Rail Mount InstallationDINSheet PART NUMBER NOMENCLATURE DR22 Series Solid State Relays Operating Voltage 20: 1-200 VDC 60: 48-600 VAC Series Crydom DR22 Series Solid State Relays were developed to offer the advantages of semiconductor switching technology in a standard 22.5 mm industrial package. Quick and easy installation is coupled with low drive power requirements and efficient, reliable power SCR output. This compact new design offers up to 35 ARMS in ambient temperatures of 40ºC. DR22 60 A Please read all instructions before using your DIN Rail Mount Solid State Relay (SSR). Relay AC To remove from DIN rail +3/A1 -4/A2 INPUT STATUS INPUT STATUS Load 1/L1 Wire Size (Solid / Stranded) Wire Pull-Out Strength (lb)[N]* Output Relay “U” suffix 2 x 18 AWG (1 mm2) Stranded [minimum] 20 [88] 2 x 10 AWG (6 mm ) Stranded [maximum] 60 [266] 2 x 18 AWG (1 mm2) Stranded 20 [88] 2 x 12 AWG (4 mm2) Stranded 40 [177] 2 x 20 AWG (0.75 mm ) [minimum] 25 [111] 2 x 10 AWG (6 mm2) 80 [355] 2 x 8 AWG (10 mm2) [maximum] 90 [400] Spring +3/A1 -4/A2 2/T1 +1 30 AWG (0.05 mm2) [minimum] 4.5 [20] 12 AWG (3.3 mm2) [maximum] 30 [133] 26 AWG (0.13 mm2) [minimum] 5 [22] 12 AWG (3.3 mm2) [maximum] 5 [22] -2 2/T1 + AC V Terminal Configuration 2 -4/A2 INPUT STATUS TABLE 1. Recommended Wire Sizes 2 +3/A1 (+ / ) (- / ) fig. 1 SSR mounted on DIN rail WARNING! Removing product from 35 mm rail incorrectly by not using the appropriate tool would damage the latching system. Screw (-) (+) V AC ■ If multiple units are installed be sure to follow derating curves ■ Recommended wire sizes as shown in TABLE 1 Input Contactor “V” &“W” suffixes Relay DC (A) Contactor AC (- / ) (+ / ) terminal: ♦ Contactor configuration (”V” & “W” suffixes): 18-20 in-lb (2.0-2.2 Nm) ♦ Relay configuration (”U” suffix): 13-15 in-lb (1.5-1.7 Nm) Output Contactor “V” &“W” suffixes J 1/L1 ■ Maximum recommended terminal screw torque load Input Relay “U” suffix R WIRING DIAGRAMS SUD terminal: ♦ Contactor configuration (”V” & “W” suffixes): 5 in-lb (0.5 Nm) ♦ Relay configuration (”U” suffix): 13-15 in-lb (1.5-1.7 Nm) Switching Type Blank: Zero Voltage Turn-On R: Instantaneous Turn-On (AC Output only) Terminal Layout Input Connector U: Relay Configuration Blank: Screw Terminal V: Contactor J: Spring Terminal (V and W suffixes only) Configuration AC (std. screw) Output W: Contactor only Configuration (elevator screw) Required for valid part number For options only and not required for valid part number 50 To install on DIN rail ■ Install the relay on the DIN Rail (as shown in fig. 1) ■ Maximum recommended terminal screw torque input U V 20 Control Voltage A: 90-280 VAC/VDC (AC Output only) D: 4-32 VDC Be sure to visit the product series datasheet available at the Crydom website to complement this information. If you have questions or need additional information please contact Crydom Tech Support. MOUNTING INSTRUCTIONS Rated Load Current 20: 20 Amps 30: 30 Amps 35: 35 Amps [High I2t] (AC Output only) V Load - ■ Important Considerations ♦ Be sure to use input and output voltages within + Load (B) 0.89 in [22.5 mm] Minimum operating ranges. ♦ LED indicates only input status. It does not represent output status. ♦ To achieve maximum ratings, there must be a minimum spacing of 0.89 in (22.5 mm) between the devices in free air (as shown in fig.2). ♦ Protective Earth (PE) screw type recommended is 10-32 UNC standard, not provided with SSR. Through the use of a DIN rail ground (protective conductor) terminal block, the DIN rail itself can be used as the grounding bus bar. In this case, the zinc plated steel material used for the DIN rail clip of DR22 models, permits a secure path to ground and avoid the need of a further PE connection (see fig.3). fig. 2 Multiple units mounting for maximum ratings fig. 3 DR22 model with Protective Earth screw * Tests performed on Stranded wire TABLE 3. Recommended Accessories TABLE 2. Compatible Terminals W D Terminals W D Fork Lug Ring Lug Crydom Part No. Width [W] in (mm) 0.45 (11.4) 0.45 (11.4) Stud Size Dia [D] (in) #8 (0.168) #8 (0.168) Wire Size AWG Copper Lug Copper Lug TRM0 TRM6 6-0 Connectors ID Marker Lug Terminal CP201 CNLB TRM0 CP202 CNLN TRM6 14-6 General Notes (A) Load can be wired to either terminal 1 or terminal 2. Proper polarity must be observed for the DC control power supply, with terminal 3 being positive with respect to terminal 4. (B) DC inductive loads must be diode suppressed. (C) AC input models operating range is -20 to 60 ºC Do not forget to visit us at: www.crydom.com Copyright © 2016 Crydom Inc. Specifications subject to change without notice. CNL2 Rev. 060816 Rail Mount InstallationDINSheet ELEVATOR SCREW (”W” SUFFIX) CONSIDERATIONS PIN TERMINAL CONSIDERATIONS ■ The Elevator Screw option allows the screw and clamp to ■ For 35 Amp Relay configuration (suffix "U") models use Pin Terminals (L 0.410 in x Ø 0.102 in) to install 8 AWG wire. be raised out of the mating threads completely. This provides for the insertion and use of a ring or lug type wire terminal. ■ To install, make sure screw is completely lifted to maximum position, and insert Pin terminal (as shown in