Omron CS1D-CPU67H Cs1 cpus mean ultimate performance Datasheet

CPU Overview
CS1 CPUs Mean Ultimate Performance
J Features
•
•
•
•
•
•
0.02 µs execution time per basic instruction.
Up to 250K steps of program memory capacity.
Up to 448K words of built-in data memory.
Up to 64 MB of auxiliary compact flash memory
available.
Built-in peripheral and RS-232 port.
Inner board compartment for additional
communication ports.
J CPUs — Basic Specifications
Model
No. of I/O bits
Program
capacity
Data memory capacity
(See note.)
LD
instruction
processing
speed
Built-in ports
Options
CS1H-CPU67H
5,120
,
bits ((Up
p to 7
E
Expansion
i R
Racks)
k )
250K steps
448K words
0.02 µ
µs
256K words
CS1H-CPU65H
60K steps
128K words
Peripheral
p
port
p
and
d RS-232C
RS 232C
port
Memoryy Cards
120K steps
CS1H-CPU64H
30K steps
64K words
CS1H-CPU63H
20K steps
CS1H-CPU66H
CS1G-CPU45H
5,120 bits (Up to 7
Expansion Racks)
60K steps
128K words
CS1G-CPU44H
1,280 bits (Up to 3
Expansion Racks)
30K steps
64K words
CS1G-CPU43H
960 bits ((Up
p to 2
E
Expansion
i R
Racks)
k )
20K steps
CS1G-CPU42H
Inner Board, such
as Serial
Communications
Board
0.04 µs
10K steps
Note: The available data memory capacity is the sum of the Data Memory (DM) and the Extended Data Memory (EM).
Programmable Controller
CS1
C--11
CPU Overview
CS1D Duplex System CPUs for Increased Reliability
J Features and Functions
•
•
•
•
•
•
•
•
•
High reliability for a no-fail redundant system. The CS1D offers
redundancy of CPUs, Power Supplies, and Controller Link
Network.
CPUs, Power Supplies, Communication Modules, Basic and
Special I/O Modules can be replaced during system operation.
Hot standby technology allows easy and fast maintenance.
Hot standby system adopted for CPU duplexing
Same support software as CS1 (CX-Programmer).
Complete compatibility among CS1 I/O Modules.
Same speed, I/O capacity and memory size as CS1.
Built-in peripheral and RS-232C port.
Inner board compartment for additional communications ports.
Basic specifications for CS1D Duplex CPUs.
J Basic Specifications for CS1D CPU Models
Model
No. of I/O bits
Program
capacity
Data memory
capacity
LD Instruction
processing
speed
Built-in ports
Options
CS1D-CPU65H
5,120 bits
60K steps
128K words
0.02 µs
Memory Cards
250K steps
448K words
Peripheral port
and RS-232C
portt
CS1D-CPU67H
Inner board, such as
serial communication
board
Note: The available data memory capacity is the sum of the Data Memory (DM) and the Extended Data Memory (EM).
With the CS1 PLCs, Memory Cards and specified ranges of the EM Area can be used as file memory. File memory can be used to
store the entire user program, I/O memory contents, and/or parameter area contents.
C--12
Programmable Controller
CS1
CPU Overview
CPU Components
CS1H-CPUjjH, CS1D-CPUjjH
Indicators
Inner Board Compartment
An Inner Board can be mounted
here.
Memory Card Indicators
The MCPWR indicator lights green when
power is being supplied. The BUSY indicator lights orange when the Memory Card is
being accessed.
Memory Card Power Supply Switch
The Memory Card power supply switch
is pressed to turn OFF power before
removing the Memory Card.
Memory Card Eject Button
Press the Memory Card eject button
to remove the Memory Card.
Peripheral Port
The peripheral port is connected to
Programming Devices, such as a
Programming Console or host computer.
RS-232C Port
The RS-232C port is connected to
Peripheral Devices other than
Programming Consoles, such as
host computers, general-purpose
external devices, and Programmable Terminals.
Memory Card Connector
Memory Card
Programmable Controller
CS1
C--13
CPU Overview
Optimum Speed and Processing Capabilities
J Ultimate Machine Performance with High-Speed Processing
CS1 PLCs provide ample speed for advanced machine interfaces, communications, and data processing.
Execution Times from 20 ns
Fast instruction processing includes 0.02 µs for LD and
0.18 µs for MOV. And, special instructions are processed
almost as fast as basic ones (e.g., as fast as 0.18 µs for
some instructions).
CS1 Series
0.02 µs
Extremely Fast Peripheral Servicing and
I/O Refresh Speed
•
•
•
CS1 refresh time for 96 input points: 0.02 ms
(15 times faster)
For 96 output points: 0.02 ms
(10 times faster)
For 256 words for Communications Module: 0.45 ms
(4 times faster)
CS1
0.18 µs
I/O refresh
96-pt Input Module
+
0.18 µs
96-pt Output Module
Communications
Module (256 words)
30 Times the Overall Cycle Speed
The following examples are for 30K-step programs
•
•
•
Basic instructions: 50%
MOV instructions: 30%
Arithmetic operation instructions: 20%
CS1
C200HX/HG/HE
34 ms
1.2 ms
I/O refresh
I/O refresh
Peripheral service
Peripheral service
J Large Capacities Fit the Application
Program Capacity
I/O Capacity
Create programs with up to 250K steps.
Handle up to 5,120 I/O points.
CS1
CS1
.
250K steps max.
5,120 I/O points
C--14
Programmable Controller
CS1
CPU Overview
Performance Flexibility and Hardware/Software Compatibility
J Data Memory
J Use Legacy Programs
Use up to 448K words of data memory (word data).
The CX-Programmer can be used to convert programs
from other OMRON PLCs.
CS1
D0000
to
D32767
32K
words
Up to 13 banks
(416K words)
448K
words
E0_00000
to
EC_00000
C200HS
C200HX/HG/HE
CVM1/CV Series
C1000H
CX-Programmer
conversion
CS1
J Timers/Counters
Program up to 4,096 timers and 4,096 counters.
CS1
J Large Capacity Data Handling with
Each Instruction
The basic operand specifications have been converted
from BCD to binary to increase data handling capacity.
4,096 timers and
4,096 counters
Item
C200HX/HG/HE
CS1
Block transfers
0 to 6655 words
0 to 65535 words
Indirect addressing
range
DM 00000 to
DM 9999
D00000 to D32767
J Use C200H Modules
All of the I/O Modules and Special I/O Module and a portion of the Communications Modules used for the C200H,
C200HS, and C200HX/HG/HE can be used, as can C200HX/HG/HE Expansion I/O Racks. (Only CS1 Modules can be
used on long-distance Expansion I/O Racks using I/O Control Modules or I/O Interface Modules.)
All C200H
I/O Modules
(except:
C200HID001/002)
All C200H
Special
I/O
Modules
C200H Communications Modules:
• SYSMAC BUS Remote I/O Master Module
• DeviceNet Master Module
• CompoBus/S Master Module
• PC Link Module
• B7A Link Module
CS1 I/O Modules
CS1 Special I/O Modules
CS1 Series
CS1 CPU Bus Modules
(including Communications Modules)
Note: There are restrictions in data transfers with the CPU for CIO and DM Area specifications (e.g., address of transfer source or transfer destination) for the C200H Special I/O Modules, as well as in data transfers programmed from these Modules (e.g., using PC
READ or PC WRITE instructions). Refer to CS1 PLC manuals for details (refer to: information on restrictions in using C200H Special I/O Modules).
