Chinfa DRD30-05 Ac - dc din rail mountable power supply industrial control equipment Datasheet

DRD30 SERIES
DC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧4:1 WIDE INPUT RANGE
‧SHORT CIRCUIT PROTECTION
‧INTERNAL INPUT FILTER
‧REMOTE ON / OFF
‧LOW PROFILE
‧3 YEARS WARRANTY
Vo
C
a
US
UL 60950-1
EN 60950-1
MODEL LIST
MODEL NO.
IND. CONT. EQ.
UL 508
INPUT
INPUT
OUTPUT OUTPUT OUTPUT
CURRENT
VOLTAGE (typ.) (max.) WATTAGE VOLTAGE CURRENT
EFF.
(min.)
EFF.
(typ.)
79%
80%
81%
82%
83%
81%
82%
83%
84%
85%
max.
unit
200
KHz
VDC
Single Output Models
DRD30-05
DRD30-09
DRD30-12
DRD30-15
DRD30-24
10-36 VDC
10-36 VDC
10-36 VDC
10-36 VDC
10-36 VDC
1.13 A
1.25 A
1.48 A
1.48 A
1.48 A
3.1 A
3.4 A
4A
4A
4A
22.5 WATTS
25 WATTS
30 WATTS
30 WATTS
30 WATTS
+ 5 VDC
+ 9 VDC
+ 12 VDC
+ 15 VDC
+ 24 VDC
4.5 A
2.8 A
2.5 A
2A
1.25 A
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
GENERAL
Characteristics
Switching frequency
Isolation voltage
Isolation resistance
Ambient temperature
Derating (see derating curve)
Storage temperature
Relative humidity
Temperature coefficient
100
-40
Altitude during operation
IEC 60068-2-13
MΩ
o
C
% / oC
+ 71
2.5
+ 85
95
± 0.03
-40
20
Vi nom, Io nom
Vi nom, Io min
Bellcore Issue 6 @40 oC, GB
typ.
100
1,500
Vi nom, from +51 oC to +71 oC
Non operational
MTBF
Dimension
Cooling
Installation position
Pollution degree
min.
Conditions
Vi nom, Io nom
Input-Output
Input-Output, @ 500VDC
Operating at Vi nom
o
C
% RH
% / oC
722,000
689,000
712,000
738,000
756,000
5V
9V
12V
15V
24V
Hours
Hours
Hours
Hours
Hours
m
mm
4,850
L91 x W35 x D56.5
Free air convection
Vertical ( other direction may derating using )
2
INPUT SPECIFICATIONS
Characteristics
Input voltage range
No load input current
Input voltage w/o damage
Startup voltage
Input filter
www.chinfa.com
2016.04.18
Conditions
Ta min ... Ta max, Io nom
Vi nom, Io = 0
Io nom
Io nom
Pi type
min.
typ.
max.
unit
10
24
36
30
40
VDC
mA
VDC
VDC
9.6
[email protected]
P1
DRD30 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
OUTPUT SPECIFICATIONS
Characteristics
Conditions
Output voltage accuracy
Vi nom, Io max
Minimum load
Line regulation
Load regulation
Voltage trim range
Vi nom
Io nom, Vi min ...Vi max
Vi nom, Io min ...Io nom
Vi nom, 0.8 Io nom
Rated continuous loading
Vi nom
Startup time
Transient recovery time
Ripple & noise
Power back immunity
Vi nom, Io nom
Vi nom, 1~0.5 Io nom
Vi nom, Io nom, BW = 20MHz
Vi nom, Io nom
Capacitor load
Vi nom, Io nom
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
DC LOW indicator threshold
after start up (Red LED)
Vi nom, Io nom
Efficiency
Vi nom, Io nom, Po / Pi
typ.
min.
max.
unit
+1
%
%
%
%
VDC
VDC
VDC
VDC
VDC
0
0
5V
9V
12V
15V
24V
5V
9V
12V
15V
24V
±1
±1
5.5
4.75
8.55
9.9
13.8
11.4
16.5
14.25
27.6
22.8
4.5 A @ 5Vdc / 4 A @ 5.5 Vdc
2.8 A @ 9Vdc / 2.5 A @ 9.9 Vdc
2.5 A @ 12Vdc / 2.1 A @ 13.8 Vdc
2 A @ 15Vdc / 1.75 A @ 16.5 Vdc
1.25 A @ 24Vdc / 1.05 A @ 27.6 Vdc
ms
ms
50
1
100
5V
9V
12V
15V
24V
5V
9V
12V, 15V
24V
5V
9V
12V
15V
24V
5V
9V
12V
15V
24V
mV
VDC
VDC
VDC
VDC
VDC
μF
μF
μF
μF
7.5
15
18
22
35
3,500
2,200
1,000
470
4.5
VDC
3.5
VDC
6.8
8.1
VDC
10.8
9
VDC
13.5
11
VDC
19.2
21.6
4.5
VDC
3.5
VDC
6.8
8.1
VDC
10.8
9
VDC
13.5
11
VDC
19.2
21.6
Up to 85%, See model list and typ efficiency curve
CONTROL AND PROTECTION
Characteristics
typ.
min.
