DIN Rail Mount Datasheet DRC Series • 7.6 Amp AC Semiconductor Motor Controller • Load voltage range up to 600 VAC • Fits standard 35mm DIN Rail • LED input status indicator • AC or DC control • Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output • C-UL-US Listed, CCC Certified, IEC Rated, CE & RoHS Compliant, Horsepower Rated • Built-in Overvoltage Protection • Ultra-efficient thermal management design (Patented) Start / Stop Reversing Solicon DRC3 Series are Solid State Contactors intended for frequently switching on and off three phase loads up to 5 HP, 600 VAC 7.6 Amps. They are available in both contactor versions DRC3P and reversing contactor versions DRC3R. instantaneous change of direction is commanded, then it will delay the direction change by 100msec in order to prevent simultaneous forward and reverse operations. All the models of Solicon DRC3 Series combine the benefits and advantages of a solid state contactor with the functionality and simplicity of use of an electromechanical contactor thanks to the proprietary thermal management technology (Patented) and complete electrical insulation (no grounding required); the embedded auxiliary contacts, normally open and/or normally closed, are intended to be used at 18-280VAC. Five different control voltages are available in order to cover most applications. All models include overvoltage protection. The Solicon Contactor DRC3P is available in either instantaneous turn-on (for Motor Control) or zero voltage turn-on (for Resistive Loads). It is available in either 2 or 3 controlled leg versions. The 2 legs control version is particularly suitable for motor control circuits where the neutral conductor is not utilized. The Solicon Reversing Contactor DRC3R includes an interlock control that allows only off, forward and reverse operation in a safe mode while providing high space saving; it switches instantaneously upon application of the control voltage unless an PRODUCT SELECTION Control Voltage Without Auxiliary Contact 230 VAC 120 VAC 48 VAC/DC 24 VAC/DC, 24 VAC 24 VDC 1 NO+NC Auxiliary Conctat DRC3P48A400, DRC3R48A400 DRC3P48B400, DRC3R48B400 DRC3P48C400, DRC3R48C400 DRC3P48D400, DRC3R48D400 DRC3R48E400 AVAILABLE OPTIONS Operating Voltage 40: 400 VAC (3R function only) 48: 480 VAC 60: 600 VAC (3P function only) Series DRC 3P 48 Function 3P: Contactor 3R: Reversing Contactor D Load Current per Phase 4: 7.6 Amp FLA (x2 Controlled Legs & 3R function); 4.8 Amp FLA (x3 Controlled Legs only) 4 Control Voltage A: 208-265 VAC B: 90-140 VAC C: 36-55 VAC/DC D: 18-30 VAC/DC (3P function only) 18-30 VAC (3R function only) Required for valid part number 2 NO Auxiliary Contact DRC3P48A411 DRC3P48B411 DRC3P48C411 DRC3P48D411 E: 18-30 VDC For options only and not required for valid part number (3R function only) 00 DRC3P48A420, DRC3R48A420 DRC3P48B420, DRC3R48B420 DRC3P48C420, DRC3R48C420 DRC3P48D420, DRC3R48D420 DRC3R48E420 Switching Mode (3P function only) Blank: Zero Voltage Turn-On R: Instantaneous Turn-On R 2 Controlled Legs Auxiliary Contacts, (3P function only) N.O. - N.C. Blank: 3 Controlled Legs 00: Not included 2: 2 Controlled Legs 11: 1 Solid State Auxiliary Contact, Normally Open; 1 Solid State Auxiliary Contact, Normally Closed (3P function only) 20: 2 Solid State Auxiliary Contacts, Normally Open FDE-07-01 REV. A Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount Datasheet OUTPUT SPECIFICATIONS (1) DRC3P48x4x DRC3P48x4x2 DRC3P60x4x DRC3P60x4x2 DRC3R40x4x DRC3R48x4x Operating Voltage (47-63Hz) [Vrms] 48-530 Transient Overvoltage [Vpk] (2)(3) 1200 Maximum Off-State Leakage