Programmable Controller
CS1
C--15
CPU Overview
Expansion Capabilities
J Up to 7 Expansion Racks
System expansion can be achieved by simply connecting the CPU Rack to an Expansion Rack using an I/O Connecting
Cable. Up to 7 Expansion Racks can be connected to one CPU with a total distance of 12 m. Long distance expansion of
50 m can be achieved by using an I/O Control Module.
For a complete pattern of Expansion Systems, including combinations with C200H Expansion I/O Racks, please refer to
the System Power and Expansion section.
CPU Rack with CS1 Expansion Racks
CPU Rack with CS1 Long-Distance Expansion Racks
I/O Control Module
CS1 Expansion Rack
CPU Rack
CS1 I/O
Connecting
Cable
Long-distance Connecting Cables
I/O Interface Module
CS1 Expansion Rack
CS1 I/O
Connecting
Cable
CS1 Expansion Rack
12 m
CS1 I/O
Connecting
Cable
CS1 Expansion Rack
Long-distance
Connecting Cable
I/O Interface Module
CS1 Expansion Rack
7 Racks
max.
Long-distance
Connecting Cable
50 m
CS1 Expansion Rack
I/O Interface Module CS1 Expansion Rack
Long-distance
Connecting Cable
I/O Interface Module
CS1 Expansion Rack
Terminating Resistor
C--16
Programmable Controller
CS1
Note:
C200H Modules cannot be mounted
to Long-Distance Expansion Racks.
I/O Interface Module
CS1 Expansion Rack
Long-distance Connecting
Cable
I/O Interface Module
CS1 Expansion Rack
Up to 7
Racks in
2 series
Long-distance Connecting
Cable
I/O Interface Module
CS1 Expansion Rack
Terminating Resistor
CPU Overview
Outstanding Connectivity and Compatibility
J CS1 Offers More
More serial communications ports, more protocols. Up to 34 port connections with protocol setting for each port.
J Protocol Macros
PLCs with Protocol Macros
Data transfer protocol for serial communications vary with the manufacturer and
with devices. Differences in protocols can make communications between devices
by different manufacturers very difficult, even when electrical standards are the
same.
CS1 PLC
Non-OMRON
PLC
OMRON’s protocol macros solve this problem by:
RS-232C
•
Non-OMRON
Temperature
Controller
RS-232C
Enabling easy creation of protocol macros designed to match the protocol of a
connected device.
Allowing you to communicate with essentially any device having an RS-232C,
RS-422, or RS-485 port, without having to write a special communications
program.
•
J The Two Main Functions of Protocol Macros
1. Creating Communications Frames
2. Creating Frame Send/Receive Procedures
The communications frames can be easily created
according to the specifications required by the connected device. Data from I/O memory in the CPU can
be easily included as part of a communications frame
to read from or write to I/O memory.
The required processing, including sending and receiving
communications frames, can be performed one step at a
time according to the results of the previous step, and
then CX-Protocol can be used to trace send and receive
data.
Variable R ( )
Create
Port/Module
CPU
I/O memory
Read
Required
processing
PMCR
Step 0
Connected
device
Send
Step n
(as required)
Address
Header
Data
Variable W ( )
Terminator
Check code
I/O memory
Receive
Write
J Application Examples
Standard System Protocols
User-Created Protocols
Data transfers with OMRON components can be easily
performed using standard system protocols. There is no
need to develop your own protocols in this case.
Data transfers with non-OMRON components can be easily
created just by defining parameters using the CX-Protocol
Windows tool.
Standard system protocol
Example: E5CK Temperature Controller
CS1 PLC
CX-Protocol
Creates protocols.
CS1 PLC
OMRON component
Example: E5CK
RS-232C
CD-ROM
Non-OMRON
component
Programmable Controller
CS1
C--17
CPU Overview
Outstanding Connectivity and Compatibility
OMRON provides all of the capabilities and capacity you
need for the advanced programming required for humanmachine interfaces, communications, data processing, and
other required applications.
J Protocols for Advanced Programming
High-Speed NT Links
High-speed NT Links that are three times faster than standard NT Links are possible with NS-series PTs. This speed
is particularly important when connecting to more than
one PT.
Host Links
Custom Protocols
Host Link (C-mode) commands or FINS commands placed
within host link headers and terminators can be sent to a
host computer to read/write I/O memory, read/control the
operating mode, and perform other operations for the PLC.
I/O instructions for communications ports (TXD(236) and
RXD(235)) can be used for simple data transfers (custom
protocols), such as to input data from bar code readers or
output data to a printer. Start/end codes can be specified,
and RS, CS, and other control signals can be handled.
(Custom protocols can be used only for the CPU’s built-in
RS-232C port.)
Unsolicited messages can also be sent from the PLC to the
host computer by sending FINS commands from the ladder
program using the SEND(090), RECV(098), and
CMND(490) instructions.
CPU
TXD
or
RXD
Command
General-purpose
external device
Response
General-purpose Protocols Using BASIC
An ASCII Module can be used to create essentially any
protocol for an external device using the BASIC language,
providing the ability to handle applications for which protocol macros cannot be created.
1:N NT Links
ASCII Module
The PLC can be connected to an Operator Interface Terminal via RS-232C or RS422A/485 ports, and I/O memory in
the PLC can be allocated to various Operator Interface
functions, including status control areas, status notifications
areas, touch switches, lamps, memory tables, and other
objects.
General-purpose
external device
Omron’s Operator
Interface Terminal
Omron’s Operator
Interface Terminal
Note: Either one or up to eight Operator Interface
Terminals can be connected to a PLC using1:N NT Links.
C--18
Programmable Controller
CS1
CPU Overview
Outstanding Connectivity and Compatibility
J Protocol List
The following protocols are supported for serial communications.
Protocol
Main Destinations
Outline
Commands/Instructions
Host Link
(SYSMAC WAY)
Computers, OMRON
Operator Interface Terminals
Communications between host
computers and PLCs.
Host Link commands or FINS
commands (unsolicited
messages supported)
Custom
General-purpose devices
Custom communications with
general-purpose external devices.
TXD and RXD instructions
Protocol Macros
General-purpose devices
(including OMRON
components)
Sending/receiving messages
(communications frames) matched to the
communications specifications of external
devices.
PMCR instruction
1:N NT Links
OMRON Operator Interface
Terminals
High-speed communications with
Operator Interface Terminals.
None
Peripheral bus
Support Software
Communications with Support Software
tools running on host computers.
None
General
(written in BASIC)
General-purpose devices
Unrestricted communications with
external devices.
BASIC
Note: Refer to Serial Communications in the Industrial Networks and Communications Section for the ports that can be used for each
protocol.
J Overview of Serial Communications
Support Software
CX-Programmer
CX-Protocol
CX-Motion
Programming
Console
Host Computer
ASCII Module
Serial Communications
Modules
Host Link
Serial Communications
Board
Operator
Interface
CPU
Peripheral Bus (Protocol Bus)
NT Link
General-Purpose
External Device
General-purpose
protocol created in
ASCII Module
using BASIC.
