HHP650 Series
AC-DC Power Supplies
600/780 Watts
• 85 V 305 VAC Input
• MILSTD810F Shock & Vibration
• 40 °C to +70 °C Operation
• SEMI F47 Compliant
• 6 kV Surge Rating IEEEStdC62.41
• UL508, ANSI/ISA 12.12.01 Class I, Div II
• Conformal Coating
• 3 Year Warranty
The HHP650 AC-DC power supply provides upto 780 W (1000 W peak) of
output power in a robust mechanical fan-cooled package for industrial
applications. The unit comprises of a main output with voltages from 12-48
VDC and a 5 VDC standby supply which can be utilitsed with the signals and
control features of the unit to provide detection of loss of output and remote
on/off control.
Dimensions:
HHP650:
9.99 x 4.20 x 2.50” (253.8 x 106.8 x 63.5 mm)
Models & Ratings
Output Voltage
V1
12
15
24
28
36
48
V
V
V
V
V
V
Output Current V1
Nom
Peak(1)
<180 V
>180 V
<180 V
>180 V
50.0 A
40.0 A
27.0 A
32.5 A
33.3 A
41.7 A
23.0 A
27.9 A
28.6 A
35.7 A
18.0 A
21.7 A
22.2 A
27.8 A
13.5 A
16.3 A
16.7 A
20.8 A
Standby
Supply
5
5
5
5
5
5
V
V
V
V
V
V
/
/
/
/
/
/
0.2
0.2
0.2
0.2
0.2
0.2
A
A
A
A
A
A
Output Power V1
Nom
Peak(1)
<180 V
>180 V
<180 V
>180 V
607 W
607 W
657 W
780 W
800 W
1000 W
651 W
780 W
800 W
1000 W
657 W
780 W
800 W
1000 W
657 W
780 W
800 W
1000 W
Model Number
HHP650PS12
HHP650PS15
HHP650PS24
HHP650PS28
HHP650PS36
HHP650PS48
Notes
1. Peak Power available for 10 seconds maximum with a 35% duty cycle. The average power in a period should be equal or less than the nominal power.
Mechanical Details
VO+
Standard Terminal Block
M3.5 Screw 3 Pins
L
9.5mm Center
Standard Terminal Block
M4 Screw 6 Pins 9.5mm Center
VO-
N
VR
2.50 (63.54)
B
LED
2.50 63.500
9.99 (253.80)
PIN 11
PIN 12
PIN 1
PIN 2
A
A
A Mounting hole
8 places M3 X 0.5
0.15(3.8) Max. Penetration
1.95 (49.50)
DETAIL B
Logic Connector J3
4.20 (106.77)
A
A
A
A
C
L
3.04 (77.30)
6.31 (160.30)
1
www.xppower.com
0.47 (11.90)
0.92 (23.30)
HHP Series
AC-DC Power Supplies
Input
Characteristic
Minimum
Input Voltage - Operating
85
Input Frequency
47
Typical
50/60
Power Factor
Maximum
Units
Notes & Conditions
305
VAC
Derate output power 10% < 90 VAC.
63
Hz
Agency approval, 47-63 Hz
EN61000-3-2 class A compliant
>0.9
Input Current - Full Load
EN61000-3-2 class C for loads ≥10%
6.5/3.2
A
115/230 VAC
305 VAC cold start, 25 ºC
305 VAC/60 Hz
Inrush Current
60
A
Earth Leakage Current
1.5
mA
Maximum
Units
Notes & Conditions
48
VDC
See Models and Ratings table
±1 (V1) , ±5 (V Standby)
%
50% load, 115/230 VAC
±10
%
V1 only. See mechanical details.
500
ms
Input Protection
T16 A / 250 V internal in-line fuse
Output
Characteristic
Output Voltage - V1
Minimum
Typical
12
Initial Set Accuracy
Output Voltage Adjustment
Minimum Load
0
A
Start Up Delay
Hold Up Time
20
Drift
Line Regulation
Load Regulation
ms
90 VAC
±0.2
%
After 20 min warm up
±0.5
%
±1 (V1) , ±5
Transient Response - V1
Ripple & Noise
%
0-100% load.
