Crydom DRH3P60D18 Din rail mount Datasheet

DIN Rail Mount
Datasheet
DRH Series
• Ratings up to 18 & 20 Amps at 600 VAC
• Fits standard 35 mm DIN Rail
• Integrated over-temperature protection
• Alarm output in case of over-temperature
• Multicolor LED with input status and alarm indicator
• AC or DC control
• Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
• C-UL-US Listed, CCC Certified, IEC Rated, CE & RoHS Compliant, Horsepower Rated
• Built-in Overvoltage Protection
• Fan controlled through thermistor and microprocessor to optimize fan operation
PRODUCT SELECTION
Control Voltage
90-280 VAC/VDC
4-32 VDC
18 A
20 A
DRH3P60A18
DRH3P60D18
DRH3P60A20
DRH3P60D20
AVAILABLE OPTIONS
Series
DRH
Control Voltage
A: 90-280 VAC/VDC
D: 4-32 VDC
Function
3P: Contactor
3P
Required for valid part number
For options only and not required for valid part number
60
A
Operating Voltage
60: 48-600 VAC
18
U
Switching Type
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
R
Rated Load Current
18: 18 Amps (3 Controlled legs)
20: 20 Amps (2 Controlled legs)
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-63Hz) [VRMS]
Transient Overvoltage [Vpk] (2)
Maximum Off-State Leakage Current @ Rated Voltage [mARMS]
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/μsec]
Load Current, General Use UL508/IEC62314 @ 40°C [ARMS] (3)
Load Current, Motor Starting UL508 FLA/IEC62314 @ 40°C [ARMS] (3)
Minimum Load Current [ARMS]
Maximum Surge Current [Apk] 1Cycle 60Hz
Maximum Surge Current [Apk] 1Cycle 50Hz
Maximum I²t for Fusing (8.33 msec) [A²sec]
Maximum I²t for Fusing (10 msec) [A²sec]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Minimum Power Factor (with Maximum Load)
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :240 VAC
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :380 VAC
Motor Rating UL 508/ IEC60947-4-2 [HP/kW] :480 VAC
18 A
20 A
48-600
1200
3
500
18
7.6
0.15
750
716
2330
2560
1.35 per channel
0.5
2/1.5
3/2.2
5/3.7
48-600
1200
3
500
20
7.6
0.15
750
716
2330
2560
1.35 per channel
0.5
2/1.5
3/2.2
5/3.7
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Minimum Turn-On Voltage
Must Turn-Off Voltage
Minimum Input Current (for on-state)
Maximum Input Current
Nominal Input Impedance [Ohms]
Maximum Turn-On Time [msec]
Maximum Turn-Off Time [msec]
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DRH3P60Dx
4-32 VDC
4 VDC
1 VDC
2 mA
17 mA
2k
1 Cycle (4)
1 Cycle
DRH3P60Ax
90-280 VAC/VDC
90 VAC/VDC
10 VAC
1 mA
3 mA
100k
30
40
DIN Rail Mount
Datasheet
POWER SUPPLY SPECIFICATIONS
(1)
Description
DRH3P60Dx
Voltage Range
Minimum Turn-On Voltage
Must Turn-Off Voltage
Maximum Source Current [mA]
Maximun Start Up Time [msec]
Maximun Shut Off Time [msec]
ALARM OUTPUT
DRH3P60Ax
90-265 VAC/VDC
90 VAC/VDC
5 VAC/VDC
40
50
500
8-32 VDC
8 VDC
3 VDC
125
20
40
(1)
Description
DRH3P60xxx
Maximum Contact Switching Voltage [Volts]
Rated Current Resistive [A] (5)
Minimum Recommended Contact Load [mA]
Static Contact Resistance (max. init.)[Ohms]
Turn-On / Off Condition
200 VDC, 120 VAC
0.5
10
0.2
See Status Chart
GENERAL SPECIFICATIONS (1)
Description
Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) (6)
Minimum Insulation Resistance (@ 500 VDC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range (7)
Ambient Storage Temperature Range
Weight (typical)
Housing Material
Housing Color
LED Status Indicator (color)
Short Circuit Current Rating (8)
Pollution Degree
Protection Degree (9)
Humidity
Control and Auxiliary Contact Terminal Screw Torque Range (in-lb/Nm)
Load Terminal Screw Torque Range (in-lb/Nm)
Input Terminal Wire Capacity
Output Terminal Wire Capacity
3750 Vrms
109 Ohm
20 pF
-10 to 70 °C
-40 to 70 °C
2 Controlled Legs (7.4 oz [210 g]) / 3 Controlled Legs (8.5 oz [242 g])
UL94 V-0
Black and Light Gray
See Status Chart
100kA
2
IP20
85% non-condensing
12 / 1.36
15 / 1.7
18-12 AWG (IEC 1-4 mm2) (stranded /solid)
18-10 AWG (IEC 1-6 mm2) (stranded /solid)
THERMAL DERATE INFORMATION
DRH3P60x20
DRH3P60x18
Single unit (10)
Single unit (10)
Multiple units
15
Load Current (Amps)
Load Current (Amps)
Multiple units
20
18
12
9
6
15
10
5
3
0
0
20
30
40
50
60
70
20
30
Ambient Temperature (ºC)
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
40
50
60
Ambient Temperature (ºC)
70
DIN Rail Mount
Datasheet
WIRING AND BLOCK DIAGRAM
L1
L2
L3
48-600 VAC, 50-60Hz
L1
L2
L3
T2
/>
L2
L3
+A3
13
+A1
DRH3P60xxx
IND. CONT. EQ.