Protocol Macro
General-Purpose
External Device
Temperature Controller,
Bar Code Reader, etc.
Microcomputer and
other devices
Non-OMRON PLC
and other devices
Protocol Macro
Protocol Macro
Programmable Controller
CS1
C--19
CPU Overview
Simple, Easy to Understand Programs
J CS1 Makes It Effortless
J Easily Handle Table Data
Index registers, table data, repeat instructions, block
programs, text strings, and more.
Table Data Instructions
One-Word Records
Instructions are provided to find the maximum value,
minimum value, and search values.
J Simplify Programs with Index
Registers
Index registers can be used as memory pointers to
enable easily changing the addresses specified for
instructions. Using an index register can often enable
one instruction to preform the processing previously
performed by many instructions.
Pointer
1 word
1 record
1 record
Process table
data, e.g., search
for maximum value
1 word
I/O
Multiword Records
Areas of memory can be defined as tables with the
specified record size (words). Index registers can be used
with these tables to easily sort records, search for values,
or otherwise process the records in the table.
Index Register
Previous
Simplification Using Index Register
Instruction A
m
Instruction A
Instruction A
Repeated
IR0
Record 1
Many words
m+1
1 record
Example.: Product
Data by Model
Record 2
Temp. setting
Indirect
addressing
using index
register
IR0 + 1
Instruction A
m+2
C--20
For example, the temperature, pressure, and other settings for each model of a product can be set in separate
records and the data handled by record.
Programmable Controller
CS1
Pressure setting
Many words
1 record
Many words
1 record
Record N
CPU Overview
Simple, Easy to Understand Programs
J Repeat Processing Is Simple
J Macro (MCRO) Instruction
Instructions are provided that let you easily repeat
sections of the program. Repeat execution can also
be ended for a specified condition.
Macro instructions can be used to execute the same
subroutine program with different operands from different
locations in the programs (subroutine instruction with
argument).
S
Returned
values
Repeated n times.
Arguments
J Program Logic Flow Control with
Block Programming Sections
A block of mnemonic programming instructions can be
executed as a group based on a single execution
condition. IF/THEN, WAIT, TIMER WAIT, and other instructions can be used inside the block programming
section to easily program logic flow control that is difficult
to program with ladder diagrams.
Subroutine
J Handle Text Strings Quickly
Manufacturing instruction can be obtained from a host
computer or other external source, stored in memory,
and then manipulated as text strings as required by the
applications. The text strings can be searched, fetched,
reordered, or other processed in the CPU of the PLC.
Host computer
Block programming section
PLC
Manufacturing
instructions in
text form.
Programmable Controller
Text processing
in the CPU.
CS1
C--21
CPU Overview
Maintenance and Management
J File Applications
Use Memory Cards to Handle Files Containing Various Types of Data
Manipulate PLC File Data Using Windows Files
• The user program, parameters, I/O memory,
names, I/O comments, and block comments can
all be handled as file data. File data can be used
to standardize programs and initialization data
for each system, and comments can be stored
as file data on Memory Cards.
System C
System B
System A
User program
PC Setup
I/O tables
DM data
Stored and
standardized
by system.
• The CX-Programmer or a Programming
Console can be connected to a CS1 PLC to
transfer files between the CPU’s memory and
Memory Cards (or EM File Memory).
• As Windows files, file icons can be dragged and
dropped to a Memory Card or computer storage
device to easily copy the files.
or
CPU
Note: A Memory Card Adapter can be used to mount
Memory Cards into a PC card slot on a computer
to use them as computer storage devices.
Programming
Device
Memory
Memory
Card
EM File
Memory
J Handle File Data Onsite with Programming Consoles
• A Handheld Programmer can be connected to the
PLC to transfer files between between the CPU’s
memory and Memory Cards (or EM File Memory).
All you need is a Handheld Programmer and
Memory Cards to change data onsite.
Note: Program and setup data can be easily backed up
onsite using only the CPU, without a Programming
Device. Programmed replacement of programs
designated in Memory Cards is also possible without a Programming Device.
Production
site
Office
Handheld
Programmer
PC Card Adapter
Download
Upload
Memory Card
J To Change Program, Simply Change Cards
• File data can be automatically transferred
from Memory Card to the CPU when power
is turned ON, enabling Memory Cards to be
used for operation in the same way as is
possible with ROM.
Step 1
Safe transfer files in
Memory Card.
Step 2
Create Memory Cards for
each product or line.
A
B
Step 3
Replace the Memory
Card and turn ON
power.
C
Power ON
J Manipulate Files During Operation
• File read and write instructions can be used
during operation to transfer files between the
CPU’s memory and Memory Cards (or EM File
Memory). Trend data, quality control data, other
data from memory can be stored during
operation in Memory Cards or EM File Memory.
Note: With EV1-version CPU, CSV and text files can be
saved, and programmed file operations, such as file
name changes and deletions, are also possible.
C--22
Programmable Controller
CS1
Saved as files.
FWRIT
Memory
Card
EM
Saved as file.
File
memory
CPU Overview
Maintenance and Management
J A Wide Range of Special Functions
Cycle Time Functions
Application
Solutions
Reducing the cycle time.
• Place tasks that are not being executed on standby.
• Create subroutines for portions of tasks executed only under special conditions.
• Disable cyclic refreshing for Special I/O Modules when not required each cycle.
Shorter cycle time
Eliminating deviations in I/O response time.
• Set the cycle time to a fixed time.
Set fixed time.
• Use the cycle time monitoring function to stop operation when the cycle time is
too long.
Stopping operation for long cycle times.
Over time
Operation
stopped.
Reducing I/O response time for
specific I/O.
Interrupt task
Interrupt input
Highspeed
I/O
Inputting signals (e.g., from photomicrosensors)
that are shorter than the cycle time.
Cycle time
Input pulse
• Use an I/O interrupt task to execute an interrupt program when a specific input
turns ON and then directly refresh external I/O when the appropriate instruction is
executed in the interrupt program.
External I/O can be directly refreshed, either by using immediate refreshing for
instruction operands or by using the IORF instruction to refresh all or a specified
portion of external I/O.
• Use the high-speed pulse input function of the C200H High-Density I/O Modules
(C200H Special I/O Modules). These Modules can detect 1-ms or 4-ms pulses
(except C200H-OD501/OD215,)
• Use the IORF instruction to refresh inputs during program execution to further
increase processing speed.
Detected
Programmable Controller
CS1
C--23
CPU Overview
Maintenance and Management
Interrupt Functions
Application
Solutions
Executing programming without being affected
by the cycle time.
• Use I/O interrupt tasks to execute interrupt programs when specific inputs turn
ON.
Interrupt program
Monitoring operating conditions at a specific
interval.
• Use a scheduled interrupt task to execute an interrupt program at a specific
interval.
Interrupt program
Executing emergency processing for power
interruptions.
Power OFF
• Use the power OFF interrupt task to execute an interrupt program before the
CPU stops. Immediate refreshing can be used inside this interrupt program to
refresh specified outputs.
Interrupt
program
Generating CPU interrupts when data is
received from a serial port.