Current @ Rated Voltage [mArms] 3.0 Maximum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] 500 Load Current, General Use UL508 /AC51 @40°C [Arms] (4) 5 Load Current, Motor Controller UL508 /AC-53a @480VAC [Arms] (4) 4.8 Minimum Load Current [Arms] 0.15 Maximum Surge Current [Apk] 1 Cycle 60Hz 750 Maximum Surge Current [Apk] 1 Cycle 50Hz 716 2330 Maximum I2t for Fusing (8.33msec)[A2sec] 2560 Maximum I2t for Fusing (10msec)[A2sec] Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.35 per channel Minimum Power Factor (with Maximum Load) 0.5 Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 240 VAC 1/.75 Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 400 VAC 2/1.5 Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 480 VAC 3/2.2 Motor Ratings @ 600 VAC [HP/kW] - Description 48-530 1200 3.0 500 7.6 7.6 0.15 750 716 2330 2560 1.35 per channel 0.5 2/1.5 3/2.2 5/3.7 - 48-600 1200 1.0 500 5 4.8 0.15 750 716 2330 2560 1.35 per channel 0.7 1/.75 2/1.5 3/2.2 3/2.2 48-600 1200 1.0 500 7.6 7.6 0.15 750 716 2330 2560 1.35 per channel 0.7 2/1.5 3/2.2 5/3.7 5/3.7 48-415 1200 5.5 500 7.6 7.6 0.15 750 716 2330 2560 1.5 per channel 0.5 2/1.5 3/2.2 - 48-510 1600 5.5 500 7.6 7.6 0.15 625 597 1621 1779 1.5 per channel 0.5 2/1.5 3/2.2 5/3.7 - INPUT SPECIFICATIONS (1) Description Option A Option B Option C Option D Option E Control Voltage Range (5) Minimum Turn-On Voltage (6) Must Turn-Off Voltage Minimum Input Current (for on-state) [mA] Maximum Input Current [mA] Nominal Input Impedance [Ohms] Maximum Delay to Turn-On [msec] (7) Maximum Turn-Off Time [msec] (8) 208-265 VAC 208 VAC 40 VAC 6.1 8 33k 30 40 90-140 VAC 90 VAC 10 VAC 7.5 13 12.5k 30 40 36-55 VAC / VDC 36 VAC / VDC 4 VAC / VDC 12 20 3k 30 40 18-30 VAC / VDC 18 VAC / VDC 4 VAC / VDC 12.5 32 0.93k 20 30 18-30 VDC 18 VDC 4 VDC 12.5 32 0.93k 100 ± 30 20 SOLID STATE AUXILIARY CONTACTS (1) Description Normally Open Suffix 2x,1x Normally Closed Suffix x1 18-280 600 1 5 40 38 6.7 7.2 0.1 500 30 40 18-280 600 1 5 40 38 6.7 7.2 5 mA 500 80 40 Operating Voltage Range (47-63Hz) [Vrms] (9) Transient Overvoltage [Vpk] Maximum Load Current [Arms] Minimum Load Current [mA] Maximum Surge Current [Apk] 1 Cycle 60Hz Maximum Surge Current [Apk] 1 Cycle 50Hz Maximum I2t for Fusing (8.33msec)[A2sec] Maximum I2t for Fusing (10msec)[A2sec] Maximum Off-State Leakage Current @ Rated Voltage [mArms] Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] Maximum Delay to Turn-On [msec] (7) Maximum Turn-Off Time [msec] GENERAL SPECIFICATIONS (1) Description Dielectric Strength, Input/Output/Base (50/60Hz) (10) Minimum Insulation Resistance (@ 500 VDC) Maximum Capacitance, Input/Output Ambient Operating Temperature Range (11) Ambient Storage Temperature Range Weight (typical) Housing Material Housing Color LED Status Indicator (color) (12) Short Circuit Current Rating (13) MTBF (Mean Time Between Failures) at 40°C ambient temperature (14) MTBF (Mean Time Between Failures) at 60°C ambient temperature (14) Pollution Degree Protection Degree (15) Humidity Control and Auxiliary Contact Terminal Screw Torque Range (in-lb/Nm) Load Terminal Screw Torque Range (in-lb/Nm) Input Terminal Wire Capacity Output Terminal Wire Capacity Do not forget to visit us at: www.crydom.com Parameters 3750 Vrms 109 Ohms 20 pF -30 to 80 °C -40 to 100 °C 2 Controlled Legs (6.9 oz [197 g]) / 3 Controlled Legs (8.0 oz [228 g]) UL94 V-0 Black and Light Gray Forward (Green) / Reverse (Amber) 100kA 1,398,000 hours (159 years) 390,000 hours (44 years) 2 IP20 85% non-condensing 12 / 1.36 15 / 1.7 18-12 AWG (IEC 1-4 mm2) (stranded /solid) 18-10 AWG (IEC 1-6 mm2 ) (stranded /solid) Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount Datasheet MECHANICAL SPECIFICATIONS (1) Tolerances: ±0.02 in / 0.5 mm All dimensions are in: inches [millimeters] 3.51 [89] 2.91 [73.9] 0.23 [5.8] A3 1.23 [31.3] 3.41 [86.7] 13 A1 DRC3 2.58 [65.5] 2.29 [58.3] 23 1.68 [42.7] IND. CONT. EQ. INPUT STATUS XXXX 14 24 A2 3.76 [95.6] 1.78 [45.3] TERMINAL SCREW TYPE Top/Bottom view (Fig. 1) THERMAL DERATE INFORMATION (16) DRC3P (2 controlled legs) & DRC3R Single unit (17) Multiple units DRC3P (3 controlled legs) Single unit (17) Multiple units 8 6 7 Load Current (Amps) Load Current (Amps) 5 4 3 2 1 6 5 4 3 2 1 0 0 0 10 20 30 40 50 60 70 80 Ambient Temperature (ºC) Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. 0 10 20 30 40 50 Ambient Temperature (ºC) 60 70 80 Fig. 1 DIN Rail Mount Datasheet SWITCHING FREQUENCY/LOAD CHARACTERISTIC FOR ALL DEVICES IL : Load Operating Current IR : Rated Full Load Current [FLA] ID : Direct-On-Line Inrush Current tL : Load Operating Current Time tD : Direct-On-Line Inrush Current Time tC : Cycle Time tOn : On Time tOff : Off Time ID IR IL tD tL tOn tOff tC MAXIMUM ALLOWABLE NUMBER OF STARTS PER HOUR DEPENDING ON THE STARTING TIME tD AND THE ON PERIOD tOn (as for standard IEC 60947-4-2) FOR ALL DEVICES Without overload relay (limit given by the contactor itself) Table 2 Table 1 • High inrush current (ID/IR = 4 to 7.2) • Full load (IL/IR= 1) Table 3 • High inrush current (ID/IR = 4 to 7.2) • 60% load (IL/IR= 0.6) tOn (sec) tOn (sec) • Low inrush current (ID/IR < 4 ) • 60% load (IL/IR= 0.6) tOn (sec) 0.1 1 10 100 0.1 1 10 100 0.1 1 10 100 0.1 1 10 0.05 5000 2700 350 35 0.05 6000 3550 350 35 0.05 7450 3200 350 35 0.05 9000 3550 350 35 0.1 3200 1950 350 35 0.1 4100 3000 350 35 0.1 4050 2100 350 35 0.1 5400 3550 350 35 0.2 - 950 320 35 0.2 - 1300 350 35 0.2 - 1200 350 35 0.2 - 1700 350 35 0.4 - 500 280 35 0.4 - 700 320 35 0.4 - 650 320 35 0.4 - 850 350 35 0.8 - 290 160 35 0.8 - 400 320 35 0.8 - 350 280 35 0.8 - 560 350 35 1.6 - - 110 30 1.6 - - 125 35 1.6 - - 180 35 1.6 - - 240 35 3.2 - - 3.2 - - 3.2 - - 3.2 - - 180 35 25 90 35 tD (sec) tOn (sec) tD (sec) 75 tD (sec) Table 4 • Low inrush current (ID/IR < 4 ) • Full load (IL/IR= 1) 90 35 tD (sec) 100 With overload relay (limit given by the overload relay itself) Table 5 Table 6 • High inrush current (ID/IR = 4 to 7.2) • Full load (IL/IR= 1) Table 7 • High inrush current (ID/IR = 4 to 7.2) • 60% load (IL/IR= 0.6) tOn (sec) Table 8 • Low inrush current (ID/IR < 4 ) • Full load (IL/IR= 1) tOn (sec) • Low inrush current (ID/IR < 4 ) • 60% load (IL/IR= 0.6) tOn (sec) tOn (sec) tD (sec) 0.1 1 10 100 tD (sec) 0.1 1 10 100 tD (sec) 0.1 1 10 100 tD (sec) 0.1 1 10 100 0.05 2200 1650 330 30 0.05 2800 1800 320 35 0.05 5150 2800 260 35 0.05 5600 3200 350 35 0.1 1500 1000 280 28 0.1 1700 1300 310 32 0.1 2850 1920 250 34 0.1 3200 2700 350 35 0.2 - 550 255 26 0.2 - 650 290 30 0.2 - 1100 250 33 0.2 - 1400 350 35 0.4 - 250 150 24 0.4 - 300 200 26 0.4 - 600 200 32 0.4 - 700 350 35 0.8 - 80 60 20 0.8 - 200 90 25 0.8 - 320 200 30 0.8 - 350 280 35 1.6 - - 40 16 1.6 - - 65 25 1.6 - - 120 25 1.6 - - 170 35 3.2 - - 3.2 - - - - 3.2 - - 75 20 3.2 - - 80 25 Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount Datasheet SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES (Conforming to the IEC60947-4-2 and UL508) IEC standard 60947-4-1 make a distinction between two different types of protection, (called “coordination”), which are designated types “1” and "2". Any short-circuit that occurs is cleared safely by either type of coordination. The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit. Type "1" coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations, but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination, the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used. Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations, and in addition the SSR will be able to operate after the fault condition is repaired. Type of coordination 1 Protection by Thermal Magnetic Circuit Breaker (18) Nominal Motor Current Thermal Magnetic Circuit Breaker (Schneider Electric) Solid State Contactor 2 controlled legs Solid State Contactor 3 controlled legs Solid State Contactor Reversing 0.40-0.63 A GV2ME04 / GV2P04 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 0.63-1 A GV2ME05 / GV2P05 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1-1.6 A GV2ME06 / GV2P06 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1.6-2.5 A GV2ME07 / GV2P07 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 2.5-4 A GV2ME08 / GV2P08 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 4-6.3 A GV2ME10 / GV2P10 DRC3Pxx4x2 DRC3Pxx4x (up to 4.8A) DRC3Rxx4x 6.3-10 A GV2ME14 / GV2P14 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A) Protection by overload relays and fuses (18) Nominal Motor Current Overload Relay (Schneider Electric) Class gG fuses (example from Littlefuse) Solid State Contactor 2 controlled legs Solid State Contactor 3 controlled legs Solid State Contactor Reversing 0.40-0.63 A LRD04 CY14X51G16 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 0.63-1 A LRD05 CY14X51G16 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1-1.6 A LRD06 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1.6-2.5 A LRD07 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 2.5-4 A LRD08 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 4-6.3 A LRD10 CY14X51G40 DRC3Pxx4x2 DRC3Pxx4x(up to 4.8A) DRC3Rxx4x 6.3-10 A LRD14 CY14X51G40 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A) Type of coordination 2 Protection by overload relays and fuses (18) Nominal Motor Overload Relay Semiconductor fuses with less than 1621A2S Solid State Contactor (Schneider Electric) Littlefuse SIBA (Cylindric) Ferraz (Cylindric) 2 controlled legs Current Solid State Contactor 3 controlled legs Solid State Contactor Reversing 0.40-0.63 A LRD04 LA50QS40-4 50.058.06.40 A093909 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 0.63-1 A LRD05 LA50QS40-4 50.058.06.40 A093909 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1-1.6 A LRD06 LA50QS40-4 50.058.06.40 A093909 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x 1.6-2.5 A LRD07 LA50QS40-4 50.058.06.40 A093909 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x DRC3Rxx4x 2.5-4 A LRD08 LA50QS40-4 50.058.06.40 A093909 DRC3Pxx4x2 DRC3Pxx4x 4-6.3 A LRD10 LA50QS40-4 50.058.06.40 A093909 DRC3Pxx4x2 DRC3Pxx4x (up to 4.8A) DRC3Rxx4x 6.3-10 A LRD14 LA50QS40-4 50.058.06.40 A093909 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A) Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block. All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter. The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor) Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount Datasheet WIRING AND BLOCK DIAGRAM DRC3P CONTACTOR (19) DRC3Pxx400 DRC3Pxx411 DRC3Pxx420 48-530 VAC, 50-60 Hz 48-600 VAC, 50-60 Hz L1 L2 L3 L1 L2 L3 Short circuit and overload current protection (see page 5) L3 A1 DRC3PXXX400XX IND. CONT. EQ. CONTROL INPUT INPUT STATUS XXXX A2 T1 T2 T1 T3 T2 T3 L1 T2 /> L2 13 /> L3 21 A1 DRC3PXXX411XX IND. CONT. EQ. 14 T1 CONTROL INPUT INPUT STATUS