Bel FNP1500-12G Ac-dc power supply Datasheet

The FNP1500/1800 front-ends are power-factorcorrected (PFC) which (depending on model type)
provide a 12 VDC or 48 VDC (1500 or 1800 watt)
output, and can be used in hot-swap redundant
systems. Their very small dimensions allow
configuration of up to three units in a 1U rack. The
FNP front-ends have a front-mounted AC
receptacle. The highly efficient thermal design with
internal-fan cooling permits their use over wide
temperature ranges and provides very high
reliability.

RoHS compliant for all six substances

High density front-ends 15.2 to 18.3 W/in3

Wide input voltage range 85 to 264 VAC

12 V standby voltage, 1A per front-end

Highly efficient topology reduces operating costs

I2C interface status and control

I2C voltage and current limit setting

Analog output voltage setting

Overtemperature, output overvoltage, and output
Status information is provided with front panel
LEDs, logic signals, and via an I2C management
interface. In addition, the I2C bus can enable the
power supply, set high fan speed, adjust the output
voltage, and set the output current limit. The
FNP1500/1800's
meet
international
safety
standards and display the CE-Mark for the
European Low Voltage Directive (LVD).
FNR-3-12G and FNR-3-48G power-shelf solutions
provide rectification, system management, and
power distribution, while maintaining high reliability
and offering flexibility for future expansion. The
power shelves can be configured with up to three
hot-swappable 1500 or 1800-watt AC-DC frontends.
overcurrent protection