4
%
Recovery within 1% in less than 500 µs
for a 50-75%-50% load change
(V Standby)
1
% pk-pk
Overvoltage Protection
115
145
%
Vnom DC. Output 1 only, recycle input to reset
Overload Protection
110
175
%
Output 1 only, auto reset. See fig 1.
°C
Auto reset. Input & output stage protection
Short Circuit Protection
V1: 20 MHz bandwidth
Trip & restart (hiccup mode)
Overtemperature Protection
100
Temperature Coefficient
0.05
%/˚C
Overtemperature Protection
°C
Protects unit from overtemperature. Auto reset.
Output Overload Characteristics
Figure 1
100
Trip & Restart
Output Voltage (%)
75
50
25
0
200
400
600
800
1000
1200
1400
Output Power (W)
www.xppower.com
2
HHP Series
AC-DC Power Supplies
General
Characteristic
Minimum
Efficiency
Isolation: Input to Output
Input to Ground
Output to Ground
Typical
%
VAC
2000
VAC
500
VAC
kHz
PFC
200
kHz
Main converter
130
kHz
Standby
7.4
W/in3
>180 VAC
177
kHrs
MIL-HDBK-217F, +25 °C GB
2.8 (1.7)
lb (kg)
Efficiency Vs Load
Figure 2
HHP650PS12
Figure 3
HHP650PS48
3
Notes & Conditions
See fig. 2 & 3
70
Power Density
Weight
Units
3000
Switching Frequency
Mean Time Between Failure
Maximum
85
www.xppower.com
HHP Series
AC-DC Power Supplies
Signals & Controls
Characteristic
Notes & Conditions
Remote Sense
Compensates for 0.5 V total voltage drop
DC OK
Volt free relay contacts NO/NC (see fig.4)
Remote On/Off (Inhibit/Enable)
Uncommited isolated optocoupler diode, powered diode inhibits both V1 & V2 (fan supply) (see fig.5)
Current Share
When 2 to 5 units (with the same output voltage) are used in parallel to increase output current, the current share pins 7/8 of one unit
should be connected to pins 7/8 of the other unit(s). This will force the current to share between the outputs. Similarly pins 9/11 of
each unit should also be connected as a ground reference. Units share current within 10% of each other at full load.
Standby Supply
Isolated 5 V/0.2 A supply, always present when AC supplied.
DC OK
Figure 4
POWER SUPPLY
1
8
+
NC
COM
NO
-
Pin 4
2
7
Pin 10
3
6
Pin 2
4
5
Chassis J3 Logic Connector
Remote On/Off (Inhibit)
Figure 5
INHIBIT HI
INHIBIT LOW
800 R
POWER SUPPLY
800 R
5 V Standby
Pin 3
5 V Standby
Pin 3
2-5 mA
100 R
2-5 mA
Inhibit Hi
Pin 6
POWER SUPPLY
100 R
Inhibit Hi
Pin 6
<0.8 V):
>4.5 V):
Inhibit Lo
Pin 5
Inhibit Lo
Pin 5
5 V Standby
Return Pin 1
5 V Standby
Return Pin 1
Chassis J3 Logic Connector
Signal
High: Power Supply OFF
Low or Floating: Power Supply ON
Chassis J3 Logic Connector
Signal
www.xppower.com
High: Power Supply ON
Low or Floating: Power Supply OFF
4
HHP Series
AC-DC Power Supplies
Environmental
Characteristic
Maximum
Units
Operating Temperature
Minimum
-40
Typical
+70
°C
See derating curve, fig.6
Notes & Conditions
Storage Temperature
-40
+85
°C
Some specification parameters maybe exceeded
until after 20 minutes warm up period.