• Use an interrupt from the Serial Communications Board to execute an interrupt
program when a specific messages received by the Board.
RS-232C
Interrupt
program
External device
Maintenance and Debugging Functions
Application
Solutions
Creating a user-defined error for specific
conditions (e.g., errors or specific signals from
the controlled system) but allow the CPU to
continue running.
• Use the FAL instruction to create a non-fatal user-defined error. An entry can also
be left in the error history when the error occurs.
Generates a non-fatal error.
• FAL can also be used just to leave error history records for specific conditions
that are not necessarily errors.
Creating a user-defined error for specific
conditions (e.g., errors or specific signals from
the controlled system) and stop the CPU as a
result.
• Use the FALS instruction to create a fatal user-defined error. An entry can also
be left in the error history when the error occurs.
Generates a fatal error.
• FALS can also be used to automatically stop operation for specific conditions that
are not necessarily errors.
C--24
Programmable Controller
CS1
CPU Overview
Maintenance and Management
Applications
Solutions
Determining if a specific output turns ON within
a specified time after an input turns ON,
generating an error if the output does not turn
ON, and determining the address in the program
responsible for the output not turning ON.
• Use the FPD instruction to perform time or logic diagnosis of a specified portion
of the program.
Time diagnosis
Program section
Logic diagnosis
Creating a history of user-defined and system
errors that have occurred.
• Use the error log to record up to 20 time-stamped error records.
Creating an external output when a non-fatal
error occurs.
• Use the Non-fatal Error Flag.
Error contents
Error
Placed in time-stamped
error log.
20 records
Turning OFF all output from Output Modules for
specific conditions.
• Use the Load OFF Bit.
Turning OFF all output from Output Modules
during trial system operation.
Non-fatal error occurs.
OFF
ON
Maintaining I/O memory status when starting
operation.
• Use the I/O memory hold function to start program execution with the same I/O
memory status as the last time the program was executed.
Operation started.
Status held.
Correcting the program during operation.
• Use the CX-Programmer to change the program as required during operation.
CX-Programmer
Program
Continuous instructions
Changes
Sampling specified I/O memory bits or word
data.
• Scheduled sampling
• Use the data tracing function.
Cyclic traces
Sampling instruction
Scheduled traces
• Sampling once per cycle
• User-defined sampling
I/O
memory
Trace
memory
I/O
memory
Trace
memory
I/O
memory
Programmable Controller
Trace
memory
CS1
C--25
CPU Overview
Maintenance and Management
Remote Programming and Monitoring
Requirements
Solutions
Monitoring and editing online for remote PLCs
using telephone lines.
• Perform online programming and monitoring from a CX-Programmer running on
a computer connected to the PLC via a modem.
Modem
RS-232C
Monitoring and editing online from the
CX-Programmer for a remote PLC connected to
a network.
Modem
Telephone line
RS-232C
• Use a Serial Communications Board or Unit; connect to a PLC via a modem; use
an instruction to switch to host link mode, and then program or monitor from the
CX-Programmer. (It’s not necessary to cut the connection during the procedure.)
• Use the host link gateway function to program or monitor any PLC connected to
a Controller Link or Ethernet Network to which the PLC connected to the
computer running the CX-Programmer is connected (via RS-232C).
Host Link
Network
Programming and editing a PLC on a remote
network.
• Use the gateway function to edit any PLC connect to a network up to two
networks away (3 networks including the local network). For example, a PLC on
the Controller Link Network shown below can be accessed from the
CX-Programmer running on a computer connected to a PLC on the Ethernet
Network.
Network 2
Network 1: Ethernet
C--26
Programmable Controller
CS1
Network 3: Controller Link
CPU Overview
CS1 CPU Specifications
J Common Specifications
Item
Specification
Control method
Stored program
I/O control method
Cyclic scan and immediate processing are both possible.
Programming
Ladder diagram
Instruction length
1 to 7 steps per instruction
Ladder instructions
Approx. 400 (3-digit function codes)
Execution time
0 02 µs min.,
min Special instructions: 0.04
0 04 µs min.
min
Basic instructions: 0.02
Number of tasks
288 (256 of which are also used as interrupt tasks)
Cyclic tasks are executed each cycle and are controlled with TKON(820) and TKOF(821) instructions.
The following 4 types of interrupt tasks are supported: Power OFF tasks:1 max., Scheduled interrupt
tasks: 2 max., I/O interrupt tasks: 32 max., External interrupt tasks: 256 max.
Interrupt types
Scheduled Interrupts: Interrupts generated at a time s’cheduled by CPU’s built-in timer.
I/O Interrupts: Interrupts from Interrupt Input Modules.
Power OFF Interrupts: Interrupts executed when the CPU’s power is turned OFF.
External I/O Interrupts: Interrupts from Special I/O Modules, CS1 Special Modules, or Inner Board.
CIO
(Core
I/O) Area
(The CIO
Area can
be used
as work
bits if not
used as
shown
here.)
I/O Area
5,120 : CIO 000000 to CIO 031915 (320 words from CIO 0000 to CIO 0319 )
Setting of first rack words can be changed from default (CIO 0000) so that CIO 0000 to CIO 0999 can be
used.
I/O bits are allocated to Basic I/O Modules, such as CS1 Basic I/O Modules, C200H Basic I/O Modules,
and C200H Group-2 High-density I/O Modules.
Link Area
3,200 (200 words): CIO 10000 to CIO 119915 (words CIO 1000 to CIO 1199 )
Link bits are used for data links and are allocated to Modules in Controller Link Systems and PC Link
Systems.
CS1 CPU Bus
Module Area
6,400 (400 words): CIO 150000 to CIO 189915 (words CIO 1500 to CIO 1899 )
Special I/O
Module Area
15,360 (960 words): CIO 200000 to CIO 295915 (words CIO 2000 to CIO 2959 )
CS1 CPU Bus Module bits store operating status of CS1 CPU Bus Modules. (25 words per Module, 16
Modules max.)
Special I/O Module bits are allocated to CS1 Special I/O Modules and C200H Special I/O Modules. (See
Note.)
(10 words per Module, 96 Modules max.) The maximum number of slots, however, is limited to 80
including expansion slots, so maximum number of Modules is actually 80.)
Note: Some I/O Modules are classified as Special I/O Modules.
Inner Board Area
1,600 (100 words): CIO 190000 to CIO 199915 (words CIO 1900 to CIO 1999 )
Inner Board bits are allocated to Inner Boards. (100 I/O words max.)
CIO
(Core
I/O)
Area
Area,
contd.
(The CIO
Area can
be used
as work
bits if not
used as
shown
here.)
SYSMAC BUS
Area
800 (50 words): CIO 300000 to CIO 304915 (words CIO 3000 to CIO 3049 )
I/O Terminal Area
512 (32 words): CIO 310000 to CIO 313115 (words CIO 3100 to CIO 3131 )
SYSMAC BUS bits are allocated to Slave Racks connected to SYSMAC BUS Remote I/O Master
Modules. (10 words per Rack, 5 Racks max.)
I/O Terminal bits are allocated to I/O Terminal Modules (but not to Slave Racks) connected to SYSMAC
BUS Remote I/O Master Modules. (1 word per Terminal, 32 Terminals max.)