ORing circuits for true redundant operation:
Vo1: ORing FETs; Vo2: ORing Diodes

Status LEDs: AC OK, DC OK, and
Fan Fail/Overtemperature Fail




Telecom
Datacom
Servers
Distributed power systems
North America
+1-866.513.2839
Asia-Pacific
+86.755.29885888
Europe, Middle East
+353 61 225 977
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB1
FNP1500/FNP1800
MODEL
FNP1500-12G
3
FNP1500-48G
FNP1800-48G
INPUT VOLTAGE
VAC
AUTO SELECTED 1
108 – 264
85 – 105
105 – 264
85 – 105
180 – 264
105 – 180
85 – 105
OUTPUT 1
OUTPUT 2
Vo1 nom
Io1 max
Vo2 nom
Io2 max
VDC
12
12
48
48
48
48
48
ADC
129 @ 11.64V
101.8 @ 11.78A
32.2
25.4
39.2
32.2
25.4
VDC
12
12
12
12
12
12
12
ADC
1
1
1
1
1
1
1
RATED
POWER
W
1512
1212
1512
1212
1812
1512
1212
COMPATIBLE
SHELF 2
FNR-3-12G
FNR-3-48G
FNR-3-48G
1
The available output power is automatically adjusted depending on the input voltage.
1U standard racks are available from Bel Power Solutions. See the Rack (Power Shelf) section of this data sheet for configurations and
details.
3
Not recommended for new design.
2
Stress in excess of the absolute maximum ratings may cause performance degradation, adversely affect long-term reliability,
or cause permanent damage to the converter.
PARAMETER
Input Voltage
Operating Ambient Temperature
Storage Temperature
CONDITIONS / DESCRIPTION
Continuous
Transient, 60 ms max.
Vi min-Vi max, Io nom, cooling by internal fan
@ 100 % load
@ 50 % load
Non-Operating
MIN
MAX
264
300
UNIT
VAC
VAC
0
0
-40
50
70
85
°C
°C
°C
MIN
NOM
MAX
UNIT
85
230
264
VAC
47
50/60
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
PARAMETER
CONDITIONS / DESCRIPTION
Input Voltage
Input Frequency
63
Hz
Turn-On Input Voltage
Ramping up
79
85
VAC
Turn-Off Input Voltage
Ramping down
70
78
VAC
Inrush Current Limitation
115/230 VAC acc. ETS 300 132-1
< 100 ms
Hold-Up Time
After last AC line peak ,Vi = 230 VAC, Po nom
Power Factor
Vi nom, Io nom
0.95
Efficiency
Vi = 230 VAC, Io nom, TC = 25 °C
89 1
50
20
Max Input Current
Input Connector
1
Apk
ms
W/VA
90
%
20
Arms
16A – 20 A / 250 VAC; according to IEC320 C19
87% for FNP1500-12
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
PARAMETER
CONDITIONS / DESCRIPTION
Nominal Output Voltage
Io = 64.5 A
Vi = 230 VAC, Io1 = 65.5 A, TC = 25 °C
Output Voltage Set Point Accuracy
MIN
Nominal Current Output 2
(Factory setting)
Adjustable via I2C (Vo1 set)
Adjustable via Margin pin (R input)
Io1 nom @ Vi =108 VAC – 264 VAC, Po 1.5 kW
Io1 nom @ Vi = 85 VAC – 105 VAC, Po 1.2 kW
Io1 max @ Vi = 108 VAC – 264 VAC droop hiccup
Io1 max @ Vi = 85 VAC – 105 VAC droop hiccup
Io2 nom @ Vi = 85 VAC – 265 VAC, Po 12 W
Current Limit Output 2
Io2 max @ Vi = 85 VAC – 265 VAC
Static Line Regulation Output 1
Vi min - Vi max, 50 % Io nom, Ta = 25 °C
Vi = 230 V, 5 - 100 % Io nom
Full load to no load [0..129 A] at Vo set = 12V
Output Voltage Trimming
Nominal Current Output 1
Current Limit Output 1
Static Load Regulation Output 1
(Droop Characteristic)
Static Load Regulation Output 2
(Droop Characteristic)
11.93
-0.42
7
6.2
NOM
12
12
12
MAX
12.05
+0.42
13 1
Vo1 set
129.0
101.8
147.4
120.2
1.0
129.0
1.0
1.5
dVo1 over the setting range [7 to 13V]
-0.5
11.64
-0.36
Full load to no load @ Vi = 85 VAC – 265 VAC
VDC
VDC
% Vo1 nom
VDC
VDC
ADC
ADC
ADC
ADC
ADC
ADC
0.5
- 5.58
12
UNITS
12.36
+0.36
0.4
% Vo nom
mV/A
VDC
VDC
VDC
Load change 50 % <─> 100 % Io nom, dIo/dt =1A/s
Voltage deviation (droop + over- or undershoot)
Dynamic Load Regulation
Current Share
Start-Up Time
Output Voltage Ripple and Noise
(Filter 10nf/10µf)
Remote Sense
-2
Max. recovery time to within 1% of Vo1 nom
Difference in current between two units for Vo1 above
10 % load.
Time required for output within regulation after initial
