Cynergy3 FSHPLC Flow switch for connection to plc Datasheet

FSHPLC
Flow switch for connection to PLC
Signal level output for PLC
20 l/min turn on flow rate
Automatic shut down on flow stop
Volt free contact for output to PLC
1”BSP pipe connections
Technical Specification
Screw mount Material
Enclosure material
Enclosure rating
Start up flow rate
Max Pressure
Max Temperature
Pipe connections
Q. min
P max
T max
l/min
bar
°C
BSP
Electrical Specification
Output
Max voltage
Switching Current Max
Vac
mA
Standard Parts
FSH10PLC
On flow rate
20 l/min
Brass
Polyamide
IP54
20
10
100
1”
SPNO volt free contact
<5
<1
The FSHPLC can be used to control some
other equipment or process via a PLC.
It could be for controlling a circulating or
centrifugal electric pump that is providing
increased pressure or flow within water
systems with storage tanks.
95
The FSHPLC switches the output, once the
flow rate through the pipe exceeds 20
l/min.
A flow of less than 20 l/min, whether due
to a lack of supply (e.g. tank empty) or to a
decrease in demand(e.g. tap closing), will
turn the output off again.
94
22
113
Cynergy3 Components Ltd.
7 Cobham Road
Ferndown Industrial Estate
Wimborne, Dorset BH21 7PE
Telephone +44 (0) 1202 897969
Email:[email protected]
ISO9001 C E R T I F I E D
www.cynergy3.com
© 2014 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
FSHPLC
Flow switch for connection to PLC
Installation information
The flow switch is designed to be used in a horizontal pipe
with the switch mounted through a side entry. Pipe
connection is G1” (1”BSP). The device relies on the flow of
liquid working in opposition to the spring loaded paddle.
The liquid flow moves the paddle within the pipe, when the
flow increases beyond the minimum specified level. A
magnet mounted on the head of the paddle closes a
magnetic switch in the control circuit.
The output switch will open, if the flow drops below the
specified level and the paddle has returned to the rest
position.
G1” socket connection
Flow
Direction
The output is a SPNO switch with contacts rated to
1mA/5Vac.
G1” - G4” pipe size
G1” mounting thread
“o” ring seal
Adaptor ring
“o” ring seal
Cynergy3 Components Ltd.
7 Cobham Road
Ferndown Industrial Estate
Wimborne, Dorset BH21 7PE
Telephone +44 (0) 1202 897969
Email:[email protected]
ISO9001 C E R T I F I E D
www.cynergy3.com
© 2012 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
Similar pages