Cooper NON-4 Non (250v) 1â 8-600a, general purpose fus Datasheet

NON/NOS, 600/250Vac Class K5 & H
NON (250V) 1⁄8-600A, General Purpose Fuses
Dimensions – in
All Diameters ± 0.008
10.38" ( 0.094)
2"
(0.031)
2.59"
0.56" (± 0.008)
1/8 to 30A
450 to 600A
3"
(0.031)
8.63" (± 0.094)
2.06"
0.81" (± 0.008)
Description: Basic protection 250V NON Class K5 and H
general purpose, non-current-limiting, one-time fuses.
35 to 60A
5.88" (± 0.062)
Catalog Symbol: NON-(amp)
Features:
— 125Vdc (1⁄8-100A)
• Protect lighting, heating and other circuits not subject to temporary
surges and where available short-circuit currents are relatively low
• NON one-time fuses do not have any appreciable degree of timedelay and thus should not be specified in circuits where large
transients or motor overloads occur. Use Bussmann advanced
protection FUSETRON™ FRN-R or ultimate protection Low-Peak™
LPN-RK dual-element, time-delay fuses.
• For general purpose circuits, size at amp rating of circuit
• For motor circuits, size at 300% to 400% according to the NEC®
motor ampacity tables 430.247 to 430.250, per 430.6(A)(1)
Amps — ⁄8-600A
1
IR — 50kA Vac RMS Sym. (1⁄8-60A)
— 10kA Vac RMS Sym. (65-600A)
— 50kA Vdc (1⁄8-60A)
— 10kA Vdc (65-100A)
Agency Information:
CE, UL Listed, Class K5 (1⁄8-60A), Std. 248-9,
Class H (65-600A), Std. 248-6 (125Vdc 1⁄8-100A),
UL Guide JDDZ, File E4274
Recommended Fuse Blocks
CSA Certified, Class 1421-01, File 53787 (1⁄8-12A, 65-600A)†
† For CSA Certified 15-60A, see PON Data Sheet # 4126.
Catalog Numbers (amps)
NON-3
NON-32⁄10
NON-4
NON-5
NON-6
NON-61⁄4
NON-7
NON-8
NON-9
NON-10
NON-12
NON-15
NON-20
NON-25
NON-30
NON-35
NON-40
NON-45
NON-50
NON-60
Carton Quantity and Weight
0713
1.56"
110 to 200A
70 to 100A
Volts — 250Vac
Amp Rating
1
⁄8-30
35–60
65–100
110–200
225–400
450–600
7.13" (± 0.062)
1.06"
Ratings:
NON-1⁄8
NON-1⁄2
NON-3⁄4
NON-8⁄10
NON-1
NON-11⁄4
NON-11⁄2
NON-16⁄10
NON-2
NON-21⁄2
225 to 400A
Carton Qty.
10
10
5
1
1
1
BU-SB13738
NON-65
NON-70
NON-75
NON-80
NON-90
NON-100
NON-110
NON-125
NON-150
NON-175
NON-200
NON-225
NON-250
NON-300
NON-350
NON-400
NON-450
NON-500
NON-600
Fuse Amps
0-30
35-60
70-100
110-200
225-400
450-600
1-Pole
H25030-1
H25060-1
HM25100-1CR
HM25200-1CR
HM25400-1CR
HM25600-1CR
2-Pole
H25030-2
H25060-2
HM25100-2CR
HM25200-2CR
HM25400-2CR
HM25600-2CR
3-Pole
H25030-3
H25060-3
HM25100-3CR
HM25200-3CR
HM25400-3CR
HM25600-3CR
For additional information on 250 volt fuse blocks, see Data
Sheet # 1112 (H250) and product brochure # 3192 (HM Series).
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
60A
100A
200A
200A
400A
Desired Fuse
(Case) Size
30A
30A
60A
60A
100A
100A
200A
Catalog Numbers
(Pairs) 250V
NO.263
NO.213
NO.216
NO.226
NO.2621
NO.2641
NO.2642
For additional information on Class K5 & H fuse reducers, see
Data Sheet # 1118.
