Gamewell-FCI MMO-6SF Multi-mod 6 zone interface module Datasheet

Velociti™ Series
MM0-6SF
Multi-MOD Six Signal
Output Module
Description
The FCI Velociti™ Series, multi-mod six signal
output module (MMO-6SF) provides six (6), Style Y
(Class B) or three (3), Style Z (Class A) supervised
control circuits suitable for a wide range of
signaling applications. Each supervised circuit may
be used as a:
• Audio speaker circuit.
• Notification applicance circuit.
• Supervised control output.
The VelocitiTM Series use a communication
protocol that substantially increases the speed of
communication between the sensors and certain
FCI analog addressable fire alarm controls. These
devices operate in a grouped fashion. If one of the
devices in the group has a status change, the
panel’s microprocessor stops the group poll and
concentrates on the single device. The net effect is
response speed up to five times greater than
earlier designs.
The MMO-6SF connects to the signaling line
circuits (SLC) of the FCI analog addressable series
fire alarm control panels. Each of the MMO-6SF
supervised control circuits occupies its own
address on the system’s SLC allowing each to be
fully programmable in its control-by-event
sequence of operation.
The address of the first supervised output circuit is
set with a pair of rotary dials. Each remaining
circuit is automatically assigned to its own
subsequent address. The MMO-6SF module
includes an address disable jumper matrix that
allows one, two, or three addresses to be turned off
to free these addresses for other purposes. An
additional jumper setting selects either Style Y or
Style Z circuit configurations. A wide range of
configurations are possible including 30 VDC,
audio input at 25 or 70.7 VRMS, 125 VAC, etc. More
than one circuit can share a power supply if the
current capacity does not exceed the power
supply’s output.
MMO-6SF
Features
• Each MMO-6SF module provides six (6), Style Y
•
•
•
•
•
•
•
•
•
•
•
(Class B) or three (3), Style Z (Class A) individually
addressable, individually programmable notification
appliance or supervised output circuits.
Removable wiring terminal blocks allow ease of
installation and servicing.
Terminal blocks can accommodate 12 to 18 AWG
wire.
Flexible jumper configuration feature allowing up to
three (3), output circuit addresses to be disabled.
Accommodates multiple external power inputs.
External power monitoring.
Short circuit protection of external power supplies.
Sources providing AC, DC, or audio inputs.
Designed for use with FCI analog addressable series
fire alarm control panels.
Individual LED indicators*.
Ideal for retrofit applications.
Two (2), mounting cabinets available for two (2),
(MBB-2 cabinet) to six (6), (MBB-6 cabinet) units.
Note: *Only the red LED is operative in panels that do not operate in Velociti™ mode.
An ISO 9001-2000 Company
Velociti™ and E3 Series™ are trademarks of Fire Control Instruments.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0634 Rev. C page 1 of 2
©2006 Gamewell-FCI. All rights reserved.
Description (continued)
Specifications
Each output circuit on the MMO-6SF monitors its
own connection to its power supply and will
indicate a fault condition by address if the power
source should fail. The MMO-6SF is also provided
with short circuit monitoring to protect the external
power source from short circuits on the notification
appliance circuit wiring. This feature can be
disabled per individual circuit if the application
requires.
Operating
Voltage:
Stand-by
Current:
Alarm Current:
Maximum IDC
Wire Resistance:
Temperature
Range:
Humidity:
Dimensions:
(Note: power supply monitoring must also be
disabled in such cases.)
MBB-2
Each circuit has its own status LED that flashes to
indicate proper polling and lights steadily when the
output has been activated.
Two (2), multi-mod series units can be mounted in
one MBB-2 cabinet. Additional mounting options
include the MCH-6 chassis that can accommodate
six multi-mod series modules. The MCH-6 chassis
can be installed in a custom cabinet or can be
mounted in the MBB-6 cabinet allowing up to six
(6), multi-mod series modules in one cabinet.
The MMO-6SF is ideal for applications where
centralized location of circuits is required. As many
as thirty-six (36), supervised output circuits may be
located in a cabinet that is only 12.63” H x 24” W x
6.5” D in dimension saving valuable wall space in
mechanical rooms and electrical closets and
reducing cost of installation.
MBB-6
External Supply
Voltage
DC Voltage:
Ripple Voltage:
Current:
15-32 VDC
2.25 mA
40 mA (with all six LEDs lit)
25 Ohms
32˚ F to 120˚ F (0˚ to 49˚ C)
10 to 85% (non-condensing)
6.8” H x 5.8” W x 1.25” D
(17.3 x 14.7 x 3.2 cm)
12.25” H x 9.25” W x 3.32” D
(31.1 x 23.5 x 8.4 cm)
12.63” H x 24” W x 6.5” D
(32 x 60.1 x 16.5 cm)
18-28 Volts, Power-limited
0.1 Volts rms maximum
90 mA per Module
Contact Ratings
Current
Rating
3A
2A
1A
Maximum
Voltage
30 VDC
30 VDC
30 VDC
0.5A
30 VDC
0.9A
0.9A
0.7A
110 VDC
125 VAC
70.7 & VAC
0.5A
125 VAC
Load
Description
Resistive
Resistive
Inductive
(L/R= 2ms)
Inductive
(L/R= 5ms)
Resistive
Resistive
Inductive
(PF= 0.35)
Inductive
(PF= 0.35)
Application
Non-coded
Coded
Coded
Coded
Non-coded
Non-coded
Non-coded
Non-coded
Ordering Information
Model
Description
MMO-6SF
MBB-2
MBB-6
MCH-6
Multi-Mod 6 zone interface module
Backbox, 2 unit
Backbox, 6 unit, requires MCH-6
6-Unit mounting chassis
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
9020-0634 Rev. C page 2 of 2
Similar pages