-A4
T1
CONTROL
INPUT
INPUT
STATUS
XXXX
Motor Controller /
AC-53a Application
T1
/>
L1
Alarm Output (0.5 A/200 VDC, 120 VAC) Normally Open
Power Supply
90-265 VAC/VDC (for A Control Voltage)
8-32 VDC (for D Control Voltage)
/>
14
T2
T1
-A2
T3
T2
T3
General Use /
AC-51 Application
T1
T3
T2
T3
M
3
DRHP60x18
Alarm Output
(DRHP60x18 & DRHP60x20)
(3 controlled legs model)
Main Circuit
+A3
L1
L2
L3
+A1
13
-A4
T1
T2
T3
-A2
14
DRHP60x20
(2 controlled legs model)
Main Circuit
+A3
L1
L2
L3
+A1
-A4
T1
T2
T3
-A2
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
Datasheet
SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES
IEC standard 60947-4-1 make a distinction between two different types of protection, (called “coordination”), which are designated types “1” and "2".
Any short-circuit that occurs is cleared safely by either type of coordination.
The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit.
Type "1" coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations,
but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination,
the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used.
Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations,
and in addition the SSR will be able to operate after the fault condition is repaired.
Type of coordination 1
For resistive loads:
Protection by Thermal Magnetic Circuit Breaker or by Fuse (11)
Nominal
Current
Class gG fuses
Solid State Contactor Solid State Contactor
(example from Littlefuse) 2 controlled legs
3 controlled legs
0.15-20 A
CY14X51G25
DRH3P60x20
DRH3P60x18 (up to 18A)
For motor loads:
Protection by Thermal Magnetic Circuit Breaker or by Fuse (11)
Nominal Motor
Current
Thermal Magnetic Circuit Breaker
(Schneider Electric)
Class gG fuses
(example from Littlefuse)
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
0.40-0.63 A
0.63-1 A
1-1.6 A
1.6-2.5 A
2.5-4 A
4-6.3 A
6.3-10 A
GV2ME04 / GV2P04
GV2ME05 / GV2P05
GV2ME06 / GV2P06
GV2ME07 / GV2P07
GV2ME08 / GV2P08
GV2ME10 / GV2P10
GV2ME14 / GV2P14
CY14X51G16
CY14X51G16
CY14X51G25
CY14X51G25
CY14X51G25
CY14X51G40
CY14X51G40
DRH3P60x20
DRH3P60x20
DRH3P60x20
DRH3P60x20
DRH3P60x20
DRH3P60x20
DRH3P60x20 (up to 7.6A)
DRH3P60x18
DRH3P60x18
DRH3P60x18
DRH3P60x18
DRH3P60x18
DRH3P60x18
DRH3P60x18 (up to 7.6A)
Type of coordination 2
For resistive loads:
Protection by Fuse (11)
Nominal
Current
Semiconductor fuses with less than 2330 A2s
Littlefuse
SIBA1 (Cylindric) Ferraz (Cylindric)
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
0.15-20 A
LA50QS35-4
DRH3P60x20
DRH3P60x18 (up to 18A)
50 058 06.32
Z093908
For motor loads:
Protection by Fuse (11)
Nominal Motor Semiconductor fuses with less than 2330 A2s
Littlefuse
SIBA1 (Cylindric) Ferraz (Cylindric)
Current
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
0.15-7.6 A
DRH3P60x20
DRH3P60x18
LA50QS40-4
50 058 06.40
A093909
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
Datasheet
STATUS CHART
1
2
3
4
5
6
50%
75%
100%
7
8
9
10
11
100%
75%
12
13
14
15
Control Input A1
Power Supply A3
Output
Over Temperature
Alarm
Pre-alarm
Alarm Output
LED Color
2s
3s
0%
50%
3s
3s
Fan Speed
Step
LED Color
Description
Blue
1, 15
Initial Condition
2, 14
Stand by condition. LED is blinking Blue. Fan is activated at full speed for 2 seconds after power is applied to A3
3
Green
A1 is On, Output is activated, temperature rises. LED is Green
4, 12
