DRA3R Series • Three Phase Motor Reversing Contactor • Ratings of 2.4 & 4.2 Amps • Load voltage range of 48-510VAC, 3-Phase • Fits standard 35mm DIN-RAIL • LED input status indicator, Forward (green), Reverse (yellow) • AC or DC control • cUL Recognized, IEC Rated, CE & RoHS Compliant, Horsepower Rated • Built in Overvoltage Protection PRODUCT SELECTION Description 4-6 VDC Control 18-28 VDC Control 36-60 VAC Control 90-140 VAC Control 200-265 VAC Control 2.4A 4.2A DRA3R48D2 DRA3R48E2 DRA3R48C2 DRA3R48B2 DRA3R48A2 DRA3R48D4 DRA3R48E4 DRA3R48C4 DRA3R48B4 DRA3R48A4 2.4 A 4.2 A 48-510 1600 2.4 2.1 0.15 3.0 500 2.6 285/300 410/375 1/2 / 0.37 1.0 / 0.75 1.0 / 0.75 0.5 24/10 24/10 12.0 in lb (1.36 Nm) 48-510 1600 4.2/3.5 3.4 0.15 3.0 500 2.6 285/300 410/375 1.0 / 0.75 1.5 / 1.1 2.0 / 1.5 0.5 24/10 24/10 12.0 in lb (1.36 Nm) AVAILABLE OPTIONS OUTPUT SPECIFICATIONS AC Output (1) Description Operating Voltage (47-63Hz) [Vrms] Transient Overvoltage [Vpk] Maximum Resistive Load Current (UL508,AC51) [Arms] (2) Maximum Motor Load Current (UL508,AC53) [Arms] (2) Minimum Load Current [Arms] Maximum Off-State Leakage Current @ Rated Voltage [mArms] Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (3) Maximum On-State Voltage Drop @ Rated Current [Vpk] Maximum Surge Current (50/60 Hz, 1 cycle) [Apk] Maximum I²t for Fusing (50/60 HZ, 1/2 cycle) [A² sec] HP/IEC 60947 Rating @ 240V, 40°C [HP/KW] HP/IEC 60947 Rating @ 380V, 40°C [HP/KW] HP/IEC 60947 Rating @ 480V, 40°C [HP/KW] Minimum Power Factor (with Maximum Load) Min/Max stranded/solid wire [AWG] Min/Max stranded/solid wire [AWG] Load Terminal Screw Torque Range: INPUT SPECIFICATIONS (1) Description Control Voltage Range Minimum Turn-On Voltage Minimum Turn-Off Voltage Minimum Input Current [mA] Maximum Input Current [mA] Maximum Turn-On Time [msec] Nominal Input Impedance [ohms] Maximum Turn-Off Time [msec] Min/Max stranded/solid wire [AWG] Min/Max stranded/solid wire [IEC mm²] Control Terminal Screw Torque Range: DRA3R48Dx DRA3R48Ex GENERAL SPECIFICATIONS (1) Description Maximum Capacitance, Input/Output Dielectric Strength, Input/Output (50/60Hz) Minimum Insulation Resistance (@ 500 V DC) Maximum Capacitance, Input/Output Ambient Operating Temperature Range Ambient Storage Temperature Range Weight (typical) Housing Material (bottom cover) Housing Material (end pieces) Parameters 20 pF 4000Vrms 109 Ohms 20 pF -20ºC to 60ºC -30ºC to 85ºC 6.5 oz. (185g) PVC Class V0 (UL94) Polyamide Class V0 (UL94) GENERAL NOTES 1) All parameters at 25°C unless otherwise specified. 2) Mounted in the Vertical position 3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 MECHANICAL SPECIFICATIONS DRA3R48Cx DRA3R48Bx DRA3R48Ax 4-6 VDC 18-28 VDC 36-60 VAC 90-140 VAC 200-265 VAC 4 VDC 18 VDC 36 VAC 90 VAC 200 VAC 2 VDC 4 VDC 10 VAC 20 VAC 100 VAC 15 15 6 5 5.5 30 18 10 8 7.7 120 120 130 130 130 Current Regulated Current Regulated 4.8K 16.4K 36K 10 10 20 20 20 24/12 24/12 24/12 24/12 24/12 0.5-2.5 0.5-2.5 0.5-2.5 0.5-2.5 0.5-2.5 4.3 in lb (0.485 Nm) 4.3 in lb (0.485 Nm) 4.3 in lb (0.485 Nm) 4.3 in lb (0.485 Nm) 4.3 in lb (0.485 Nm) WIRING DIAGRAM THERMAL DERATE INFORMATION AGENCY APPROVALS Designed in accordance with the requirements of IEC 62314 Rev 111011