency 47 to 63 Hz Input fusing Internal 25 A fuses Both lines fused Inrush current ≤40 A peak Either hot or cold start Power factor 0.97 typical Meets EN61000-3-2 Harmonics Meets IEC 61000-3-2 requirements @ 50% load Input current 19 A max input current Holdup time 10 ms minimum At full rated load Leakage current 1.4 mA At 240 Vac Power line transient MOV directly after the fuse Input through Card Edge Connection on same end as DC output Note: HPS3000-9-001 variant available for applications with higher airflow requirements HPS3000 Series Data Sheet Output 48 V @ 62.0 A 5 Vsb @ 3.0 A 180 - 264 Vac 48 V @ 29.4 A 5 Vsb @ 3.0 A 90 - 140 Vac Set point Total regulation range 48 V Programmable 96-117% through I2C serial bus 48 V ± 5% 5 Vsb ± 4% Line/load/transient when measured at output connection Rated load 3000 W maximum @ 200 Vac Input 1500 W maximum @ 110 Vac Input No derating over operating temp range Minimum load 48 V @ 0.0 A 5 Vsb @ 0.0 A No loss of regulation Output noise 480 mV max P-P 100 mV max P-P 48 V output 5 Vsb output Measured with a 0.1μF Ceramic and 10 μF Tantalum capacitor on any input Output voltage overshoot ± 5% maximum Nominal Voltage Setting Transient response 5% maximum deviation 50% load step @ 1 A/us Step load valid between 10% to 100% of output rating. Max units in parallel Up to 4 Total power in 1U 19” rack is 12 KW Short circuit protection 120% - 130% of rated output Output to return Forced load sharing Within ± 6.25 A of all shared outputs Digital sharing control Overcurrent protection (OCP) 120% to 130% 110% to 140% 48 V output 5 Vsb output Overvoltage protection (OVP) 110% to 133% 110% to 125% 48 V output 5 Vsb output Overtemperature protection 10 - 15 deg C above safe operating area Both PFC and output converter monitored 5 Vsb will operate under overtemperature condition. Built in hysteresis Output rating Environmental Specifications Vibration/Shock Non-operational 5G Sine sweep from 5 Hz to 500 Hz, dwelling at resonant frequencies for 1 hour each Operating temperature - 10 ° to +40 °C Storage temperature - 40 ° to +85 °C Cooling External fans with Fan Fail and Fan Speed control Operating relative humidity 5% to 95% non-condensing Storage relative humidity 5% to 95% non-condensing Operating altitude Up to 10,000 feet above sea level Storage altitude Up to 30,000 feet above sea level RoHS compliant Yes HPS3000 Series Data Sheet Module Information (All units in mm) HPS3000-9 HPS3000 Series Data Sheet Module Information (All units in mm) HPS3000-9-001 HPS3000 Series Data Sheet Pin Assignments Bottom Pin 1 AC LINE 9 +48 Vdc out 17 +48 Vdc RTN 25 Reserved 2 AC LINE 10 +48 Vdc out 18 +48 Vdc RTN 26 PRESENT# 3 n.c. 11 +48 Vdc out 19 +48 Vdc RTN 27 DCOK/PWOK# 4 AC NEUTRAL 12 +48 Vdc out 20 +48 Vdc RTN 28 SDA 5 AC NEUTRAL 13 +48 Vdc out 21 +48 Vdc RTN 29 HVCC 6 n.c. 14 +48 Vdc out 22 +48 Vdc RTN 30 PSON# 7 n.c. 15 +48 Vdc out 23 n.c. 31 #ALERT 8 n.c. 16 +48 Vdc RTN 24 V_STBY 32 ISHARE Pin Assignments Top Pin 64 AC LINE 56 +48 Vdc out 48 +48 Vdc RTN 40 Reserved 63 AC LINE 55 +48 Vdc out 47 +48 Vdc RTN 39 ACOK# 62 n.c. 54 +48 Vdc out 46 +48 Vdc RTN 38 SMBUS_ALERT_OUT 61 AC NEUTRAL 53 +48 Vdc out 45 +48 Vdc RTN 37 SCL 60 AC NEUTRAL 52 +48 Vdc out 44 +48 Vdc RTN 36 A2 59 n.c. 51 +48 Vdc out 43 +48 Vdc RTN 35 PSKILL 58 n.c. 50 +48 Vdc out 42 n.c. 34 A1 57 n.c. 49 +48 Vdc RTN 41 SYS_GND 33 A0 HPS3000 Series Data Sheet Timing Diagram AC On AC Input AC On T PW OK_Off_ T Vout_Holdup Main Vout T PW OK_Off_ T AC_On_Delay T PW OK_Off_ T PW OK_On T PW OK_Off_ T PW OK_Off PWOK T PW OK_Delay T PW OK_On T PW OK_On T PSON_PWO K T sb_On 5 Vsb Vout T PSON_On_Delay T SB_Vout PS_ON T ACOK_Delay AC_OK AC Input ON / OFF Cycle PSON ON / OFF Cycle HPS3000 Series Data Sheet Timing Signal Definitions Turn ON/OFF Timing Item Description Tvout_rise 48 V Output rise time Min Max Units 5 300 msec Tsb_on_delay Tac_on_delay Delay from AC being applied to 5 Vsb being within regulation. 