ETC2 APT-DINAV53G3 3-channel power transducer Datasheet

Energy Management
3-channel Power Transducer
Type APT-DIN
• Measurement of: kW
• 9 selectable full-scales
in 9 intervals from 0 to 5 (range from 0,4kW to 3,6kW)
• Degree of protection (front): IP 50
• 3 analogue outputs (0 to 10VDC)
• Response time: ≤50ms
Product Description
Ordering Key
APT-DINAV53G3 2 1
ing range from 0,4 to 3,6kW)
The house is for DIN-rail
mounting and ensures a
degree of protection (front)
of IP 50.
Model
Range code
System
Power supply
Rated outputs
Number of inputs
Calibration
Range code
System
Power supply
Rated outputs
AV5:
3:
D:
230VAC –15+10%
50/60Hz
3:
G:
400VAC –15+10%
50/60Hz
Active power transducer
with auxiliary power supply of 400VAC (phasephase connection). 9 measuring ranges selectable in 9
intervals from 0 to 5 (measur-
Type Selection
400 VAC - 5,2 AAC
(max. 480 V (L-L) 6,2 A) (standard)
Three phase system
(3 wires, balanced/
unbalanced load)
Number of inputs
Calibration
2:
1:
2 x (3-phase inputs)
3 x (0 to 10VDC)
3600W.
Input Specifications
Rated inputs
Accuracy
Active power
(@ 25°C ± 5°C, R.H. ≤ 60%)
Additional errors
Humidity
Input frequency
Magnetic field
Ripple
2 (3-phase inputs) for current
and voltage measurements
±3% rdg (cos ϕ 0.7 L/C,
0.5 to 1Ph)
< 0.5%, 60% to 90% R.H.
< 0.5%, 50 to 60 Hz
< 0.5% @ 400 A/m
balanced load: ≤1% according to IEC 60688-1 and
Measurement
Ranges (impedances)
AV5:
Frequency range
Over-load protection
Continuous: voltage/current
For 1 s
Voltage:
Current:
EN 60 688-1
unbalanced load: ≤5%
kW
400VAC (≤2W per channel)
5.2AAC (≤0.3 VA per channel)
48 to 62 Hz
1.2 x rated input
2 x rated input
20 x rated input
Output Specifications
Analogue outputs
Number of outputs
Range
Response time
Temperature drift
Load:
10 V output
3 (one per channel)
0 to 10 VDC
≤ 50 ms typical
±500 ppm/°C
≥ 10 kΩ
Specifications are subject to change without notice
Analogue outputs
Insulation
APT-DIN 3 DS0603
By means of optocouplers,
2000 Vrms output to
measuring input /
power supply
1
APT-DIN
Supply Specifications
AC voltage
400 VAC (standard),
-15%+10% 50/60 Hz
230VAC (optional)
–15+10% 50/60Hz
Power consumption
≤ 7 VA
General Specifications
Operating temperature
Storage temperature
Insulation reference voltage
Insulation
Dielectric strength
-20 to +60°C (–4 to 140°F)
(R.H. < 90% non-condensing)
-30 to +80°C (–22 to 176°F)
(R.H. < 90% non-condensing)
300 Vrms to ground
(with neutral connection),
CAT II (double insulation),
CAT III (main insulation)
Pollution degree 2
4000 Vrms between all inputs/
outputs to ground
4000 Vrms for 1 minute
Noise rejection
CMRR
EMC
Safety standards
Safety requirements:
Products requirements:
Connector
Housing
Dimensions
Material
Degree of protection
Weight
100 dB, 48 to 62 Hz
EN 50081-1, EN 50082-1
IEC 61010-1, EN 61010-1
IEC 60688-1, EN 60688-1
Screw-type,
max. 4 mm2 wires
115 x 76 x 100 mm
ABS, self-extinguishing: UL94 V-0
Front: IP50
Approx. 810 g
(packing included)
Front Panel Description
Wiring Diagrams
Three-phase, 3-wire ARON input connections - Unbalanced loads
4
1
2
3
CT connection (3-wire system)
1. Rotary switch
9-position rotary switch for input full scale selection (at
every selected input full scale correspond a 10VDC output) .
2. LED
Power-ON.
3. Connection terminal blocks
4. Connection terminal blocks
Dimensions
2
APT-DIN 3 DS0603
Specifications are subject to change without notice
Similar pages