Fuji EDS9-24A Fc series pt type distributor (48mm width) Datasheet

FC SERIES PT TYPE DISTRIBUTOR (48mm width)
DATA SHEET
PTL
The FC series PT type distributor converts a current signal
(4 to 20mA DC) from the transmitter into a voltage signal (1
to 5V DC ) then distributes the voltage signal to each receiver. In addition, the distributor is provided with built-in
transmitter power supply.
Its structure is plug-in style.
SPECIFICATIONS
INPUT SPECIFICATION
Input signal:
1 point
Input type
Current
Input signal
4 to 20mA DC
Input resistance
250Ω
OUTPUT SPECIFICATION
Output signal:
2 points
Output type
Voltage
Output signal
1 to 5 V DC
Allowable load re- 500kΩ or over (reception,
non-insulation) 15kΩ or over
sistance
(with output buffer)
POWER SUPPLY
Power supply:
24V DC (20 to 30V DC)
24V AC, +13%, –10%,(47 to 63Hz)
100V AC (85 to 132V AC / 47 to 63Hz)
200V AC (187 to 264V AC / 47 to 63Hz)
as specified.
Power consumption:
Approx. 2W (at DC power)
Approx. 6VA (at AC power)
OPERATION CONDITION
Ambient temperature:
0 to 50°C
Ambient humidity:
Less than 90%RH (no condensation)
Outline dimension (HxWxD):
96 x 52 x130mm
Mass:
Appox. 300g
Housing:
Plastic housing (color: black)
Mounting method:
Panel mounting or DIN rail mounting
CHARACTERISTICS
Accuracy:
Less than ± 0.1% of full span
Response time: Less than 0.1 sec. (90% response)
Dielectric strengh: 1500V AC, 1 min. (indicated below)
Insolation resistance:
500V DC, 100MΩ or over (indicated below)
Reception only: Input/Output - Ground
Non-insulation type:
Input/Output•Power - Ground
Non-insulation with buffer:
Input/Output•Power - Ground
Power insulation with buffer:
Input/Output - Power - Ground
Power I/O insulation with buffer:
Input - Output - Power - Ground
Ambient temperature effect:
Less than ± 0.15% of full span/10°C
Power regulation effect:
Less than ± 0.1% of full span
CODE SYMBOLS
1 2 3 4 5 6 7 8
P L T 2 V
Description
1
Input signal
4 to 20mA DC
2
Output signal
1 to 5V DC
V
A0
B1
C1
D1
E1
D2
E2
D3
E3
Output system
Reception only
Non-insulation type
Non-insulation with buffer
Power insulation with
buffer
Power I/O insulation with
buffer
Power insulation with
buffer
Power I/O insulation with
buffer
Power insulation with
buffer
Power I/O insulation with
buffer
Power supply
None
24V DC
24V DC
24V DC/ 24V AC (50/
60Hz)
24V DC/24V AC (50/
60Hz)
100V AC (50/60Hz)
100V AC (50/60Hz)
200V AC (50/60Hz)
200 V AC (50/60Hz)
EDS9-24a
Date
Feb. 20, 1996
PTL
FUNCTIONAL DIAGRAM
1. Reception only type
11
31
Output 1
Transmitter
(4 to 20mA DC)
250Ω
12
32
41
21
Output 2
42
22
34
2. Non-insulation type
11
Transmitter
(4 to 20mA DC)
Power
restric
circuit
31
Output 1
12
32
41
Output 2
21
42
22
250Ω
43
Power
44
34
3. Power insulation with buffer
11
Transmitter
(4 to 20mA DC)
Power
restric
circuit
31
Output 1
12
32
41
Output 2
21
42
22
Power
circuit
43
Power
44
250Ω
34
4. Power input/output insulation with buffer
Current
limiting
circuit
11
Transmitter
(4 to 20mA DC)
31
Output 1
12
32
Signal insulation
circuit
41
Output 2
21
42
22
43
Power
circuit
Power
44
250Ω
34
OUTLINE DIAGRAM (Unit: mm)
Terminal screw M2.5
(for transmission)
35
74
Main unit
94
Terminal screw M4
Terminal
2
48
52
100
Stopper
130
Panel mounting
DIN rail mounting
2-M4
DIN rail
40
52
Stopper
PTL
EXTERNAL CONNECTION DIAGRAM
General
Reception only type
(non-insulation type, power insulation type, power
I/O insulation type)
+
-
+
-
11 12
+
-
13 14
11 12
+
-
13 14
21 22
23 24
21 22
23 24
5
5
6
6
31 32
+
-
33 34
OUTPUT
31 32
+
-
33 34
OUTPUT
41 42
+
-
43 44
+
-
41 42
+
-
OUTPUT
POWER
OUTPUT
43 44
RANGE OF DELIVERY
Main unit and socket
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan