POWER LPS100-M Series 150 Watts Data Sheet Total Power: 80 - 150 Watts Input Voltage: 90 - 264 Vac 120 - 300 Vdc # of Outputs: Single SPECIAL FEATURES Medical and ITE safety approvals, 2X MOPP Active power factor correction 2” x 4” footprint Less than 1U high EN61000-3-2 compliant Remote sense Power fail Adjustable main output Built-in Class B EMI filter Overvoltage protection Overload protection Thermal overload protection Isolated 12 V fan output LPX100 Enclosure kit available POE isolation on main output of LPS109-M SAFETY TUV UL cULus CB CE CQC Electrical Specifications Input Input range 90 - 264 Vac; 120 - 300 Vdc Frequency 47 - 63 Hz Inrush current 50 A max., cold start @ 25 °C Efficiency 88% typical at full load EMI/RFI FCC Class B conducted; CISPR22 Class B conducted; EN55022 Class B conducted; VDE0878PT3 Class B conducted Safety ground leakage current 275 μA @ 50/60 Hz, 264 Vac input Output 60950, 60601-1 60950, 60601-1 60950, 60601-1 Certificate & report Mark (LVD) Mark Maximum power 100 W for convection (80 W for LPS102-M); 150 W with 30 CFM forced air (120 W for LPS102-M) Adjustment range ± 10% minimum on the main outputs Fan output 12 V @ 1 A isolated, ± 10% Hold-up time 10 ms @ 150 W load, 120 Vac input Overload protection Short circuit protection on all outputs. Case overload protected @ 110-160% above rating Overvoltage protection 15-35% above nominal output Logical Control Power failure Open collector logic signal goes high 100-500 msec after main output; it goes low at least 6 msec before loss of regulation Remote sense Compensates for 0.5 V lead drop min. Will operate without remote sense connected. Reverse connection protected. LPS100-M Series Data Sheet Environmental Specifications Operating temperature 0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up Storage temperature -40 °C to +85 °C Electromagnetic susceptibility Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Humidity Operating; non-condensing 10% to 95% RH Vibration IEC 60068-2-6 to the levels of IEC721-3-2 MTBF calculated 534,000 hours at full load and 25 °C ambient conditions, 230 V input, Bellcore Ordering Information Output Voltage Minimum Load LPS102-M 5V 0A LPS103-M 12 V 0A LPS104-M 15 V 0A LPS105-M 24 V 0A LPS108-M 48 V LPS109-M 54 V Model Number Maximum Load with Convection Cooling Ripple P/P (PARD)3 Maximum Load with 30CFM Forced Air Peak Load Regulation2 16 A 24 A 30 A ± 2% 50 mV 8.3 A 12.5 A 14 A ± 2% 120 mV 6.7 A 10 A 11 A ± 2% 150 mV 4.2A 6.3 A 7A ± 2% 240 mV 0A 2.1A 3.1 A 3.5 A ± 2% 480 mV 0A 1.85 A 2.8 A 3.1 A ± 2% 540 mV 1. Peak current lasting < 30 seconds with a maximum 10% duty cycle. 2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings. 3. Peak-to-peak with 20 MHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges. 4. This product is a Component Power Supply and is only for inclusion by professional installers within other equipment and must not be operated as a standalone product. EMC compliance to appropriate standards must be verified at the system level. This product is for sale to OEMs and System Integrators, including through Distribution Channels. It is not intended for sale to End Users. Pin Assignments Mating Connectors Connector LPS100-M AC Input (SK1) SK1 Pin 1 Neutral Molex P/N: 09-50-3031, Pins: 08-52-0072 or Landwin P/N: 3060S0302, Pins: 3360T011P Pin 3 Line AC Ground Molex: 01-90020001 Pin 1 Common Pin 2 Common DC Output (SK2) Molex P/N: 09-50-3081, Pins: 08-52-0072or Landwin P/N: 3060S0802, Pins: 3360T011P Pin 3 Common Pin 4 Common Remote Sense (SK203) Molex P/N: 35155-0400, Pins: 08-70-0056 or Landwin P/N: 2640S04A0, Pins: 2543T011P Pin 5 +Vout Fan: (SK5) Pin 6 +Vout Molex P/N: 22-01-1042, Pins: 08-70-0049 or Landwin: P/N: 2510S04A0, Pins: 2543T011P Pin 7 +Vout Pin 8 +Vout Pin 1 Common Pin 2 Power Fail Pin 3 - Remote Sense Pin 4 + Remote Sense Pin 1 +12 V Fan Pin 2 +12 V Fan Pin 3 Fan Return (Isolated) Pin 4 Fan Return (Isolated) SK2 SK203 SK5 Artesyn Embedded Technologies Connector Kit #70-841-025, includes all of the above Notes: 1. Specifications subject to change without notice. 2. All dimensions in inches (mm), tolerance is ±.02”. 3. Mounting holes M1, M2 should be grounded for EMI purpose 4. Mounting M1 is safety ground connection 5. Specifications are for convection rating at factory settings at 115 Vac input 25 °C unless otherwise stated. 6. This power supply requires mounting on metal standoffs 0.20” (5 m) in height. 7. For DC input an external DC safety rated fuse must be used. 8. Warranty: 2 years 9. Weight: 0.44 lb. / 0.20 kg LPS100-M Series Data Sheet Mechanical Drawing VR1 Output Voltage Adjust Pot M2 M1 1 SK20 3 4 SK2 8 SK5 1 1 3 3.72" (94.6) (2.7) 0.11” 1.29" 4.00" (101.6) Mounting Hole Ø0.16"[4.0] 4 Places Max. Screw Head Diameter .22” (5.6) (33.0) SK1 4 (43.8) 2.00" (50.8) 1 1.72" GND 0.197” (5.0) Minimum Standoff height WORLDWIDE OFFICES Americas Europe (UK) Asia (HK) 2900 S.Diablo Way Tempe, AZ 85282 USA +1 888 412 7832 Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom +44 (0) 1384 842 211 14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong +852 2176 3333 Artesyn Embedded Technologies, Artesyn and the Artesyn Embedded Technologies logo are trademarks and service marks of Artesyn Embedded Technologies, Inc. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. © 2016 Artesyn Embedded Technologies, Inc. All rights reserved. For full legal terms and conditions, please visit www.artesyn.com/legal. www.artesyn.com For more information: www.artesyn.com/power For support: [email protected] LPS100-M DS 28Sep2016