C200H Special
I/O Module Area
DeviceNet
Area
8,196 (512 words): CIO 000000 to CIO 051115 (words CIO 0000 to CIO 0511)
C200H Special I/O Module bits are allocated to C200H Special I/O Modules and allow access separate
from I/O refreshing.
1,600 (100 words): Outputs: CIO 005000 to CIO 009915 (words CIO 0050 to CIO 0099)
Inputs: CIO 035000 to CIO 039915 (words CIO 0350 to CIO 0399)
DeviceNet bits are allocated to Slaves according to DeviceNet remote I/O communications.
PC Link Area
64 bits (4 words): CIO 027400 to CIO 025015 (words CIO 0247 to CIO 0250)
When a PC Link Module is used in a PC Link, use these bits to monitor PC Link errors and operating
status of other CPUs in PC Link.
(This table continues on the next page.)
Programmable Controller
CS1
C--27
CPU Overview
CS1 CPU Specifications
Common Specifications (continued)
Item
Specification
Internal I/O Area
4,800 (300 words): CIO 120000 to CIO 149915 (words CIO 1200 to CIO 1499)
37,504 (2,344 words): CIO 380000 to CIO 614315 (words CIO 3800 to CIO 6143)
These bits in CIO Area are used as work bits in programming to control program execution. They cannot
be used for external I/O.
Work Area
8,192 bits (512 words): W00000 to W51115 (words W000 to W511)
Control programs only. (I/O from external I/O terminals is not possible.)
Note: When using work bits in programming, use bits in Work Area first before using bits from other
areas.
Holding Area
8,192 bits (512 words): H00000 to H51115 (words H000 to H511)
Holding bits are used to control execution of program, and maintain their ON/OFF status when PLC is
turned OFF or operating mode is changed.
Auxiliary Area
Read only: 7,168 bits (448 words): A00000 to A44715 (words A000 to A447)
Read/write: 8,192 bits (512 words): A44800 to A95915 (words A448 to A959)
Auxiliary bits are allocated specific functions.
Temporary Area
16 bits (TR00 to TR15) Temporary bits are used to store ON/OFF execution conditions at program
branches.
Timer Area
4,096: T0000 to T4095 (used for timers only)
Counter Area
4,096: C0000 to C4095 (used for counters only)
DM Area
32K words: D00000 to D32767
Used as a general-purpose data area for reading and writing data in word units (16 bits). Words in DM
Area maintain their status when PLC is turned OFF or operating mode is changed.
Internal Special I/O Module DM Area: D20000 to D29599 (100 words × 96 Units). Used to set
parameters.
CS1 CPU Bus Module DM Area: D30000 to D31599 (100 words × 16 Units). Used to set parameters.
Inner Board DM Area: D32000 to D32099. Used to set parameters for Inner Boards.
EM Area
32K words per bank, 13 banks max.: E0_00000 to EC_32767 max. (Not available on some CPU.)
Used as a general-purpose data area for reading and writing data in word units (16 bits). Words in EM
Area maintain their status when PLC is turned OFF or operating mode is changed.
The EM Area is divided into banks, and addresses can be set by either of following methods.
Changing current bank using EMBC(281) instruction and setting addresses for current bank.
Setting bank numbers and addresses directly.
EM data can be stored in files by specifying number of first bank. (EM file memory)
Data Registers
DR0 to DR15. Store offset values for indirect addressing. Data registers can be used independently in
each task. One register is 16 bits (1 word).
Index Registers
IR0 to IR15. Store PLC memory addresses for indirect addressing. Index registers can be used
independently in each task. One register is 32 bits (2 words).
Task Flag Area
32 (TK0000 to TK0031). Task Flags are read-only flags that are ON when corresponding cyclic task is
executable and OFF when corresponding task is not executable or in standby status.
Trace Memory
4,000 words (500 data trace samples at the maximum sample size of 31 bits and 6 words)
File Memory
Memory Cards: Compact flash memory cards can be used (MS-DOS format).
EM file memory: Part of EM Area can be converted to file memory (MS-DOS format).
OMRON Memory Cards with 8-MB, 15-MB, 30-MB, or 48-MB capacities can be used.
Note: A maximum of 10 or 16 C200H Special I/O Modules can be used depending on the CPU. Some I/O Modules are Special I/O
Modules.
C--28
Programmable Controller
CS1
CPU Overview
CS1 CPU Specifications
J Function Specifications
Item
Specification
Constant cycle time
1 to 32,000 ms (Unit: 1 ms)
Cycle time monitoring
Possible (Module stops operating if cycle is too long): 1 to 40,000 ms (Unit: 10 ms)
I/O refreshing
Cyclic refreshing, immediate refreshing, refreshing by IORF(097).
I/O memory holding when
changing operating modes
Possible (Depends on ON/OFF status of IOM Hold Bit in Auxiliary Area.)
Load OFF
All outputs on Output Modules can be turned OFF.
Input time constant setting
Time constants can be set for inputs from CS1 Basic I/O Modules. The time constant can be
increased to reduce influence of noise and chattering or it can be decreased to detect shorter pulses
on inputs. (CS1 Basic I/O Modules only)
Mode setting at power-up
Possible
Memoryy Card functions
Automatic reading programs from Memory Card (autoboot).
Memory Card Storage Data
User program: Program file format (binary)
PC System Setup: Data file format (binary)
I/O Memory: Data file format (binary), text format, CSV format
Memory Card Read/Write
User program instructions, Peripheral Devices (such as Programming Console), Host Link computer.
Filing
Memory Card data and EM (Extended Data Memory) Area can be handled as files.
Debugging
Force-set/reset, differential monitoring, data tracing (scheduled, each cycle, or when instruction is
executed), instruction error tracing.
Online editing
One or more program blocks in user programs can be overwritten when CPU is in PROGRAM or
MONITOR mode. This function is not available for block programming areas.
Program protection
Overwrite protection: Set using DIP switch.
Copy protection: Password set using Peripheral Device.
Error check
User-defined errors (i.e., user can define fatal errors and non-fatal errors)
The FPD(269) instruction can be used to check execution time and logic of each programming block.
Error log
Up to 20 errors are stored in error log. Information includes error code, error details, and time error
occurred.
Serial communications
Built-in peripheral port: Peripheral Device (including Programming Console), Host Links, NT Links
Built-in RS-232C port: Peripheral Device (excluding Programming Console), Host Links, no-protocol
communications, NT Links
Communications Board (sold separately): Protocol macros, Host Links, NT Links
Clock
Provided on all models.
Note: Used to store time when power is turned ON and when errors occur.
Power OFF detection time
10 to 25 ms (not fixed)
Power OFF detection delay time
0 to 10 ms (user-defined, default: 0 ms)
Memory protection
Held Areas: Holding bits, contents of Data Memory and Extended Data Memory, and status of
counter Completion Flags and present values.
Note: If IOM Hold Bit in Auxiliary Area is turned ON, and PC Setup is set to maintain IOM Hold Bit
status when power to PLC is turned ON, contents of CIO Area, Work Area, part of Auxiliary
Area, timer Completion Flag and PVs, Index Registers, and Data Registers will be saved.
(This table continues on the next page.)