application of AC-input (Vi nom, Io nom)
after removal of inhibit (Vi nom, Io nom)
Vi nom, Io nom, 20 MHz bandwidth
Vo1
Vo2
Total compensation for cable losses
2
% Vo nom
400
s
12.9
ADC
1.5
s
ms
120
120
500
mVpp
mVpp
mV
100
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
PARAMETER
CONDITIONS / DESCRIPTION
MIN
NOM
MAX
UNITS
Nominal output voltage Vo1
Io = 16.1 A
48
VDC
Nominal output voltage Vo2
Io = 0.5 A
Vi = 230 VAC, Io1 =16.1 A, TC = 25 °C
12
VDC
Output voltage set point accuracy
Output voltage trimming
(via I2C or with external resistor)
(47.8 - 48.2 VDC)
Adjustable (44.16 to 51.84 VDC)
Nominal current output 2
Io1 nom @ Vi =105 VAC – 264 VAC,
Io1 nom @ Vi = 85 VAC – 105 VAC,
Io1 nom @ Vi =180 VAC – 264 VAC,
Io1 nom @ Vi =105 VAC – 180 VAC,
Io1 nom @ Vi = 85 VAC – 105 VAC,
Io1 max @ Vi = 105 VAC – 264 VAC
Io1 max @ Vi = 85 VAC – 105 VAC
Io1 max @ Vi = 180 VAC – 264 VAC
Io1 max @ Vi = 105 VAC – 180 VAC
Io1 max @ Vi = 85 VAC – 105 VAC
Io2 nom @ Vi = 85 VAC – 264 VAC,
Current limit output 2
Io2 max @ Vi = 85 VAC – 264 VAC
Static line regulation output 1
Vi min - Vi max, 50 % Io nom
Vi = 230 V, 5-100 % Io nom
Vo : full load (32.2 ADC) to no load
Vi = 230 V, 5-100 % Io nom
Vo : full load (32.2 ADC) to no load
Vi = 230 V, 5-100 % Io nom
Vo : full load (32.2 ADC) to no load
Load change 50 % <--> 100 % Io nom, dIo/dt =1 A/s
FNP1500-48G
Nominal current
output 1
FNP1800-48G
FNP1500-48G
Current limit output 1
FNP1800-48G
Static load regulation
output 1
(droop characteristic)
FNP1500-48G
FNP1800-48G
Static load regulation
output 2 (droop characteristic)
-0.5
+0.5
% Vo1 nom
-8
+8
% Vo1 nom
Po 1.5 kW
Po 1.2 kW
Po 1.8 kW
Po 1.5 kW
Po 1.2 kW
32.2
25.4
39.2
32.2
25.4
36.8
30
43.8
36.8
30
1.0
droop hiccup
droop hiccup
droop hiccup
droop hiccup
droop hiccup
Po 12 W
39.2
1.0
1.5
-0.5
46.54
45.91
ADC
0.5
90.1
48
90.1
48
ADC
ADC
ADC
ADC
ADC
ADC
ADC
ADC
ADC
ADC
ADC
49.44
49.44
0.4
% Vo nom
mV/A
VDC
mV/A
VDC
VDC
% Vo nom
Voltage deviation (droop + over- or undershoot)
Dynamic load
regulation
FNP1500-48G
-5
5
% Vo nom
FNP1800-48G
-5.7
5.7
% Vo nom
400
s
3.2
ADC
3.9
ADC
1.5
s
ms
480
120
500
mVpp
mVpp
mV
MAX
UNIT
All models
Current Share
Max. recovery time to within 1 % of Vo1 nom
Difference in current between two units for Vo1 above
10 % load.
FNP1500-48G
FNP1800-48G
Start-up time
Output voltage ripple and noise
(Filter 10 nF/10 µF)
Remote sense
PARAMETER
Input fuse
Time required for output within regulation
after initial application of AC-input (Vi nom, Io nom)
after removal of inhibit (Vi nom, Io nom)
Vi nom, Io nom, 20 MHz bandwidth
100
Vo1
Vo2
Total compensation for cable losses
CONDITIONS/DESCRIPTION
MIN
25A, fast blow
Tracking
Absolute for 48V models
Absolute for 12V models
Automatic power shutdown at TC
No-load -, short circuit - and overload proof
122
% Vo nom
115
59.5
V
16.85
V
95
°C
Inrush current limitation
With NTCs
Output
Overvoltage protection latching1
Overtemperature protection
1
NOM
Not user accessible
Remove input voltage to reset.
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
PARAMETER
CONDITIONS / DESCRIPTION
Status Indication
LEDs: DC OK (green), AC OK (green); fan fail and overtemperature (amber)
I2C Digital Bus
Monitors alarm functions and sets parameters
PS Present Pin
Contact closure to logic ground ( internal pull-down resistor of 1 kΩ)
PS Remote Shutdown / Inhibit Pin
Power Supply OK (I2C)1
DC Current Fail (I2C)1
AC Fail / Power Down Warning
(I2C & OC)2
DC fail / Output Voltage Fault
(I2C & OC)2
Temperature Warning (I2C & OC)2
DC Voltage Monitoring (I2C)1
DC Current Monitoring (I2C)1
DC Voltage Trimming
(I2C or external resistor)1
Fan speed control (I2C)1
Fan OK (I2C & OC)2
Synch. Startup Pin
1
2