1500 msec Delay from AC being applied to all output voltages being within regulation. 2000 Tvout_holdup msec Time all output voltages, including 5 Vsb, stay within regulation after loss of AC. 10 msec Tpwok_holdup Delay from loss of AC to de-assertion of PWOK 5 msec Tpson_on_delay Delay from PSON# active to output voltages within regulation limits. 5 Tpson_pwok Delay from PSON# de-active to PWOK being de-asserted. Tacok_delay Delay from loss of AC input to de-assertion of ACOK#. 10 Tpwok_on Delay from output voltages within regulation limits to PWOK asserted at turn on. Tpwok_off Delay from PWOK de-asserted to 48 V dropping out of regulation limits. Tpwok_low Duration of PWOK being in the de-asserted state during an off/on cycle using AC or the PSON# signal. 100 Tsb_vout Delay from 5 Vsb being in regulation to 48 V being in regulation at AC turn on. 50 400 msec 50 msec 100 1000 msec 1 1000 msec msec msec 2000 msec Signals and Controls - All Models PSON# The PSON# signal is required to remotely turn on/off the power supply. PSON# is an active low signal that turns on the 48 V power rail. When this signal is not pulled low by the system, or left open, the 48 V output turns off. The 5 Vsb output remains on. This signal is pulled to a standby voltage by a pull-up resistor internal to the power supply. The power supply fan(s) shall operate at the lowest speed. PSON# Signal Characteristic Signal Type Accepts an open collector/drain input from the system. Pulled-up to the 5 Vsb located in power supply. PSON# = Low ON PSON# = Open Logic level low (power supply ON) Logic level high (power supply OFF) Source current, Vpson = low Power up delay: Tpson_on_delay OFF MIN MAX 0V 0.4 V 2.40 V 3.40 V -- 4 mA 5 msec 400 msec HPS3000 Series Data Sheet Signals and Controls - All Models PWOK# (Power Good) PWOK# is a power good signal and will be pulled LOW by the power supply to indicate that both the outputs are above the regulation limits of the power supply. When any output voltage falls below regulation limits or when AC power has been removed for a time sufficiently long so that power supply operation is no longer guaranteed, PWOK will be de-asserted to a HIGH state. The start of the PWOK# delay time shall be inhibited as long as the 48 V output is in current limit or the 5 Vsb output is below the regulation limit. PSON# Signal Characteristic Signal Type Open collector/drain output from power supply. Pullup to 5 Vsb external to the power supply. PWOK = High ON PWOK = LOW OFF MIN Logic level low voltage, Isink=4mA Logic level high voltage, Isource=200μA MAX 0V 0.8 V 2.0 V 4.80 V Sink current, PWOK = low 4 mA Source current, PWOK = high 2 mA PWOK delay: Tpwok on 100 msec 1000 msec PWOK rise and fall time Power down delay: Tpwok off 100 μsec 1 msec 1000 msec Power Supply Present Indicator (PRESENT#) The PRESENT# signal is primarily used to provide a mechanism by which the host system can sense the number of power supplies physically present (operational or not). This pin is connected to the standby ground in the power supply. AC INPUT Present Indicator (ACOK#) The AC OK# signal is used to indicate presence