XXXX Motor Controller / AC-53a Application T1 /> 22 A2 T2 T1 T3 T2 T3 2nd Auxiliary Contact (18 - 280 VAC) Normally Open L2 /> 1st Auxiliary Contact (18 - 280 VAC) Normally Open /> 2nd Auxiliary Contact (18 - 280 VAC) Normally Closed L1 /> 1st Auxiliary Contact (18 - 280 VAC) Normally Open /> General Use / AC-51 Application T1 T3 T2 L1 13 L2 L3 A1 L1 L2 L3 A1 T1 T2 T3 A2 T1 T2 T3 A2 DRC3Pxx400 DRC3Pxx420 (2 Normally Open) Auxiliary Contacts 13 23 14 T1 DRC3Pxx411 (1 Normally Open - 1 Normally Closed) Auxiliary Contacts 13 21 14 Do not forget to visit us at: www.crydom.com 24 Copyright © 2017 Crydom Inc. Specifications subject to change without notice. 14 22 CONTROL INPUT 24 T2 T1 Without Auxiliary Contacts A1 INPUT STATUS XXXX DRC3P L1 23 IND. CONT. EQ. M (2 controlled legs model) Main Circuit L3 DRC3PXXX420XX 3 DRC3P /> L2 T3 (3 controlled legs model) Main Circuit /> A2 T3 T2 T3 DIN Rail Mount Datasheet DRC3R REVERSING CONTACTOR (20) DRC3Rxx400 DRC3Rxx420 48-415 VAC, 50 - 60 Hz 48-510 VAC, 50 - 60 Hz L1 L2 L3 L1 L2 L3 Short circuit and overload current protection (see page 5) L1 /> L2 L3 A3 CONTROL INPUT (Reverse) /> A1 CONTROL INPUT (Forward) DRC3RXXX400XX IND. CONT. EQ. INPUT STATUS XXXX A2 T1 T2 T1 CONTROL INPUT (Common) T3 T2 2nd Auxiliary Contact (18 - 280 VAC) Normally Open /> 1st Auxiliary Contact (18 - 280 VAC) Normally Open /> L1 CONTROL INPUT (Reverse) T1 T2 /> L2 A3 L3 13 23 A1 CONTROL INPUT (Forward) DRC3RXXX420XX IND. CONT. EQ. INPUT STATUS XXXX 14 T1 Motor Controller / AC-53a Application T3 /> 24 A2 T2 T1 CONTROL INPUT (Common) T3 T2 T3 T3 M 3 Overload current protection needs to be considered DRC3R Forward L1 L2 L3 A1 T1 T2 T3 A2 Forward 13 14 Reverse 23 L2 T1 T2 L3 A3 24 DRC3Rxx420 models only Do not forget to visit us at: www.crydom.com Reverse L1 Copyright © 2017 Crydom Inc. Specifications subject to change without notice. T3 A2 DIN Rail Mount Datasheet TIMING DIAGRAM Input/Output 1 TIMING DIAGRAM FOR DRC3R 3 4 5 6 2 7 8 9 10 Input A1 Input A3 FWD Direction 100 msec 100 msec REV Direction 100 msec STEP interlock DESCRIPTION 1, 4, 10 Initial Condition. A1 & A3 open 2 A1 is activated, FWD Output waits for 100msec 3, 9 FWD direction is activated 4 A1 changes to off. FWD Output is disabled at the same time 5 Input A1 Input A3 FWD REV Open Open Off Off Close Open On Off A3 is activated. REV Outputs waits for 100msec Open Close Off On 6 REV direction is On Close Close Off Off 7 Interlock fuction is activated. REV is disabled due to A1 & A3 both being active 8 A3 is open, A1 is closed, activation delayed 100msec AGENCY APPROVALS Agency Approvals Certification in accordance with: United States Standard for Industrial Control Equipment - UL 508 and Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14. China Compulsory Certification for AC Semiconductor Motor Controller-GB14048.6-2008 DRC3 series conforms to the harmonized EN standard EN/IEC 60947-4-2 Electromagnetic Compatibility: IEC 61000-4-2 : Electrostatic Discharge – Level 3 IEC 61000-4-4 : Electrically Fast Transients – Level 3 IEC 61000-4-5 : Electrical Surges – Level 3 Vibration Resistance: IEC 60068-2-6 : Amplitude Range 10-55 Hz, Displacement 0.75mm Shock Resistance: IEC 60068-2-27 : Peak Acceleration 15g, Duration11msec. E116949 s (Only DRCx40x4x & DRCx48x4x) Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount Datasheet ACCESSORIES FOR ALL DEVICES Recommended Accessories Motor Nominal Current Bimetal Overload Relay Electronic Overload Relay Thermal Magnetic Circuit Breaker (Push Button) Thermal Magnetic Circuit Breaker (Selector) 0.40 - 0.63 A LRD04 LR97 D015xx