Programmable Controller
CS1
C--29
CPU Overview
CS1 CPU Specifications
Function Specifications (continued)
Item
Specification
Sending commands to a Host
Link computer
FINS commands can be sent to a computer connected via Host Link System by executing Network
Communications Instructions from PLC.
Remote programming and
monitoring
Host Link communications can be used for remote programming and remote monitoring through a
Controller Link System or Ethernet network.
Three-level communications
Host Link communications can be used for remote programming and remote monitoring from
devices on networks up to two levels away (Controller Link Network, Ethernet Network, or other
network).
Storing comments in CPU
I/O comments can be stored in CPU in Memory Cards or EM file memory.
Program check
Program checks are performed at beginning of operation for items such as no END instruction and
instruction errors. A Peripheral Device (excluding Programming Console) can also be used to check
programs.
Control output signals
RUN output: The contacts will turn ON (close) while CPU is operating. These terminals are provided
only on C200HW-PA204R and C200HW-PA209R Power Supply Modules.
Battery life
5 years at 25°C (Depending on the ambient operating temperature and communications conditions,
1.1 years min. Battery Set: CS1W-BAT01)
Note: Use a replacement battery that is no more than 2 years old from the date of manufacture.
Self-diagnostics
CPU errors (watchdog timer), I/O verification errors, I/O bus errors, memory errors, and battery
errors.
Other functions
Storage of number of times power has been interrupted, the times of the interrupts, and system
operation time (in Auxiliary Area).
C--30
Programmable Controller
CS1
CPU Overview
CS1D Duplex CPU Specifications
J System Configuration and Basic Functions
Item
Specification
Functional equivalence of
existing CS1-H CPUs
The following CPUs are equivalent in terms of basic functions (I/O points, program capacity, DM
capacity, and instruction execution speed).
CS1D-CPU67H: Equivalent to CS1H-CPU67H.
CS1D-CPU65H: Equivalent to CS1H-CPU65H.
Mountable Modules
CS1-Series Basic I/O Modules, CS1-Series Special I/O Modules, CS1-Series CPU Bus Modules
C200H Basic I/O Modules C200H Group-2 Multipoint I/O Modules, and C200H Special I/O Modules
cannot be mounted.
Mountable Inner Boards
Non-duplex Inner Boards cannot be used in either Duplex Mode or Simplex Mode.
System configuration
These system configurations are possible:
Duplex System
In a Duplex System, two CS1D CPUs, two (or one) CS1D Power Supply Units, and one Duplex Unit are
mounted to a CS1D Backplane.
Simplex System
In a Simplex System, one CS1D CPU, two (or one) CS1D Power Supply Units, and one Duplex Unit are
mounted to a CS1D Backplane.
Duplex Mode
A Duplex System can be operated in either of the following two modes:
Duplex Mode
The system operates with CS1D CPUs and CS1D Power Supply Units in duplex status.
Simplex Mode
The system operates with just a single CS1D CPU. In a Simplex System, only the Simplex Mode is
possible.
Duplex CS1D CPUs
(Supported only in Duplex
Mode in a Duplex System)
Operation of the two
CS1D CPUs in
Duplex
Operation of the two CS1D CPU in Duplex Mode Hot standby method:
One of the two CS1D CPUs actually controls operations, and the other is on
standby as a backup. The two CS1D CPUs have the same I/O memory, and
parameters (PLC Setup, I/O tables, etc.), and both run the same user’s program.
Their operations differ in the following points:
The active CPU executes I/O refreshing and all event servicing.
The standby CPU handles file accessing (read only) and FINS command
execution event servicing (read only).
Operation switching
errors
Power interruptions
(CPU operation setting
switch: NO USE), CPU
errors, memory errors,
program errors, cycle
time overrun errors,
FALS executions
If any of the errors listed on the left occur in the active
CPU, stopping operation, the standby CPU
automatically switches to active status and takes over
control. At the same time, the mode is switched to
Simplex Mode. The CPU where the error occurred
can be replaced without stopping system operation.
Duplex errors
Duplex bus errors
Duplex verification
errors
If either of the errors listed on the left occurs in Duplex
Mode, the active CPU remains the same and
operation is switched to Simplex Mode.
Automatic recovery
to duplex operation
After operation has been switched from Duplex Mode to Simplex Mode as a
result of any of the operation switching errors listed above, operation is
automatically returned to Duplex Mode when it is determined that the cause of
the error has been cleared. Automatic recovery to duplex operation must first be
enabled in the PLC Setup. (The recovery can be repeated up to ten times.)
Hardware conditions
for the two CS1D
CPUs in Duplex
Mode
Identical models must be used for the two CS1D CPUs.
Software conditions
for the two CS1D
CPUs in Duplex
Mode
The same user program areas must be used.The same parameter areas (PLC
Setup, etc.) must be used.
CS1D CPU online
replacement
The CS1D CPU where the error occurred can be replaced online by turning OFF
the power to only that Unit (i.e., setting the CPU operation switch to NO USE).
(This table continues on the next page.)
Programmable Controller
CS1
C--31
CPU Overview
CS1D Duplex CPU Specifications
System Configuration and Basic Functions (continued)
Item
Specification
Duplex CS1D Power Supply
Units
Operation with two
CS1D Power Supply
Units mounted
Power is supplied to the Backplane simultaneously by two CS1D Power Supply
Units. (The load for each CS1D Power Supply Unit is approximately one half.)
This function is supported in either a Duplex System (in either Duplex or Simplex
Mode) or in a Simplex System.
Operation when one
CS1D Power Supply
Unit breaks down
If one CS1D Power Supply Unit breaks down (i.e., if the power supply voltage
drops), operation is continued using only the other one.
Duplex Communications
When two Optical-ring Controller Link Units for duplex communications (H-PCF cable: CS1W-CLK12-V1;
GI cable: CS1W-CLK52-V1) are mounted using the same node address and unit number, and a special
cable is used to connect them, one of the Modules will continue communications even if the other one
breaks down.
Online Module replacement
Using the Programming Console, it is possible to mount or remove CS1-Series Basic I/O Modules,
CS1-Series Special I/O Modules, and CS1-Series CPU Bus Units while the power is ON and the CPU is
operating in any mode (PROGRAM, MONITOR, or RUN).This function is supported in either a Duplex
System (in either Duplex or Simplex Mode) or in a Simplex System.
J Specifications with Application Restrictions
Item
Specification
Programming Device
operating restrictions
CX-Programmer
PLC model: Select: “CS1H-H.” Cable connection: Connect to peripheral port or
RS-232C port of active CPU. If a CX-Programmer is connected to the standby
CPU, write processing from the CX-Programmer cannot be executed.
Programming
Console
Cable connection: Connect to peripheral port of active CPU. If a Programming
Console is connected to the standby CPU write processing from the
Programming Console cannot be executed.
Applications constantly
connected to RS-232C port
When a constant monitoring system, such as an Operator Interface or personal computer application, is
connected to the CPUs RS-232C port, an RS-232C/RS-422 Adapter can be used to connect to both the
active and standby CS1D CPUs. Set the standby CPUs RS-232C port setting in the PLC Setup so that it
cannot be used independently.‘
Restrictions on Memory
Card functions
When writing to a Memory Card, the same data is written to not only the Memory Card mounted in the
active CPU, but also to the one mounted in the standby CPU.