of AC input to the power supply. This signal shall be connected to 5 Vsb through a resistor on the host system side. A logic “Low” level on this signal shall indicate AC input to the power supply is present. A Logic “High” on this signal shall indicate a loss of AC input to the power supply. Table 12 ACOK# Signal Characteristics Signal Type Pull-up to 5 Vsb through a resistor in the host system. PRESENT# = Low Present PRESENT# = High Not present MIN MAX Logic level low voltage, Ising=4 mA 0V 0.8 V Logic level high voltage, Isink=50 μA 2.0 V 4.80 V Sink current, PRESENT# = Low 4 mA Source current, PRESENT# = High 50 μA HPS3000 Series Data Sheet Signals and Controls - All Models LED INDICATORS There will be a green POWER LED (PWR) to indicate that AC is applied to the PSU and standby voltage is available when blinking. This same LED should go solid when the 48 V output is enabled and operational. There will be an Amber Power Supply Fail LED (FAIL) to indicate that the power supply has failed and a replacement of the unit is necessary. Faults including UVP, OVP, OTP, or Fan Fail when PSON# is asserted “Logic Low” shall cause the amber LED to turn on. The LED can be turned off by recycling PSON# signal or by an AC power interruption more than 1 second. The LED shall be off when PSON# is not asserted “Logic Low”. Refer to table 13 for conditions of the LED’s: Table 13 LED Indicators Power Supply Condition Power LED (GREEN) Fail LED (AMBER) No AC power to PSU OFF OFF Blinking OFF Power supply 48 V output ON and OK ON OFF Power supply failure (includes overvoltage, overtemperature) OFF ON Current limit ON Blinking AC present / Standby Output On MTBF The power supply has a minimum MTBF of 300K hours using the Bell core 332, issue 6 specification @ 25 °C and 40 °C, ambient, at full load. With the power supply installed in a system in a 25 °C ambient environment and operating at full load, capacitor life shall be 10 years, minimum for ALL electrolytic capacitors contained within this power supply. The power supply shall demonstrate a MTBF level of > 500,000 hours. Quality Assurance Full QAV testing shall be conducted in accordance with Artesyn Embedded Technologies Standards with reports available upon request. Warranty Artesyn Embedded Technologies shall warrant the power supply to be free of defects in materials and workmanship for a minimum period of two years from the date of shipment, when operated within specifications. The warranty shall be fully transferable to the end owner of the equipment powered by the supply. Ordering Information Model Number Main Output Main Output Current Standby Output Standby Current HPS3000-9 48 Vdc 62.0 A 5.0 V 3.0 A HPS3000-9-001 48 Vdc 62.0 A 5.0 V 3.0 A Note: HPS3000-9-001 version is recommended for applications where higher airflow is required. WORLDWIDE OFFICES Americas Europe (UK) Asia (HK) 2900 S.Diablo Way Tempe, AZ 85282 USA +1 888 412 7832 Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom +44 (0) 1384 842 211 14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong +852 2176 3333 Artesyn Embedded Technologies, Artesyn and the Artesyn Embedded Technologies logo are trademarks and service marks of Artesyn Embedded Technologies, Inc. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. © 2016 Artesyn Embedded Technologies, Inc. All rights reserved. For full legal terms and conditions, please visit www.artesyn.com/legal. www.artesyn.com For more information: www.artesyn.com/power For support: [email protected] HPS3000 Series DS 26Apr2016