TTL compatible signal, inhibited when open contact, high or at TTL logic “1”.
Signal referenced to logic return (LRTN)
AC OK & DC OK & no overcurrent & no overtemperature & fans working
Overcurrent on Io1
Provides a warning that the input power has failed at least 5 ms before the output falls
out of regulation (<90% Vo1 set).
Open collector signal with 20 mA pull-down capability, referenced to logic return (LRTN).
AC fail will go high or open during power fail condition and will go low when input is within the operating
range.
A Power Fail warning will turn off the green AC OK LED.
Internal undervoltage and overvoltage supervision of Vo1.
Open collector signal with 20 mA pull-down capability, referenced to logic return (LRTN).
DC fail will go high or open if Vo1 is < 90% or > 110% of Vo1 set, measured in front of the ORing FETs.
A green LED on the front panel indicates normal operation.
The LED will flash if in parallel operation Vo1 is OK, but the unit is disabled.
I2C critical temperature warning: Indicates that the operating temperature has reached [Tshut-down – 10K]
I2C & OC overtemperature warning: Indicates if the unit is in overtemperature shutdown.
Open collector signal with 20 mA pull-down capability, referenced to logic return (LRTN).
The OC-output will go low 100 ms before an overtemperature condition shuts down the unit.
An amber LED on the front panel indicates overtemperature or fan fail.
Monitors the voltage Vo1 at the output connector.
Accuracy ± 0.45 V over setting range, temperature and load.
Monitors the output current Io1 : Accuracy ± 0.4A over the load range.
Output voltage trimming Vo1: ± 8 % of Vo set
Setting accuracy over I2C: ± 50mV at Vo nom, ± 150 mV over setting range
Two fan speed levels automatically set depending on the internal temperature.
The fan speed can be set to full speed or automatic control.
Indicates if the fans are operating or have failed.
Overcurrent signal which can be used for synchronous startup of units in parallel or to recover from an
overload condition. (See application note).
Detailed I2C information is available from the model’s I2C Manual found on the Bel Power Solutions web site.
Provided over the I2C interface and as an open collector signal on the output connector (OC).
PARAMETER
Altitude
Relative Humidity, Non-Condensing
CONDITIONS / DESCRIPTION
Operating
Non-Operating
Operating
MIN
Storage
Temperature Coefficient
0 °C to 70 °C (after 15 min warm-up)
Shock
IEC/EN 60068-2-27, 11 ms
IEC/EN 60068-2-6
2-8 Hz
8-200 Hz
200-500 Hz
10-2000 Hz
Calculated per Bellcore (SR-332, Issue 1):
GB 25 °C
GB 25 °C (FNP1500-12G)
Demonstrated
Sinusoidal Vibration
Random Vibration
MTBF
NOM
10
MAX
10 k
40 k
90
UNIT
ASL Ft.
ASL Ft.
% RH
5
95
% RH
0.02
%/K
40
gpk
7.5
2
4
6.15
230
TBD
250
mil
gpk
gpk
grms
kh
kh
kh
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Maximum electric strength testing is performed in the factory according to EN 550116, IEC/EN 60950, and UL 60950.
Input-to-output electric strength tests should not be repeated in the field. Bel Power Solutions will not honor any warranty
claims resulting from electric strength field tests.
PARAMETER
Agency Approvals
Insulation Safety Rating
Electric Strength Test Voltage
1
CONDITIONS / DESCRIPTION
UL60950, (UL) CSA 60950 (cUL),
EN 60950(TÜV), CE Mark for LVD
Input to case
Input to output
Output to case
Input to case
Input to output
Output to case
Output 1 to output 2
MIN
NOM
MAX
UNIT
Basic
Reinforced
Functional
2121
4242 1
500
100
VDC
Subassemblies are pre-tested with 4.2 kVDC in accordance with EN50116 and IEC/EN60950.
PARAMETER
DESCRIPTION
Electrostatic Discharge
IEC/EN 61000-4-2, level 4
Electromagnetic Field
IEC/EN 61000-4-3, level 3