Note: 1. In the PLC Setup, duplex operation must be enabled for Memory Cards.
2. No processing is executed during duplex initialization to match the data on the Memory Cards
mounted in the active and standby CPUs even if the data is not the same. Therefore, before
enabling duplex operation for Memory Cards, make sure that the contents are the same for
both of the Memory Cards.
3. When EM File Memory is set for duplex operation, processing is executed to match the contents of EM File Memory in both CPUs. It is not necessary to enable duplex operation for
Memory Cards in the PLC Setup.
Restrictions on types of
interrupts
The CS1D CPUs do not support any interrupt functions.
Restrictions on I/O refresh
methods
No restrictions.
Power OFF interrupt tasks, scheduled interrupt tasks, I/O interrupt tasks, and external interrupt tasks
cannot be used in either a Duplex or Simplex System. Interrupt control instructions (MSKS, MSKR, and
CLI) are executed as NOP.
Cyclic refreshing
Refreshing by I/O refresh instruction (IORF(097))
Refreshing by CPU Bus Unit immediate refresh instruction (DLINK(226))
Cannot be used
(disabled).
Immediate refresh option “!”
Immediate refresh option “!” will not be used, even if it was specified
Restrictions of CPU
processing modes
Only Normal Mode can be used.
Restrictions on background
execution
Background execution of text string instructions, table data instructions, and data shift instructions
cannot be used.
Parallel Processing Mode and Peripheral Servicing Priority Mode cannot be used
(This table continues on the next page.)
C--32
Programmable Controller
CS1
CPU Overview
CS1D Duplex CPU Specifications
Specifications with Application Restrictions (continued)
Item
Specification
Accuracy of timer
instructions
± (10 ms + cycle time)
When operation is switched from duplex to simplex during timer instruction execution, the deviation in
the first cycle after switching may exceed the normal time, as shown below.
TIM, TIMX, TIMH(015), TIMHX(551), TTIM(087), TTIMX(555), TIML(542), TIMLX(553), MTIM(543),
MTIMX(554), TIMW(813), TIMWX(816), TMHW(815), TMHWX(817): (10 ms + cycle time) ± 10 ms or
less
TMHH(540), TMHHX(552):
(10 ms + cycle time) ± 20 ms or less
PV refresh during
timer-system instruction
jump or while block program
is stopped (Different from
CS1-H.)
TIM, TIMX, TIMH(015), TIMHX(551), TMHH(540), TMHHX(552), TTIM(087), TTIMX(555):
Clock function
Synchronized with active CPU.
The timer PV is not refreshed when the timer instruction is jumped for JMP, CJMP, or CJPN--JME. The
PV will be refreshed for the entire period it was jumped the next time it is executed (i.e., the next time it is
not jumped). (With CS1-H CPUs, the PV for these timers were refreshed even when jumped.)
J Common Specifications other than Duplex Specifications
Item
Specification
Control method
Stored program
I/O control method
Cyclic scan and immediate processing (by IORF only) are both supported.
Programming
Ladder diagram
CPU processing mode
Normal Mode only. Parallel Processing Mode and Peripheral Servicing Priority Mode cannot be used.
Instruction length
1 to 7 steps per instruction
Ladder instructions
Approx. 400 (3--digit function codes)
Instruction execution times
Basic instructions
0.02 µs min.
Special instructions
0.06 µs min.
Overhead processing time
1.9 ms
Number of Expansion
Racks
7 max. (CS1D Expansion Racks)
Number of Tasks
288 (cyclic tasks: 32; extra cyclic tasks: 256)
(C200H Expansion I/O Racks and SYSMAC BUS Remote I/O Slave Racks cannot be connected.)
The extra cyclic tasks can be executed each cycle, just like the cyclic tasks, making a total of 288 tasks
that can be executed each cycle.
Cyclic tasks are executed each cycle and are controlled with TKON(820) and TKOF(821) instructions.
Starting subroutines from
multiple starts
Supported (by global subroutines).
(This table continues on the next page.)
Programmable Controller
CS1
C--33
CPU Overview
CS1D Duplex CPU Specifications
Common Specifications other than Duplex Specifications (continued)
CIO (Core I/O) Area
I/O Area
5,120: CIO 000000 to CIO 031915 (320 words from CIO 0000 to CIO 0319)
The setting of the first word can be changed from the default (CIO 0000) so that
CIO 0000 to CIO 0999 can be used.
I/O bits are allocated to Basic I/O Modules (CS1--Series Basic I/O Modules).
Data Link Area
3,200 (200 words): CIO 10000 to CIO 119915 (words CIO 1000 to CIO 1199)
Link bits are used for data links and are allocated to Modules in Controller Link
Systems
CPU Bus Unit Area
6,400 (400 words): CIO 150000 to CIO 189915 (words CIO 1500 to CIO 1899)
CPU Bus Unit bits can be used to store the operating status of CPU Bus Units.
(25 words per Unit, 16 Units max.)
Special I/O Module
Area
15,360 (960 words): CIO 200000 to CIO 295915 (words CIO 2000 to CIO 2959)
CS1-Series
DeviceNet Area
9,600 (600 words): CIO 320000 to CIO 379915 (words CIO 3200 to CIO 3799)
CS1-Series DeviceNet Area bits are allocated to Slaves according to
CS1W-DRM21
Special I/O Module bits can be allocated to CS1-Series Special I/O Modules.
(10 words per Unit, 96 Units max.)
DeviceNet Module remote I/O communications.
Fixed Allocations 1: Output 3200 to 3263
Input: 3300 to 3363
Fixed Allocations 2: Output 3400 to 3463
Input: 3500 to 3563
Fixed Allocations 3:Output 3600 to 3663
Input: 3700 to 3763
The following words are allocated in the Master even when fixed allocations are
used for the remote I/O communications Slave functions of a CS1-Series
DeviceNet Module (CS1W-DRM21).
Fixed Allocations 1: To Slave: Output 3370
To Master: Input: 3270
Fixed Allocations 2: To Slave:Output 3570
To Master: input: 3400
Fixed Allocations 3: To Slave:Output 3770
To Master: input: 3670
(Core I/O) Area, Work
Areas
Internal I/O Area
4,800 (300 words): CIO 120000 to CIO 149915 (words CIO 1200 to CIO 1499)
37,504 (2,344 words): CIO 380000 to CIO 614315 (words CIO 3800 to CIO
6143)
These bits in the CIO Area are used as work bits in programming to control
program execution. They cannot be used for external I/O.
Work Area
8,192 bits (512 words): W00000 to W51115 (W000 to W511)
These bits are used to control the programs only. (I/O from external I/O is not
possible.)
When using work bits in programming, use the bits in the Work Area first, before
using bits from other areas.
Holding Area
8,192 bits (512 words): H00000 to H51115 (H000 to H511)
Holding bits are used to control the execution of the program, and maintain their ON/OFF status when
the PLC is turned OFF or the operating mode is changed.
Auxiliary Area
Read only: 7,168 bits (448 words): A00000 to A44715 (words A000 to A447)
Read/write: 8,192 bits (512 words): A44800 to A95915 (words A448 to A959)
Auxiliary bits are allocated for specific functions.
