Systemsensor A5060 Intelligent low-flow duct smoke detector Datasheet

H
V
A
C
S
Y
S
T
E
M
S
M
O
N
I
T
O
R
I
N
G
Intelligent Low-Flow
Duct Smoke Detectors
Intelligent Models Available
DH200PL
DH200RPL
DH200PL (non-relay)
DH200RPL (with relay)
Product Overview
Air velocity rating from 100 to 4000 feet
per minute (0.5 to 20.32 m/sec.)
Patented telescopic sampling tube
Easily accessible code wheels
Outside mounting tabs
Easy and quick mounting to round
or rectangular ducts from 1′–12′
(0.3–3.7 meters) wide
Easy to clean
UL recognized field-replaceable
power and sensor boards
Transparent cover for convenient
visual inspection
UL 268A listed
3-year warranty
DH200PL (non-relay)
Has outputs for remote LED display,
remote test
Incorporates zener diodes to conserve
power for communications to other
devices
Requires com line power only
DH200RPL (with relay)
Powered outputs for remote LED, and
remote test and sounder
Two form “C” auxiliary contacts
Can be configured as a relay version or
jumpered to mimic a non-relay version
Patented cover tamper trouble signal
Requires both com line power and one of
the following; 24VAC/DC or
120/220VAC for operation
APPROVED
S911
342-02-E
3013287
CS308
2125
3240-1209:155
The System Sensor Innovair™ DH200 Low-Flow Series photoelectric air duct smoke
detectors are capable of sensing smoke in air velocities from 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
This Innovair features low-flow technology that enables duct smoke detection throughout a broad range of airflow environments. Many difficult to solve HVAC applications
occur in low airflow duct applications where reliable smoke detection is critical. Innovair
low-flow technology can detect smoke at air speed velocities of 100 feet per minute or
greater, while continuing the same reliable performance to 4,000 feet per minute.
The DH200 Series Detector samples air currents passing through a duct and gives
dependable performance for shutdown of fans, blowers, and air conditioning systems,
preventing the spread of toxic smoke and fire gases through the protected area.
These intelligent sensors communicate and are continuously monitored through the communication line. Detector sensitivity changes caused by dirt, temperature, or humidity
are reported to the panel, allowing compensation algorithms to maintain the sensor’s set
sensitivity. An advance indication at the panel specifies the sensor address, allowing for
selected maintenance to be performed as needed.
Remote alarm annunciation can be accomplished by using the RA400Z Remote
Annunciator or the RTS451 or RTS451KEY Remote Test Station. Both these devices
allow testing of the detector from a remote location.
The Innovair family is designed for simplified installation and easy maintenance. The
modular construction allows for easy cleaning and uncomplicated field replacement of
the UL recognized power and sensor boards.
WARNING: Duct smoke detectors have specific limitations.
DUCT SMOKE DETECTORS ARE:
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional duct smoke detector application information.
Architect/Engineer Specifications
The duct smoke detector shall be a System
Sensor Model DH200PL or DH200RPL
Intelligent Low-Flow Duct Smoke Detector
to be used with compatible control panels. The duct smoke detector shall be UL
listed per UL 268A, Standard for Smoke
Detectors for Duct Applications, specifically for use in air handling systems. The
detector shall operate in air velocities from
100 to 4000 feet per minute. The detec-
tor shall be an intelligent photoelectronic
detector. It shall be capable of local testing
via magnetic switch or remote testing from
the RTS451 or RTS451KEY Remote Test
Station. The duct smoke detector housing
shall incorporate an airtight smoke chamber in compliance with UL 268A. The
housing shall be capable of mounting to
either rectangular or round ducts without
adapter brackets. An integral filter system
shall be included to reduce dust and residue effects, thereby reducing maintenance
and servicing. Sampling tubes shall be easily installed after the housing is mounted
to the duct by passing through the duct
housing. Terminal connections shall be of
the strip and clamp method suitable for
12-18 AWG wiring.
