Systemsensor B501B-FTXA Intelligent photoelectric smoke detector Datasheet

Filtrex
Intelligent Photoelectric
Smoke Detector
™
Models
FTX-P1
FTX-P1A
Base
B501B-FTX
B501B-FTXA
Accessories
RF-FTX
RA400Z
M02-04-01
M02-09-00
Product Overview
Intelligent communications
High density filter removes particulate
down to 32 microns
Air delivery system is separately
powered and fully supervised
System Sensor Filtrex Smoke Detector provides early warning smoke detection in
difficult environments where traditional smoke detectors are not practical. Filtrex
provides protection in dirty, dusty environments that tend to cause
false alarms with standard smoke detectors.
Operation:
Resistant to water spray in applications
where occasional hose-down cleaning is
performed
Using a small air intake fan and a high density replaceable filter, air and smoke
are drawn into a photoelectric sensing chamber while airborne particulate and
water spray are removed. When the filter becomes too clogged to draw adequate air into the sensing chamber, power is cut from the detector, causing a
trouble signal at the fire alarm control panel. When the filter is replaced,
power-up is automatic.
Optional remote LED accessory
Applications:
Filter is easily field replaceable
Rotary decade address switches
Compatible with 200 and 500 Series
products’ protocol
No modification required to panels
compatible with System Sensor intelligent photoelectric smoke detectors
Animal research facilities
Institutional laundry facilities
Amusement parks
Zoos
Performance theatres
Loading docks
Paper mills
Textile mills
Specifications
Size
3.5″ (8.9 cm) H × 6.1″ (15.5 cm) diam,
in B501B-FTX base
Weight
7.3 oz. (207 grams)
External/Auxiliar y Power Supply Voltage Range
15–30 VDC (filtered)
Air Intake Fan
On 5 seconds ever y 30 seconds
External/Auxiliar y Power Supply Maximum Current
123 mA
Filter
Air flow checked ever y 4 hours
External/Auxiliar y Power Supply Avg. Current
27 mA
Signaling Line Circuit Supply Range
15–32 VDC
Temperature Range
32º to 122°F (0° to 50° C)
Detector Current (max. avg.)
250 µA @ 24 VDC (without communication)
360 µA @ 24 VDC (one communication ever y 5
seconds with LED enabled)
Relative Humidity
10% to 93% noncondensing
Filtrex Wiring Diagram
+
CONTROL PANEL
–
2(–)
1(+)
3(RA
) 4(S
)
3(R
A) 4
(S)
X+
AU
X
AU
X
AU
X+
AU
AUX.
POWER
SUPPLY
2(–)
–
–
1(+)
+
–
Ordering Information
Model
Description
FTX-P1
Photoelectric smoke detector
FTX-P1A
Photoelectric smoke detector, (Canadian)
B501B-FTX
Flanged adapter base, 6.1″ (15.5 cm)
B501B-FTXA
Flanged adapter base, 6.1″ (15.5 cm), (Canadian)
RF-FTX
Replacement filter cover assembly (6 pack)
RA400Z
Remote LED annunciator, fits U.S. single gang electrical box
M02-04-01
Test magnet
M02-09-00
Test magnet with telescoping handle
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800/SENSOR2
Fx: 630/377-6495
Documents-on-Demand
800/736-7672 x3
www.systemsensor.com
System Sensor Canada
Ph: 905.812.0767
Fx: 905.812.0771
System Sensor in China
Ph: 86.29.524.6253
Fx: 86.29.524.6259
System Sensor – Far East
Ph: 85.22.191.9003
Fx: 85.22.736.6580
System Sensor Europe
Ph: 44.1403.276500
Fx: 44.1403.276501
System Sensor in Singapore
Ph: 65.273.2230
Fx: 65.273.2610
System Sensor – Australia
Ph: 613.54.281.142
Fx: 613.54.281.172
© 1999 System Sensor. The company reserves the right to change product specifications without notice.
System Sensor – India
Ph: 91.124.637.1770 x.2700
Fx: 91.124.637.3118
A05-985-01•7/99(10K)•#522