fig. 5) ■ A #2 Phillips head driver should be used with the Elevator Screws. If a powered driver is used, avoid speeds above 500 RPM. ■ Once installed, tighten terminal screws. Maximum ■ Cutting threads in the cover plastic as the screw elevates recommended screw torque is 14 in-lb(1.58 Nm). Be sure to apply sufficient downward pressure while tightening the terminal screws to prevent the screw assembly from lifting. is key to the elevating feature. It has a finite life and therefore not recommended to be used more than 50 times during the product lifetime. ■ Do not continue rotating the screw (in the elevating direction) once it freely rotates at the top of the plastic surface. The Elevator screw is capable of clearing 0.125 inches between the terminal and the bottom of the screw. Insertion of a terminal or lug thicker than 0.125 in is not recommended. ■ When inserting the terminal ensure that the terminal hole is in line with the screw. fig. 4 Elevator screw ■ During tightening, be certain that the terminal is seated flat within the cavity, and that the clamping washer is secure against the upper surface of the terminal. ■ If fork terminations, spade lugs, or stranded wire are used, to prevent improper contact do not raise the elevator screw out of the mating threads. fig. 5 Pin Terminal DERATING CURVES (C) DR2260x20x 10 5 20 30 40 50 60 70 Ambient Temperature (ºC) 25 20 15 10 5 0 80 Load Current (Amps) Load Current (Amps) Load Current (Amps) 30 15 0 20 30 80 20 30 40 50 60 70 Ambient Temperature (ºC) 80 30 Load Current (Amps) 20 15 10 5 0 40 50 60 70 Ambient Temperature (ºC) 35 30 25 20 15 10 5 0 DR2220D30U DR2220D20U Load Current (Amps) DR2260x35x DR2260x30x 20 20 30 40 50 60 70 Ambient Temperature (ºC) 80 25 Single unit 20 15 Multiple units, no minimum spacing between components (see fig. 2) 10 5 0 20 30 40 50 60 70 Ambient Temperature (ºC) 80 DANGER / DANGER / GEFARH / PELIGRO / PERICOLO / STROMSCHLAG-, EXPLOSIONS- ODER LICHTBOGENGEFAHR HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH RISQUE D'ELECTROCUTION, D'EXPLOSION OU D'ARC ELECTRIQUE • Turn off power supply before working on this equipment. • Coupez l'alimentation avant de travailler sur cet appareil. • Vor dem Arbeiten an dem Gerät dessen Stromversorgung abschalten. Failure to follow these instructions will result in death or serious injury. Le non-respect de ces instructions provoquera la mort ou des blessures graves. Die Nichtbeachtung dieser Anweisungen führt zu Tod oder schwerer Körperverletzung. RIESGO DE ELECTROCUCIÓN, EXPLOSIÓN O ARCO ELÉCTRICO RISCHIO DI SCOSSA ELETTRICA, DI ESPLOSIONE O DI OFTALMIA DA FLASH 存在电击、爆炸或电弧闪烁危险 Desconecte toda alimentación antes de realizar el servicio. Si no se siguen estas instrucciones provocará lesiones graves o incluso la muerte. • Scollegare l'apparecchio dalla presa di corrente prima di qualsiasi intervento. Il mancato rispetto di queste istruzioni provocherà morte o gravi infortuni. • 在操作此设备之前请先关闭电源。 若不遵守这些说明,可能会导致严重的人身伤害甚至死亡。 WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告 RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE • The product's side panels may be hot, allow the product to cool before touching. • Follow proper mounting instructions including torque values. • Do not allow liquids or foreign objects to enter this product. RISQUE DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER • Les panneaux latéraux du produit peuvent être chauds. Laisser le produit refroidir avant de le toucher. • Respecter les consignes de montage, et notamment les couples de serrage. • Ne pas laisser pénétrer de liquide ni de corps étrangers à l'intérieur du produit. GEFAHR VON MATERIALSCHÄDEN UND GEHÄUSEERHITZUNG • Die Seitenwände können heiß sein. Lassen Sie das Produkt abkühlen, bevor Sie es berühren. • Beachten Sie die Montageanweisungen, • Führen Sie keine Flüssigkeiten oder Fremdkörper in das Produkt ein. Failure to follow these instructions can result in serious injury, or equipment damage. Le non-respect de cette directive peut entraîner, des lésions corporelles graves ou des dommages matériels. Die Nichtbeachtung dieser Anweisung kann Körperverletzung oder Materialschäden zur Folge haben. RIESGO DE DAÑOS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD • Los paneles laterales del producto pueden estar calientes. Esperar que el producto se enfríe antes de tocarlo. • Respetar las instrucciones de montaje, y en particular los pares de apretado. • No dejar que penetren líquidos o cuerpos extraños en el producto. Si no se respetan estas precauciones pueden producirse graves lesiones, daños materiales. RISCHIO DI DANNI MATERIALI E D'INVOLUCRO CALDO • I pannelli laterali dell'apparecchio possono scottare; lasciar quindi raffreddare il prodotto prima di toccarlo. • Seguire le istruzioni di montaggio corrette. • Non far entrare liquidi o oggetti estranei in questo apparecchio. La mancata osservanza di questa precauzione può causare gravi rischi per l'incolumità personale o danni alle apparecchiature. Rev. 060816 Do not forget to visit us at: www.crydom.com Copyright © 2016 Crydom Inc. Specifications subject to change without notice.