DH200PL Specifications
Accessory Current Loads
Voltage Range
15 to 32 VDC
Standby Current
300µA @ 24 VDC (one communication ever y 5 seconds with LED blink
enabled)
Device
Standby
Alarm
RA400Z
0 mA
10 mA Max.
RTS451/RTS451KEY
0 mA
7.5 mA Max.
COM (+)
COM (-)
COM(+)
COM(-)
RTS451
KEY
COMMON
TEST
COM (-)
COM(-)
RA400Z
COM (+)
COM(+)
COMMON
TEST
RTS451
KEY
+
RA400Z
Wiring diagram for DH200PL Duct Smoke Detector using a UL listed control panel
COMMUNICATION
LINE
–
UL LISTED CONTROL
PANEL
1ST DETECTOR
IN LOOP
2ND DETECTOR
IN LOOP
Wiring diagram for DH200PL Duct Smoke Detector with optional RA400Z
COM(-)
COM(+)
RA400Z
TEST
RTS451
KEY
RA400Z
COMMON
COMMON
(Must break tab on back of RA400Z when used with DH200PL.)
+
RA400Z
DH200PL
COM(-)
COM(-)
COM(+)
COMMON
RTS451
KEY
TEST
RA400Z
TEST
RA400Z
RTS451
KEY
COMMON
COM(+)
Wiring diagram for DH200PL Duct Smoke Detector with RTS451/RTS451KEY
COMMON
4
TEST
5
6
FIELD INSTALLED
JUMPER
1
LED
DH200PL
2
3
RESET
RTS451/RTS451KEY
FOR RTS451, TERMINAL 3 IS NOT USED.
(RTS451 DOES NOT HAVE A TERMINAL 6.)
FOR RTS451KEY, TERMINALS 3 AND 6
ARE NOT USED.
DH200RPL Specifications
Current Requirements (using no accessories)
Power supply voltage
20-30 VDC
24 VAC, 50-60HZ
120VAC, 50-60Hz
220/240 VAC, 50-60Hz
Max. standby current
26 mA
65 mA RMS
44 mA RMS
25 mA RMS
Max. alarm current
87 mA
182 mA RMS
52 mA RMS
30 mA RMS
Alarm response time
3 to 10 sec.
3 to 10 sec.
3 to 10 sec.
3 to 10 sec.
Power up time
2 sec.
2 sec.
2 sec.
2 sec.
Contact Ratings
Accessory Current Loads at 24 VDC
Alarm auxiliar y contacts* (DPDT)
10 A @ 30 VDC
10 A @ 277 VAC (0.75 power factor)
240 VA @ 249 VAC (0.4 power factor)
1
⁄8 HP @ 120 VAC
1
⁄4 HP @ 240 VAC
Device
Standby
Alarm
PA400
0 mA
15 mA Max.
RA400Z
0 mA
12 mA Max.
RTS451/RTS451KEY
0 mA
10 mA Max.
Supervisory contact (SPST)
2.0 A @ 30 VDC (resistive)
*Minimum switching current for auxiliar y contact
must be 100 mA DC minimum @ 5 VDC.
Wiring diagram for DH200RPL Duct Smoke Detector using a UL listed control panel
1
2
COM (-)
COM (+)
COM (-)
+
COM (+)
NOTE: Jumper J1 shunt must be installed for 2-W applications. J1 shunt must be removed for power PCB super vision.
1 2
NOTE: External power of 24V AC/DC or
120/220 VAC must be connected in
order to power all remote horn or
strobe accessories.
