Gamewell-FCI MCBL-7 Fire alarm control panel with built-in dact and remote-site upload/download capability Datasheet

Features
Flex 405
Fire Alarm Control Panel with built-in DACT
and remote-site upload/download capability
Description
g2405ph1.jpg
The Gamewell Flex 405 is a 24-volt,
five-zone Fire Alarm Control Panel
FACP) with built-in communicator and
remote-site upload/download capability. The integral communicator transmits event information (alarms,
troubles, supervisories, faults, etc.) to
a UL-Listed central station. The Flex
405 may be used in a variety of costeffective applications, including: local
fire alarm control panel (communicator disabled), fire alarm control panel/
communicator, stand-alone sprinkler
supervisory communicator, or slave
communicator to a UL-Listed host fire
alarm panel (requires normally-open dry
contacts to trigger five channels). Selectable transmission formats allow the
Flex 405 to communicate to virtually all central stations.
Remote-Site Upload/Download
The Flex 405 may be downloaded or uploaded without affecting the system fire
protection. Download system programming, and upload key system information
such as: current system status, history and walk test files; zone, AC line, NAC
1 and NAC 2, resettable power and battery voltages; and system programming.
Upload or download within one minute without affecting normal fire panel functions. The upload/download function also features multiple security techniques.
The Flex 405 requires the PK-CD programming kit, which works with most Hayescompatible modems (consult factory for listing).
• Five programmable Initiating Device Circuits
(zones). Each zone may be programmed for:
two-wire smoke detectors, normally open
contact devices (pull stations, heat detectors),
four-wire smoke detectors, waterflow
operation, supervisory operation, auto-reset
supervisory operation.
• Two built-in, Class A or B (Style Z or Y)
Notification Appliance Circuits (NACs).
NACs may be programmed: silenceable,
non-silenceable (a strobe circuit can keep
flashing after the panel is silenced), autosilence (program 5 to 30 minutes), silence
inhibit (60 seconds), coding (march time,
temporal, California).
• 3.0 amps of notification appliance power,
expandable to 5.0 amps (meets the critical
power requirements for ADA and UL-1971
devices).
• Two built-in Form-C Alarm and Trouble relays.
• Supervisory and communication fail outputs.
• Dual-line rotary- or Touch-Tone®-dial DACT
interfaces to public telephone network (leased
phone lines are not required).
• 24-Volt operation.
• Built-in voltmeter measures: zone voltage;
primary AC line voltage; battery voltage;
NAC(s) voltage; resettable 24-volt power.
• Surface Mount Technology (SMT).
• Fully programmable via built-in keypad (no
costly external programmers necessary).
• Complies with NFPA 72 (Local, Central
Station and Remote Station [DACT only – not
polarity reversal] Fire Alarm Systems).
• Reporting formats include:
3+1, 4+1, 4+2 Standard + Expanded;
4+1, 4+2, Ademco Express.
• Integral battery charger for up to 60 hours of
standby power.
• Fuseless, power-limited technology meets
UL power-limiting requirements.
• Programmable alarm presignal timer, alarm
verification timer, and optional trouble
reminder.
• Single-person walk test. Fire drill function.
• Zone disable capability (software).
• 32-Event history buffer with time-and-date
stamp. Accurate real-time clock/calendar.
• Extensive built-in transient protection.
• Electronics and operational controls fully
enclosed in a lockable cabinet capable of
housing up to 7 AH batteries.
• Optional: contact-by-zone module, remote
annunciator, printer interface for on- or off-line
printing.
Listings
Listings and approvals below apply to the
basic Flex 405 panel. In some cases, certain
modules may not be listed by certain
approval agencies, or listing may be in
process. Consult factory for latest listing
status.
• UL Listed.
• CSFM approved: file 7165-1288:179.
• MEA approved: file 366-04-E.
Flex 405 CS-2405 09/01/06
Page 1 of 4
Specifications
Ordering Information
F405
Five-zone, 24-volt fire alarm control communicator. Includes
backbox, transformer, technical manual, and frame-and-post
operating instruction sheet.
XRM-24
120 VAC, 100 VA transformer expands NAC power from 3.0
to 5.0 amps.
SAN-405
Five-zone remote annunciator (RZA-5F), mounts to a singlegang box (requires ADM-24).
ADM-24
Annunciator driver module (supports SAN-405).
RM-5F
Five-zone relay module, provides contact-by-zone.
CAC-5F
Class A converter module. Converts all Class B initiating
device circuits (zones) to Class A.
PRT-24
Printer interface module, provides an EIA-232 printer output.
Includes cable, DB9F and DB25 adapter.
PK-CD
Contains programming software for Windows®-based PC
computer (cable not included).
MCBL-7
DACT phone cord, 7 feet (2.134 m) long (two required).
BB-17F
Battery backbox, required for batteries over 7 AH.
TR-3-R
Trim ring.
52223
Flex 405 Installation and Maintenance Manual.