GV2ME04 GV2P04 0.63 - 1 A LRD05 LR97 D015xx GV2ME05 GV2P05 1 - 1.6 A LRD06 LR97 D07xx GV2ME06 GV2P06 1.6 - 2.5 A LRD07 LR97 D07xx GV2ME07 GV2P07 2.5 - 4 A LRD08 LR97 D07xx GV2ME08 GV2P08 4 - 6.3 A LRD10 LR97 D25xx GV2ME10 GV2P10 6.3 - 10 A LRD14 LR97 D25xx GV2ME14 GV2P14 Fully compatible with Schneider Electric thermal overload relays & thermal magnetic circuit breakers Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block. All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter. The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor) When the LAD7C1 module is used, the common terminal for the control input is not anymore the ”A2” terminal of DRC but it is the “96” terminal of the overload relay. ID Marker Strips CNLB, CNLN, CNL2 Packages of 10 plastic strips comprising 10 individual markers which can be placed for easy identification during the use of multiple units. Numbered 1 to 10 Strips Part no.: CNLN Blank Strips Part no.: CNLB Numbered 11 to 20 Strips Part no.: CNL2 Do not forget to visit us at: www.crydom.com Copyright © 20167 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount Datasheet GENERAL NOTES (1) All parameters at 25°C unless otherwise specified. (2) For DRC3P relay will self trigger between 900-1200V, Not suitable for capacitive loads. (3) For DRC3R over rated voltage internal self protection will be activated increasing leakage current. (4) Mounted in the Vertical position. (5) On DRC3R models the range for option D is 18-30 VAC. (6) For low temperature operation consider nominal control voltage. (7) For DRC3R the turn-on time is 100msec ± 30msec. (8) When is complete removed the control signal. For DRC3R the turn-off time is 20msec. (9) Operating voltage range 18-30 VDC is also valid when used to latch the DRC contactor control input. (10) For input to auxiliary output the dielectric strength is 2.5kV. (11) UL approval up to 40°C surrounding temperature. (12) Reverse Amber Indicator is for DRC3R models only. (13) 100kA, 480VAC, when protected with CC class fuses rated 600VAC, 20 A or equivalent. (14) All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report). (15) IP20 rating is not associated with the UL approval. (16) Derate information is valid when DCR contactors are used with or without accessories, installed on top and/or bottom. (17) Minimum spacing to obtain max. current is 22mm between adjacent units. (18) Combinations of these Protective Devices and Solid State Contactor have not been evaluated by UL. (19) For DRC3P models external loads can be connected in parallel to the control input. (20) DRC3R internal safety interlock circuit prevents the product to work if any leakage current is present in the control input currently not enabled. Rev. 083117 ECN 20312 Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DIN Rail Mount Datasheet DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH. • Disconnect all power before installing or working with this equipment. • Verify all connections and replace all covers before turning on power. Failure to follow these instructions will result in death or serious injury. RIESGO DE DESCARGA ELECTRICA O EXPLOSION. • Desconectar todos los suministros de energia a este equipo antes de trabajar con este equipo. • Verificar todas las conexiones y colocar todas las tapas antes de energizer el equipo. El incumplimiento de estas instrucciones puede provocar la muerte o lesiones serias. RISQUE DE DESCHARGE ELECTRIQUE OU EXPLOSION • Eteindre toutes les sources d'énergie de cet appareil avant de travailler dessus de cet appareil • Vérifier tous connections, et