Forced-cooled via integral dual voltage level fan,
which is load dependant. See fig.7
Cooling
Humidity
Operating Altitude
95
%RH
5000
m
Non-condensing
Shock
30 g pk, half sine, 6 axes EN60068-2-27, -2-47
& MIL-STD-810F 514.5 cat 4
Vibration
2 g rms, 5-500 kHz, 3 axes EN60068-2-6 & MILSTD-810F 516.5 cat 1
Temperature Derating Curve
Fan Speed Control
Figure 6
Figure 7
100
0
-40
Fan Speed (%)
50
Some specification
parameters may not be met
Output Load (%)
100
50
0
-20
0
+50
+70
0
25
Ambient Temperature (ºC)
50
75
Output Power (%)
EMC: Emissions
Phenomenon
Standard
Test Level
EN55011/22
Class B
Radiated
EN55011/22
Class A
Harmonic Current
EN61000-3-2
Class A
Standard
Conducted
Criteria
Notes & Conditions
Test Level
Criteria
Notes & Conditions
EMC: Immunity
Phenomenon
Voltage Fluctuations
Low Voltage PSU EMC
EN61000-3-3
EN61204-3
High severity level
as below
ESD Immunity
EN61000-4-2
3
A
Radiated Immunity
EN61000-4-3
3
A
EFT/Burst
EN61000-4-4
3
A
EN61000-4-5
Installation class 3
A
IEEEStdC62.41-loc cat C1
6kV, 3 kA
Surges
Conducted
EN61000-4-6
EN55024 (100 VAC)
Dips and Interruptions
EN55024 (240 VAC)
3
A
Dip 30% (70 VAC), 416 ms
B
Dip >95% (0 VAC), 4160 ms
Dip >95% (0 VAC), 10.0 ms
B
Dip 30% (70 VAC), 500 ms
B
Dip >95% (0 VAC), 5000 ms
B
SEMI F47
55
A
Dip >95% (0 VAC), 8.3 ms
www.xppower.com
A
Compliant
100
HHP Series
AC-DC Power Supplies
Safety Approvals
Safety Agency
Safety Standard
Notes & Conditions
CB Report
IEC60950-1:2005 + A1:2009
Information Technology
UL60950-1 (2011), CSA 22.2 No.60950-1
Information Technology
UL508, CSA 22.2 No. 107.1-01
Industrial Control Equipment
ANSI/ISA 12.12.01-2000
Hazardous Locations
TUV
EN60950-1 A12:2011
Information Technology
CE
LVD & RoHS
Equipment Protection Class
Class I
UL
See safety agency conditions of acceptibility for details
Mechanical Details
VO+
Standard Terminal Block
M3.5 Screw 3 Pins
L
9.5mm Center
Standard Terminal Block
M4 Screw 6 Pins 9.5mm Center
VO-
N
VR
2.50 (63.54)
B
LED
2.50 63.500
9.99 (253.80)
PIN 11
PIN 12
PIN 1
A
A
PIN 2
A Mounting hole
8 places M3 X 0.5
0.15(3.8) Max. Penetration
1.95 (49.50)
DETAIL B
Logic Connector J3
A
A
4.20 (106.77)
C
L
3.04 (77.30)
A
A
6.31 (160.30)
0.47 (11.90)
0.92 (23.30)
J3 Logic Connector
(JST S12B-PHDSS)
Pin
Function
1
5 V Standby Return
2
NO (Relay)
3
+5 V Standby
4
N.C (Relay)
5
- Inhibit
6
+ Inhibit
7
Current Share
8
Current Share
9
- Sense / Signal GND
10
COM (Relay)
11
- Sense / Signal GND
12
+Sense
Notes
1. Dimensions shown in inches (mm).
2. Weight: 2.8 lb (1.27 kg).
3. J1 Mating Plug: JST part no. PHR-2, contact: JST part no. SPH-002T-P0.5S;
J2 Mating Plug: JST part no. PHDR-10VS, contact: 26-22AWG JST part no. SPHD-001T-P0.5
www.xppower.com