Fan is activated at 50% speed. If A1 is disabled, LED changes to blinking Blue
5, 11
Fan is at 75% speed
6, 10
LED changes to blinking Red, fan is at full speed
7
Output is Off, Alarm Output is On, LED changes to solid Red
8
If A1 is disabled while alarm output is active, LED alternates between Blue and Red
9
LED is solid Red, temperature starts to fall
13
Fan is activated at 50% speed, temperature is steady
MECHANICAL SPECIFICATIONS
3.51
[89]
0.23
[5.8]
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
2.91
[73.9]
+A3
1.23
[31.3]
3.41
[86.7]
2.29
[58.3]
13
+A1
DRH3
2.58
[65.5]
1.68
[42.7]
IND. CONT. EQ.
INPUT
STATUS
XXXX
-A4
14
-A2
3.76
[95.6]
Fig. 1
1.78
[45.3]
TERMINAL SCREW TYPE
Top/Bottom view (Fig. 1)
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
Red
DIN Rail Mount
Datasheet
ACCESSORIES
ID Marker
ID Marker
CNLB
CNLN
Package of 10 plastic strip
comprising 10 individual markers
which can be placed for easy
identification during the use of
multiple units.
CNL2
AGENCY APPROVALS
Certification in accordance with:
United States Standard for Industrial Control Equipment - UL 508 and
Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14.
China Compulsory Certification for AC Semiconductor Motor Controller-GB14048.6-2008
DRH series conforms to the harmonized EN standard EN/IEC 60947-4-2
Electromagnetic Compatibility:
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
Vibration Resistance:
IEC 60068-2-6: Amplitude Range 10-55 Hz, Displacement 0.75mm
Shock Resistance:
IEC 60068-2-27: Peak Acceleration 15g, Duration 11msec.
E116949
s
GENERAL NOTES
(1) All parameters at 25°C unless otherwise specified.
(2) Relay will self trigger between 950-1200V, Not suitable for capacitive loads.
(3) Mounted in the Vertical position.
(4) Turn-on time for Instantaneous turn-on version is 4 msec.
(5) Decrease Maximun Current 15mA/°C above 40°C ambient temperature.
(6) For input to alarm output the dielectric strength is 1.5kV.
(7) UL approval up to 40°C surrounding temperature.
(8) 100kA, 480 VAC, when protected with CC class fuses rated 600VAC, 20 A or equivalent.
(9) IP20 rating is not associated with the UL approval.
(10) Minimum spacing to obtain max. current is 22mm between adjacent units.
(11) Combination of these Protective Devices and Solid State Contactor have not been evaluated by UL.
Rev. 052616
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
DIN Rail Mount
Datasheet
DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险
HAZARD OF
ELECTRIC
SHOCK,
EXPLOSION,
OR ARC FLASH.
• Disconnect all
power before
installing or
working with
this equipment.
• Verify all
connections
and replace all
covers before
turning on
power.
Failure to follow
these
instructions will
result in death
or serious injury.
RIESGO DE
DESCARGA
ELECTRICA O
EXPLOSION.
• Desconectar
todos los
suministros de
energia a este
equipo antes
de trabajar
con este equipo.
• Verificar todas
las conexiones
y colocar todas
las tapas antes
de energizer
el equipo.
El
incumplimiento
de estas
instrucciones
puede provocar
la muerte o
lesiones serias.
RISQUE DE
DESCHARGE
ELECTRIQUE
OU EXPLOSION
• Eteindre
toutes les
sources
d'énergie de
cet appareil
avant de
travailler
dessus de cet
appareil
• Vérifier tous
connections, et
remettre tous
couverts en
olace avant de
mettre sous
De non-suivi de
ces instructions
provoquera la
mort ou des
lésions sérieuses
sérieuses.