remettre tous couverts en olace avant de mettre sous De non-suivi de ces instructions provoquera la mort ou des lésions sérieuses sérieuses. GEFAHR EINES ELEKTRISCHE N SCHLAGES ODER EINER EXPLOSION. • Stellen Sie jeglichen Strom ab, der dieses Gerät versorgt, bevor Sie an dem Gerät Arbeiten durchführen • Vor dem Drehen auf Energie alle Anschlüsse überprüfen und alle Abdeckungen ersetzen. Unterlassung dieser Anweisungen können zum Tode oder zu schweren Verletzungen führen. RISCHIO DI SCOSSA ELETTRICA O DELL’ESPLOSIONE. • Spenga tutta l'alimentazione che fornisce questa apparecchiatura prima di lavorare a questa apparecchiatura 存在电击、 爆炸或电弧 闪烁危险 • 在操作此设 备之前请先 关闭电源。 若不遵守这些说明, 可能会导致严重的 人身伤害甚至死亡。 • Verificare tutti i collegamenti e sostituire tutte le coperture prima dell’accensione L'omissione di queste istruzioni provocherà la morte o lesioni serie WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告 RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE RISQUE DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER GEFAHR VON MATERIALSCHÄDEN UND GEHÄUSEERHITZUNG • The product's side panels may be hot, allow the product to cool before touching. • Follow proper mounting instructions including torque values. • Do not allow liquids or foreign objects to enter this product. • Les panneaux latéraux du produit peuvent être chauds. Laisser le produit refroidir avant de le toucher. • Respecter les consignes de montage, et notamment les couples de serrage. • Ne pas laisser pénétrer de liquide ni de corps étrangers à l'intérieur du produit. • Die Seitenwände können heiß sein. Lassen Sie das Produkt abkühlen, bevor Sie es berühren. • Beachten Sie die Montageanweisungen, • Führen Sie keine Flüssigkeiten oder Fremdkörper in das Produkt ein. Le non-respect de cette directive peut entraîner, Failure to follow these instructions can result in des lésions corporelles graves ou des serious injury, or equipment damage. dommages matériels. Die Nichtbeachtung dieser Anweisung kann Körperverletzung oder Materialschäden zur Folge haben. RIESGO DE DAÑOS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD RISCHIO DI DANNI MATERIALI E D'INVOLUCRO CALDO 材料损坏和高温外壳的危险性 • Los paneles laterales del producto pueden estar calientes. Esperar que el producto se enfríe antes de tocarlo. • Respetar las instrucciones de montaje, y en particular los pares de apretado. • No dejar que penetren líquidos o cuerpos extraños en el producto. • I pannelli laterali dell'apparecchio possono scottare; lasciar quindi raffreddare il prodotto prima di toccarlo. • Seguire le istruzioni di montaggio corrette. • Non far entrare liquidi o oggetti estranei in questo apparecchio. Si no se respetan estas precauciones pueden producirse graves lesiones, daños materiales. La mancata osservanza di questa precauzione può causare gravi rischi per l'incolumità personale o danni alle apparecchiature. Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. • 产品的一侧面板可能很热,在其冷却前请 不要触碰。 • 遵照正确的安装说明,包括扭矩值。 • 请勿让液体及其他异物进入本产品。 如不能正确执行这些操作说明, 极有可能造成严重人体伤害或者设备的损坏。 DIN Rail Mount Datasheet ANNEX - ENVIRONMENTAL INFORMATION The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products. Part Name Toxic or hazardous Substance and Elements Lead (Pb) Mercury (Hg) Cadmium (Cd) Hexavalent Chromium (Cr (VI)) Polybrominated biphenyls (PBB) Polybrominated diphenyl ethers (PBDE) Semiconductor die Solder 附件 - 环保信息 此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006, 电子信息产品污染控制标识要求。 部件 名称 铅 汞 镉 有毒有害物质或元素 六价铬 多溴联苯 (Pb) (Hg) (Cd) (Cr (VI)) 半导体芯片 焊接点 50 Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. (PBB) 多溴二苯醚 (PBDE)