Page 1 of 4
Data Sheet # 1030
NON/NOS, 600/250Vac Class K5 & H
NON (250V) 1⁄8-600A, General Purpose Fuses
600A
400A
200A
60A
100A
30A
35A
300
15A
20A
Time-Current Curves - Average Melt
AMP RATING
100
TIME IN SECONDS
10
1
CURRENT IN AMPS
0713
BU-SB13738
Page 2 of 4
10,000
1,000
20
0.01
100
0.1
Data Sheet # 1030
NON/NOS, 600/250Vac Class K5 & H
NOS (600V), 1-600A, General Purpose Fuses
Dimensions – in
All Diameters ± 0.008
13.38" ( 0.094)
5" (± 0.031)
0.81" (± 0.008)
1 to 30A
3.13"
450 to 600A
5.5" (± 0.031)
11.63" (± 0.094)
2.59"
1.06" (± 0.008)
35 to 60A
110 to 200A
Features:
Volts — 600Vac
Amps — 1-600A
IR — 50kA Vac RMS Sym. (1-60A)
— 10kA Vac RMS Sym. (70-600A)
Agency Information:
CE, UL Listed, Class K5 (1-60A), Std. 248-9,
Class H (70-600A), Std. 248-6, UL Guide JDDZ, File E4273
CSA Certified, Class 1421-01, File 53787
NOS-9
NOS-10
NOS-12
NOS-15
NOS-20
NOS-25
NOS-30
NOS-35
NOS-40
NOS-45
NOS-50
NOS-60
NOS-70
NOS-75
NOS-80
NOS-90
NOS-100
NOS-110
NOS-125
NOS-150
NOS-175
NOS-200
NOS-225
NOS-250
NOS 600V Carton Quantity and Weight
Carton Qty.
10
10
5
1
1
1
• Protect lighting, heating and other circuits not subject to temporary
surges and where available short-circuit currents are relatively low
• NOS one-time fuses do not have any appreciable degree of timedelay and thus should not be specified in circuits where large
transients or motor overloads occur. Use Bussmann advanced
protection FUSETRON™ LPS-R or ultimate protection Low-Peak™
LPS-RK dual-element, time-delay fuses.
• For general purpose circuits, size at amp rating of circuit
• For motor circuits, size at 300% to 400% according to the NEC®
motor ampacity tables 430.247 to 430.250, per 430.6(A)(1)
Recommended Fuse Blocks
Catalog Numbers (amps)
Amp Rating
1–30
35–60
70–100
110–200
225–400
450–600
1.84"
1.34"
70 to 100A
Ratings:
NOS-1
NOS-2
NOS-3
NOS-4
NOS-5
NOS-6
NOS-7
NOS-8
9.63" (± 0.062)
7.9" (± 0.062)
Description: Basic protection 600V NOS Class K5 and H
general purpose, non-current-limiting, one-time fuses.
Catalog Symbol: NOS-(amp)
225 to 400A
NON-300
NOS-350
NOS-400
NOS-450
NOS-500
NOS-600
Fuse Amps
0-30
35-60
70-100
110-200
225-400
450-600
1-Pole
H60030-1
H60060-1
HM60100-1CR
HM60200-1CR
HM60400-1CR
HM60600-1CR
2-Pole
H60030-2
H60060-2
HM60100-2CR
HM60200-2CR
HM60400-2CR
HM60600-2CR
3-Pole
H60030-3
H60060-3
HM60100-3CR
HM60200-3CR
HM60400-3CR
HM60600-3CR
For additional information on 600 volt fuse blocks, see Data
Sheet # 1112 (H) and product brochure # 3192 (HM Series).
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
60A
100A
200A
200A
400A
Desired Fuse
(Case) Size
30A
30A
60A
60A
100A
100A
200A
Catalog Numbers
(Pairs) 250V
NO.663
NO.216
NO.616
NO.626
NO.2621
NO.2641
NO.2642
For additional information on Class R fuse reducers, see
Data Sheet # 1118.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
0713
BU-SB13738
Page 3 of 4
Data Sheet # 1030
NON/NOS Class K5 & H, 600/250Vac
NOS (600V), 1-600A, General Purpose Fuses
600A
400A
200A
100A
60A
30A
35A
300
15A
20A
Time-Current Curves - Average Melt
AMP RATING
100
TIME IN SECONDS
10
1
0.1
0.08
0.06
0.04
0.03
CURRENT IN AMPS
10,000
1,000
20
0.01
100
0.02
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
0713
BU-SB13738
Page 4 of 4
Data Sheet # 1030