• Single PC board design using Surface Mount
Technology (SMT).
• Two modular telephone jacks for connection to
RJ31X/modules.
AC power
• 120 VAC, 50/60 Hz, 2.3 A.
• Wire size: minimum 14 AWG
(2.0 mm²) with 600-volt insulation.
• Built-in brownout circuitry, built-in voltmeter.
Communicator
• One line-active indicator for each of two
phone lines.
• “Kiss-Off” signal LED.
• Dual “low telephone voltage detect” circuitry.
• Programmable event codes per each format.
• Up to 62 transmitted events/messages.
Selectable/deselectable transmissions of 62
events.
• Five zones may be configured to five
channels as a slave communicator (channels
are auto-resettable.
Communication formats
Express formats allow complete transaction to
be communicated in under five seconds.
• 20 PPS, 3+1 standard & expanded.
• 20 PPS, 4+1 standard & expanded.
• 20 PPS, 4+2 standard & expanded.
• 4+1 and 4+2 Ademco Express.
Initiating device circuits (zones)
• The Flex 405 includes five programmable
initiating device circuits (zones). Circuits 1, 2, 4,
and 5 are Style B (Class B). Circuit 3 is Style
D (Class A). Use Class A converter module
(P/N CAC-5F) to convert Class B IDCs to
Class A.
• Each zone may support two-wire smoke
detectors. Programming options include:
waterflow (silenceable/non-silenceable),
supervisory (standard/auto-reset), pull station,
normally-open-contact device.
• All circuits are power-limited and supervised.
• All circuits allow up to 100 ohms of line
resistance. Use 12 to 18 AWG wire (3.1 to
0.78 mm²).
Notification appliance circuits
• Two Style Z/Y (Class A/B) @ 2.5 A each.
• All circuits are fully power-limited
and meet UL power-limiting requirements.
Auxiliary outputs
• Resettable four-wire smoke detector power @
300 mA. Non-resettable power @ 300 mA.
• Integral Form-C Alarm and Trouble relays.
• Relay drivers for supervisory and
communication fail.
Cabinet specifications
• The compact cabinet can be surface- or semiflush-mounted.
• Knockouts on the top, sides, and back
provide ease of wire entry.
• Dimensions, Door: 15.219” high x 14.219” wide
(38.655 cm H x 36.115 cm W). Backbox: 15.0”
high x 14.5” wide x 3.0” deep (38.1 cm H x
36.83 cm W x 7.62 cm D). Trim ring (P/N TR1-R): 18.125” high x 17.62” wide (46.038 cm H
x 44.755 cm W).
Page 2 of 4
Flex 405
CS-2405 09/01/06
UL-Listed Receivers Compatible
with the Flex 405
Format #
(Addresses 16 & 42)
Ademco
685 (1)
Silent
Knight
9000
ITI
CS-4000
(3)
FBI
CP220FB
Osborne
Hoffman
Models
1&2
0
4+1 Ademco Express
4
4
1
4+2 Ademco Express
4
4
4 (8)
2
3+1/Standard/1800/2300
4
4 (2)
4
4 (4)
4
3
3+1/Expanded/1800/2300
4
4 (2)
4
4 (4)
4
3+1/Standard/1900/1400
4
4 (2)
5
3+1/Expanded/1900/1400
4
4 (2)
6
4+1/Standard/1800/2300
4
4 (2)
7
4+1/Expanded/1800/2300
4
8
4+1/Standard/1900/1400
9
Radionics
6000/6500
(5)
Sescoa
3000R
(7)
SurGuard
MLR-2
(9)
4
4
4
4
4
4
4
4 (4)
4
4
4
4 (4)
4
4
4
4 (4)
4
4
4
4 (2)
4 (4)
4
4
4
4
4 (2)
4 (4)
4
4
4
4+1/Expanded/1900/1400
4
4 (2)
4 (4)
4
4
4
A
4+2/Standard/1800/2300
4
4 (2)
4 (4)
4
4
4
B
4+2/Expanded/1800/2300
4
4 (2)
4 (4)
4
4
4
C
4+2/Standard/1900/1400
4
4 (2)
4 (4)
4
4
4
D
4+2/Expanded/1900/1400
4
4 (2)
4 (4)
4
4
4
E
(NOT USED)
F
(NOT USED)
4
4
4 (5, 6)
4 (5)
4 (5)
51348t1.tbl
KEY:
(1) With 685-8 Line Card with Rev. 4.4d software.
(2) With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software.
(3) Rev. 4.0 software.
(4) FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with
Rev. 3.8 software.
(5) Model 6500 with Rev. 600 software.
(6) Model 6000 with Rev. 204 software.
(7) With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software.
(8) Model 2 only.
(9) Version 1.62 software.
Flex 405 CS-2405 09/01/06
Page 3 of 4
Notes
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation. For
more information, contact Gamewell-FCI.
Page 4 of 4
Flex 405
CS-2405 09/01/06
Similar pages