Conditions
Input fuse
Internal surge voltage protection
IEC 61000-4-5
Rated over load protection
Vi nom (see typ current limited curve)
Over voltage protection
Vi nom,0.8 Io nom
(Auto Recovery)
Remote ON / OFF
max.
unit
T6.3A / 125VDC internal
Varistor
110
145
%
5V
5.75
6.5
VDC
9V
10.35
11.7
VDC
12V
14.4
16.2
VDC
15V
17.25
19.5
VDC
24V
28.8
32.4
VDC
ON : opened or 8 ~ 10VDC applied, reference to input GND
OFF : -0.3 ~ 2VDC applied, reference to input GND
Output short circuit
Current limited (Auto-recovery)
Degree of protection
IP20
www.chinfa.com
2016.04.18
[email protected]
P2
DRD30 SERIES
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
APPROVALS AND STANDARDS
UL / cUL
UL 508
CTUVUS
UL 60950-1
TUV
EN 60950-1
CE
EN 61000-6-3, EN 55022 Class B
EN 61000-6-2, EN 55024, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4
EN 61000-4-5, EN 61000-4-6, EN61000-4-8, ENV 50204, EN 61204-3
Vibration resistance
meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
91 x 35 x 56.5 mm (3.58 x 1.38 x 2.22 inches)
Case size
Case material
Weight
Packing
Plastic
120g
0.16kg ; 88
/ 14kg / 1.82CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safely and
firmly on the rail; no tools required even to remove
INSTALLATION
Ventilation / Cooling
Normal convection
All sides 25m/m free space
For cooling recommended
Connector size range
AWG24-12 (0.2~2.5mm2) flexible / solid cable
-Connector can withstand torque at maximum
6 pound-inches.
7 m/m stripping at cable end recommends.
Use copper conductors only, 60/75 oC
Vo
GENERAL TOLERANCE
Vi
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
PIN ASSIGNMENT
1, 2
3, 4
Designation
OUT
PIN NO.
6
IN
5
OTHER
7
www.chinfa.com
2016.04.18
Description
-
Negative output terminal
+
Positive output terminal
ON / OFF
Remote ON / OFF terminal
+
Positive input terminal
-
Negative input terminal
Vout ADJ.
Trimmer-potentiometer for Vout adjustment
DC ON
Operation indicator LED
DC LO
DC Low indicator LED
[email protected]
P3
DRD30 SERIES
CIRCUIT SCHEMATIC
‧Block diagram for DRD30 series
Fuse
Vi +
Vo +
Line
Filter
Switching
Device
Rectifier
Vi -
Vo PWM
controller
ON / OFF
Opto Isolation
Reference &
Error Amp.
Opto Isolation
Over Voltage
Detection
Vout
ADJ.
Output Level
Detection
DC ON
(Green LED)
DC LO
(Red LED)
DERATING CURVE
Input Voltage : 11.5V ~ 28V
Input Voltage :
Power out [ % ]
100
50
50
Safe Operating Area
0
-40
51
Safe Operating Area
0
-40
71
71
o
Temperature [ C ]
Input Voltage : >28V but
51
-25
o
Temperature [ C ]
o
Ta : 50 C
36V
100
Power out [ % ]
100
Power out [ % ]
10V but <11.5V
100
Safe Operating Area
40
0
-40
41
80
Safe Operating Area
0
10
71
28
Input Voltage [ V ]
o
Temperature [ C ]
36
DERATING AND EFFICIENCY CURVE
Efficiency Vs Input Voltage
DRD30-12
90
90
85
Efficiency [ % ]
Efficiency [ % ]
85
80
75
70
12
15
18
21
24
Input Voltage (V)
www.chinfa.com
2016.04.18
27
30
33
80
75
70
65
Io : Full Load
65
10
Efficiency Vs Output Load
DRD30-12
36
60
Vi : 24VDC
10
20
30
40
50
60
70
80
90
100
Output Load (%)
[email protected]
P4