COMMUNICATION
LINE
–
UL LISTED CONTROL
PANEL
J1 JUMPER
1ST DETECTOR
IN LOOP
J1 JUMPER
2ND DETECTOR
IN LOOP
Wiring diagram for DH200RPL Duct Smoke Detector with optional RA400Z
5 7
Wiring diagram for DH200RPL Duct Smoke
Detector with RTS451/RTS451KEY
RTS 451/RTS451KEY
RA400Z
1
ALARM SIGNAL
3
DO NOT BREAK TAB ON RA400Z
NOT USED
5
6
7
2
4
4
3
5
ALARM SIGNAL
NOT USED
AUX. POWER (—)
5 = Alarm Signal
7 = Aux. Power (—)
CIRCUIT
REFERENCE
TEST +
TEST —
TEST
SWITCH
Wiring diagram for DH200RPL Duct Smoke Detector with optional PA400
5 7
5 = Alarm Signal
7 = Aux. Power (—)
PA400
FOR RTS451, TERMINAL 3 IS NOT
USED. (RTS451 DOES NOT HAVE
A TERMINAL 6.) FOR RTS451KEY,
TERMINALS 3 AND 6 ARE NOT USED.
Innovair™ 200 Series Low-Flow Specifications
Operating Temperature Range
32° to 131°F (0° to 55°C)
Duct Air velocity
100 – 4000 ft./min. (0.5 – 20.32 m/s)
Width
51⁄ 2″ (14 cm)
Operating Humidity Range
10% to 93% relative humidity
(non-condensing)
Shipping Weight
DH200PL:
3.35lbs. (1.5 kg)
Depth
23⁄ 4″ (7 cm)
Storage Temperature Range
–22º to +158ºF (–30º to +70º C)
Length
143⁄ 4″ (37 cm)
DH200RPL:
3.90lbs. (1.8 kg)
Ordering Information
Par t No.
Description
Accessories
Description
DH200PL
Innovair™ intelligent low-flow photoelectric nonrelay duct smoke detector
RTS451
Remote test station (see below)
RTS451KEY
Remote test station w/key (see below)
DH200RPL
Innovair™ intelligent low-flow photoelectric with
relay duct smoke detector
RA400Z
Remote LED (see below)
ST-1.5
Metal sampling tube duct widths 1′–2′
PA400
Mini-Aler t™ Sounder (see below)
ST-3
Metal sampling tube duct widths 2′–4′
F36-09-11
Replacement filters
ST-5
Metal sampling tube duct widths 4′–8′
M02-04-00
Test magnet
ST-10
Metal sampling tube duct widths 8′–12′
P48-21-00
End cap for metal sampling tube
A5053
Replacement photoelectric sensor board
P48-61-00
End cap for plastic sampling tube
A5060
Replacement power board for DH200RPL (w/relay)
S08-39-01
Replacement photo insect screen
A5067
Replacement power board for DH200PL (w/o relay)
T80-71-00
Replacement plastic sampling tube
ALARM
ALARM
RESET
ON
TEST
RESET
RTS451
Remote Test Station
(UL S2522)
RTS451KEY
Remote Test Station with
key (UL S2522)
RA400Z
Remote
Annunciator
(UL S2522)
PA400
Mini-Aler t™ Sounder
(UL S3593)
Device cannot be wired
directly to DH200PL
(non-relay).
System Sensor Canada
Ph: 905.812.0767
Fx: 905.812.0771
System Sensor in China
Ph: 86.29.524.6253
Fx: 86.29.524.6259
System Sensor – Far East
Ph: 85.22.191.9003
Fx: 85.22.736.6580
System Sensor Europe
Ph: 44.1403.276500
Fx: 44.1403.276501
System Sensor in Singapore
Ph: 65.6273.2230
Fx: 65.6273.2610
System Sensor – Australia
Ph: 613.54.281.142
Fx: 613.54.281.172
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800/SENSOR2
Fx: 630/377-6495
Documents-on-Demand
800/736-7672 x3
www.systemsensor.com
© 2003 System Sensor. The company reserves the right to change product specifications without notice.
System Sensor – India
Ph: 91.124.637.1770 x.2700
Fx: 91.124.637.3118
A05-0353-000•7/03•#1012