GEFAHR EINES
ELEKTRISCHE
N SCHLAGES
ODER EINER
EXPLOSION.
• Stellen Sie
jeglichen
Strom ab, der
dieses Gerät
versorgt, bevor
Sie an dem
Gerät Arbeiten
durchführen
• Vor dem
Drehen auf
Energie alle
Anschlüsse
überprüfen
und alle
Abdeckungen
ersetzen.
Unterlassung
dieser
Anweisungen
können zum
Tode oder zu
schweren
Verletzungen
führen.
RISCHIO DI
SCOSSA
ELETTRICA O
DELL’ESPLOSIONE.
• Spenga tutta
l'alimentazione
che fornisce
questa
apparecchiatura
prima di lavorare
a questa
apparecchiatura
存在电击、
爆炸或电弧
闪烁危险
•
在操作此设
备之前请先
关闭电源。
若不遵守这些说明,
可能会导致严重的
人身伤害甚至死亡。
• Verificare tutti
i collegamenti
e sostituire
tutte le coperture
prima
dell’accensione
L'omissione di
queste istruzioni
provocherà la
morte o
lesioni serie
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
RISK OF MATERIAL DAMAGE AND HOT
ENCLOSURE
RISQUE DE DOMMAGE MATERIEL ET DE
SURCHAUFFE DU BOITIER
GEFAHR VON MATERIALSCHÄDEN UND
GEHÄUSEERHITZUNG
• The product's side panels may be hot, allow
the product to cool before touching.
• Follow proper mounting instructions including
torque values.
• Do not allow liquids or foreign objects to enter
this product.
• Les panneaux latéraux du produit peuvent être
chauds. Laisser le produit refroidir avant de le
toucher.
• Respecter les consignes de montage, et
notamment les couples de serrage.
• Ne pas laisser pénétrer de liquide ni de corps
étrangers à l'intérieur du produit.
• Die Seitenwände können heiß sein. Lassen Sie
das Produkt abkühlen, bevor Sie es berühren.
• Beachten Sie die Montageanweisungen,
• Führen Sie keine Flüssigkeiten oder
Fremdkörper in das Produkt ein.
Le non-respect de cette directive peut entraîner,
Failure to follow these instructions can result in des lésions corporelles graves ou des
serious injury, or equipment damage.
dommages matériels.
Die Nichtbeachtung dieser Anweisung kann
Körperverletzung oder Materialschäden
zur Folge haben.
RIESGO DE DAÑOS MATERIALES Y DE
SOBRECALENTAMIENTO DE LA UNIDAD
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO
CALDO
材料损坏和高温外壳的危险性
• Los paneles laterales del producto pueden
estar calientes. Esperar que el producto se
enfríe antes de tocarlo.
• Respetar las instrucciones de montaje, y en
particular los pares de apretado.
• No dejar que penetren líquidos o cuerpos
extraños en el producto.
• I pannelli laterali dell'apparecchio possono
scottare; lasciar quindi raffreddare il prodotto
prima di toccarlo.
• Seguire le istruzioni di montaggio corrette.
• Non far entrare liquidi o oggetti estranei in questo
apparecchio.
Si no se respetan estas precauciones pueden
producirse graves lesiones, daños materiales.
La mancata osservanza di questa precauzione può
causare gravi rischi per l'incolumità personale o
danni alle apparecchiature.
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
• 产品的一侧面板可能很热,在其冷却前请
不要触碰。
• 遵照正确的安装说明,包括扭矩值。
• 请勿让液体及其他异物进入本产品。
如不能正确执行这些操作说明,
极有可能造成严重人体伤害或者设备的损坏。
DIN Rail Mount
Datasheet
ANNEX - ENVIROMENTAL INFORMATION
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.
Part
Name
Toxic or hazardous Substance and Elements
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr (VI))
Polybrominated
biphenyls
(PBB)
Polybrominated
diphenyl ethers
(PBDE)
Semiconductor die
Solder
附件 - 环保信息
此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006,
电子信息产品污染控制标识要求。
部件
名称
铅
汞
镉
有毒有害物质或元素
六价铬
多溴联苯
(Pb)
(Hg)
(Cd)
(Cr (VI))
半导体芯片
焊接点
50
Do not forget to visit us at: www.crydom.com
Copyright © 2017 Crydom Inc. Specifications subject to change without notice.
(PBB)
多溴二苯醚