Battery BPS1.2-6 Maintenance free(topping up not needed) Datasheet

VRLA Rechargeable Battery
Measures
BPS1.2-6
FEATURES
Technology
Values
Innovation
APPLICATIONS
Maintenance Free ( topping up not needed )
UPS
Security Systems
Medical Equipment
Non - spillable ( no free electrolyte )
Low Self Discharge, less than 3% per month
both Vertical & Horizontal installations
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
6V
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
T1 (Faston Tab 187)
(Fully Charged )
55m
18 A (5 sec.)
0.36 A
Charge:0oC~40oC(32oF~104oF)
Discharge:-20oC~50oC(-4oF~122oF)
Storage.:-20oC~40oC(-4oF~104oF)
1.2Ah @ 20 hour rate F.V.(1.75V/cell)
300g(0.66lbs.)
Operating Temperature Range
Standard: ABS( UL 94-HB) BPS1.2-6
Optional: Flame Retardant ABS(UL 94-V0) BPS1.2-6FR
Container Material
DIMENSION(mm/inch)
OUTER DIMENSIONS
IEC 61056-1
JIS C 8702-1
GB/T 19639.1
TERMINAL TYPE
Length
97±1.5(3.82±0.06)
Terminal T1
3.2(0.13)
25 1.5(0.98 0.06)
97 1.5(3.82 0.0 6)
4.75(0.19)
Width
51±1.5(2.01±0.06)
Total Height
56±2.0(2.20±0.08)
6.35(0.25)
0.8(0.03)
51 1.5(2.01 0.06)
Container Height
56 2(2.20 0.08)
25±1.5(0.98±0.06)
Constant power discharge characteristics at 25 oC/77 oF
F.V.
(V/cell)
Discharge
Time
1.80V
1.75V
1.70V
1.65V
1.60V
5 Min
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
21.69
15.97
12.80
7.61
4.367
1.749
1.206
0.674
0.355
25.11
17.30
13.39
7.90
4.498
1.784
1.224
0.684
0.360
26.68
17.92
13.80
8.08
4.579
1.800
1.231
0.687
0.360
27.88
18.35
14.12
8.20
4.634
1.813
1.235
0.689
0.360
28.80
18.72
14.40
8.28
4.680
1.823
1.239
0.689
0.360
o
o
Constant current discharge characteristics at 25 C/77 F
F.V.
(V/cell)
Discharge
Time
1.80V
1.75V
1.70V
1.65V
1.60V
Unit: W
5 Min
10 Min
15 Min
3.91
2.81
4.61
3.05
4.89
Unit: A
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
2.23
1.291
0.734
0.291
0.201
0.112
0.059
2.33
1.340
0.756
0.297
0.204
0.114
0.060
3.16
2.40
1.370
0.770
0.300
0.205
0.115
0.060
5.11
3.23
2.46
1.389
0.779
0.302
0.206
0.115
0.060
5.28
3.30
2.50
1.403
0.787
0.304
0.206
0.115
0.060
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
For operation, please refer to the instruction from technical manual.
A/3
REV. May. 2016
Powered by
B.B. Battery Co., Ltd.
Similar pages