GPSEMI GOG91K28 Three phase ac-dc bridge Datasheet

Green Power Solutions srl
Via Venezia 34D - 10088 Volpiano (TO), Italy
Phone: +39-011-988 2251
Fax: +39-011-988 1358
Web: www.gpsemi.it
e-mail: [email protected]
GOG91K28
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 1000V
DC OUTPUT CURRENT 2800 A
GOG91K28
1000 V
Line to line voltage
Characteristic
IDC
DC output current
VINS (rms)
Insulation voltage
Conditions
Value
2800 A
1 min. (IEC 1461.1)
3000 V
THYRISTOR CHARACTERISTICS
VGT
Gate trigger voltage
Tj = 25 °C, V D = 5 V
3 V
IGT
Gate trigger current
Tj = 25 °C, V D = 5 V
400 mA
dV/dt
Critical rate of rise off-state voltage
Tj= 125 °C
1000 V/us
VRRM
Blocking Voltage
Tj = 125 °C
2800 V
FUSE TYPE: 2 x SIBA 2078132.900
VNF
Rated voltage
1250 V
INF
Rated current
900 A
PVF
Power loss
At rated current
I²t
Total I2t
At 1000 V
140 W
2
1300 kA s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
802 mm
Depth
495 mm
Height
1420 mm
Mass
200 kg
Ta max
Max amb. op. Temp.
40 °C
Tstg
Storage temperature
-40/60 °C
Document GOG91K28T001
THREE PHASE AC-DC BRIDGE
GOG91K28
The part numbering system is reported at the beginning of the Open Assembly section.
Customisations are available on request. Please contact factory.
In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet
without notice.
Document GOG91K28T001
THREE PHASE AC-DC BRIDGE
GOG91K28
Cooling:
Fan type:
Number of fans:
Voltage:
Current:
Frequency:
Noise:
three phase cross flow
1
380 V
1.4 A
50/60 Hz
75 dBA
In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data
sheet without notice.
Document GOG91K28T001
Similar pages