Temporary Relay (TR) Area
6 bits (TR0 to TR15)
Temporary bits are used to temporarily store the ON/OFF execution conditions at program branches.
Timer Area
4,096: T0000 to T4095 (used for timers only)
Counter Area
4,096: C0000 to C4095 (used for counters only)
(This table continues on the next page.)
C--34
Programmable Controller
CS1
CPU Overview
CS1D Duplex CPU Specifications
Common Specifications other than Duplex Specifications (continued)
Data Memory (DM) Area
32K words: D00000 to D32767
Used as a general--purpose data area for reading and writing data in word units (16 bits). Words in the
DM Area maintain their status when the PLC is turned OFF or the operating mode is changed.
Special I/O Module DM Area: D20000 to D29599 (100 words x 96 Units)
Used to set parameters for Special I/O Modules.
CPU Bus Unit DM Area: D30000 to D31599 (100 words x 16 Units)
Used to set parameters for CPU Bus Units.
Inner Board DM Area: D32000 to D32099
Used to set parameters for Inner Boards.
Extended Data Memory
(EM) Area
32K words per bank, 13 banks max.: E0_00000 to EC_32767 max. (Not available on some CPUs.)
Used as a general-purpose data area for reading and writing data in word units (16 bits).
Words in the EM Area maintain their status when the PLC is turned OFF or the operating mode is
changed.
The EM Area is divided into banks, and the addresses can be set by either of the following methods.
Changing the current bank using the EMBC(281) instruction and setting addresses for the current
bank.Setting bank numbers and addresses directly.
EM data can be stored in files by specifying the number of the first bank.
Index Registers
IR0 to IR15
Store PLC memory addresses for indirect addressing. One register is 32 bits (2 words).Index registers
can be set to be shared by all tasks or to be used independently by each task.
Data Registers
DR0 to DR15
Used to offset the PLC memory addresses in Index Registers when addressing words indirectly.
Data registers can be set to be shared by all tasks or to be used independently by each task
Task Flags
32 (TK0000 to TK0031)
Task Flags are read--only flags that are ON when the corresponding cyclic task is executable and OFF
when the corresponding task is not executable or in standby status.
Trace Memory
4,000 words (trace data: 31 bits, 6 words)
File Memory
Memory Cards: Compact flash memory cards can be used (MS--DOS format).
EM file memory: The EM Area can be converted to file memory (MS--DOS format)
Programmable Controller
CS1
C--35
CPU Overview
CS1D Duplex CPU Specifications
J Functions
Constant cycle time
1 to 32,000 ms (Unit: 1 ms)
Cycle time monitoring
Possible (Module stops operating if the cycle is too long): 10 to 40,000 ms (Unit: 10 ms)
Timing of special refreshing
for CPU Bus Units
Data links for Controller Link Modules and SYSMAC LINK Modules, remote I/O for DeviceNet Modules,
and other special refreshing for CPU Bus Units is performed at the I/O refresh period and when the CPU
Bus Unit I/O REFRESH (DLNK(226)) instruction is executed.
I/O memory holding when
changing operating modes
Depends on the ON/OFF status of the IOM Hold Bit in the Auxiliary Area.
Load OFF
All outputs on Output Modules can be turned OFF when the CPU is operating in RUN, MONITOR, or
PROGRAM mode.
Input response time setting
Time constants can be set for inputs from Basic I/O Modules. The time constant can be increased to
reduce the influence of noise and chattering or it can be decreased to detect shorter pulses on the
inputs.
Startup mode setting
Supported.
The CPU will start in RUN mode if the PLC Setup is set to use the Programming Console mode (default)
and a Programming Console is not connected.
Flash memory
The user program and Parameter Area data (e.g., PLC Setup) are always backed up automatically in
flash memory.
Memory Card functions
(Accessed for Memory Card
mounted in active CPU Bus
U it only.)
Unit
l )
Automatically reading programs (autoboot) from
the Memory Card when the power is turned
ON.
Supported.
Program replacement during PLC operation
Supported.
Format in which data is stored in Memory Card
User program:Program file format
PLC Setup and other parameters: Data file format
I/O memory: Data file format (binary format), text format,
or CSV format (except pre-version-1 CS1 CPUs)
Functions for which Memory Card read/write is
supported
User program instructions, Programming Devices
(including Programming Consoles), Host Link
computers, AR Area control bits, simple backup
operation
Filing
Memory Card data and the EM (Extended Data Memory) Area can be handled as files.
Debugging
Control set/reset, differential monitoring, data tracing (scheduled, each cycle, or when instruction is
executed), storing location generating error when a program error occurs
Online editing
User programs can be overwritten in program--block units when the CPU is in MONITOR or PROGRAM
mode. This function is not available for block programming areas. With the CX--Programmer, more than
one program block can be edited at the same time.
Program protection
Overwrite protection: Set using DIP switch.
Copy protection: Password set using Programming Device.
Error check
User--defined errors (i.e., user can define fatal errors and non--fatal errors)
The FPD(269) instruction can be used to check the execution time and logic of each programming block.
FAL and FALS instructions can be used with the CS1-H CPUs to simulate errors.
Error log
Up to 20 errors are stored in the error log. Information includes the error code, error details, and the time
the error occurred.
The CPU can be set so that user--defined FAL errors are not stored in the error log.
Serial communications
Built-in peripheral port: Programming Device (including Programming Console) connections, Host Links,
NT Links
Built-in RS-232C port: Programming Device (excluding Programming Console) connections, Host Links,
no-protocol communications, NT Links
Serial Communications Board (sold separately): Protocol macros, Host Links, NT Links
Provided on all models. Accuracy: ± 30 s/mo. at 25°C
Clock
Note: a.) The accuracy varies with the temperature;
b.) Used to store the time when power is turned ON and when errors occur.
Power OFF detection time
10 to 25 ms (AC power supply)
2 to 5 ms (DC power supply)
Power OFF detection delay
time
0 to 10 ms (user-defined, default: 0 ms)
(This table continues on the next page.)
C--36
Programmable Controller
CS1
CPU Overview
CS1D Duplex CPU Specifications
Functions (continued)
Memory protection
Held Areas: Holding bits, contents of Data Memory and Extended Data Memory, and status of the
counter Completion Flags and present values.
Note: If the IOM Hold Bit in the Auxiliary Area is turned ON, and the PLC Setup is set to maintain the
IOM Hold Bit status when power to the PLC is turned ON, the contents of the CIO Area, the Work
Area, part of the Auxiliary Area, timer Completion Flags and PVs, Index Registers, and the Data
Registers will be saved.
Sending commands to a
Host Link computer
FINS commands can be sent to a computer connected via the Host Link System by executing Network
Communications Instructions from the PLC.
Program check
Program checks are performed at the beginning of operation for items such as no END instruction and
instruction errors.
CX-Programmer can also be used to check programs.
Control output signals
RUN output: The internal contacts will turn ON (close) while the CPU is operating.These terminals are
provided only on CS1D--PA207R Power Supply Units.
Battery service life
Battery Set: CS1W--BAT01
Self-diagnostics
CPU errors (watchdog timer), I/O verification errors, I/O bus errors, memory errors, and battery errors.
Other functions
Storage of number of times power has been interrupted. (Stored in A514.)
Programmable Controller
CS1
C--37