Performance criterion A
Electrical Fast Transients/Burst
IEC/EN 61000-4-4, level 3
Performance criterion B
Surge
IEC/EN 61000-4-5, level 3
Performance criterion B
Voltage Dips and Interruptions
IEC/EN 61000-4-11
RF Conducted Immunity
IEC/EN 61000-4-6
Emissions Conducted
CISPR 22/EN 55022/EN 61204
Performance criterion B or better
10 VAC, AM 80 %, 1 kHz
Performance criterion A
Class B
Emissions Radiated
CISPR 22/EN 55022/EN 61204
Class A
Harmonics
IEC/EN 61000-3-2
Class B
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
Pass
Voltage Sag
SEMI F47-0200 (High Line 230V)
Pass
OUTPUT CONNECTOR
DESCRIPTION
PIN
LOCATION
Overtemperature / Fan Fail
U1
AC Fail / Power down warning
U2
Power Supply Present
U3
DC Fail / Output voltage fault
U4
Internal ground
U5
ADDR0, I2C address bus
T1
ADDR1, I2C address bus
T2
ADDR2, I2C address bus
T3
ADDR3, I2C address bus
T4
ADDR4, I2C address bus
T5
CRITERION
Performance criterion B
TYPE
OC-output, protected by 16 V Zener diode and a
10 Ω resistor in series, referenced to logic GND
OC-output, protected by 16 V Zener diode and a
10 Ω resistor in series, referenced to logic GND
Resistor (1 kΩ) connected to logic GND
OC-output, protected by 16 V Zener diode and a
10 Ω resistor in series, referenced to logic GND
Internal ground (Vo1– line before the output filter).
Do not connect the internal grounds in systems
with several units.
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
LOW LEVEL
HIGH LEVEL
< 0.4 V @ 20 mA
Pull up
< 0.4 V @ 20 mA
Pull up
Open
Pull up
< 0.4 V @ 20 mA
Pull up
VMAX
IMAX
15 V
20 mA
15 V
20 mA
10 V
10 mA
15 V
20 mA
Switch closed
Switch open
Switch closed
Switch open
Switch closed
Switch open
Switch closed
Switch open
Switch closed
Switch open
5V
5V
5V
5V
5V
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
DATA, I2C data line
S1
CLOCK, I2C clock line
S2
Vo2 + output
S3
Vo2 – output
S4
Logic ground
S5
Output inhibit
R1
V sense +
R2
V sense -
R3
12V model
I2C compatible signal
referenced to logic GND
I2C compatible signal
referenced to logic GND
Auxiliary power pin, insulated from main output
PS active when pulled low (DC-DC stage off when
left open) Referenced to logic GND
Open or connected to Vo1+ at the load
(Internally connected to Vo1+ over 100 Ω)
Open or connected to Vo1- at the load
(Internally connected to Vo1- over 100 Ω)
Open or connected over resistor to internal ground.
Do not connect the margin pins in
systems with several units.
Open or connected to internal ground
(+8 % Vo1) or V sense+ (-8 % Vo1)
Do not connect the margin pins in
systems with several units.
Open or connected to synch startup circuit,
referenced to Vo1 - at the output connector
Open or connected to synch startup circuit,
referenced to Vo1 - at the output connector
Output margin
R4
12V model
Synch. startup
48V models
R5
Vo1 + output
12V model
Vo1 – output
12V model
R5
P2, P4, P6,
P8, P10, P12
P1, P3, P5,
P7, P9, P11
Vo1 + output
48V models
Vo1 – output
48V models
P1, P3, P5
Main output – pins
Power Supply is inhibited
Input AC is low
Input AC is low or missing
10 V
3.5 mA
dU < 3 Vpp
30 mA
dU < 3 Vpp
30 mA
3 VDC
60 VDC
12V
3mA
12V
2mA
Main output – pins
Main output + pins
Normal Operation
< 0.8 V
> 2.0 V
Main output + pins
P2, P4, P6
CONDITION
5 V or 3.3 V logic
Auxiliary ground pin, insulated from main output
Internally connected over 10 Ω to Auxiliary GND.
Wire separately form Auxiliary - and main output
GND to minimize noise on signals and I2C.
Leave open if not used.
R4
48V models
5 V or 3.3 V logic
POWER FAIL
(AC OK)
Green
OUTPUT GOOD
(DC OK)
Green
FAN FAIL AND
OVER - TEMPERATURE
OFF
Green
OFF
Amber
OFF
OFF
Amber
OFF
OFF
Amber/OFF
Over-temperature
Green
OFF
Amber
Output overload (In regulation)
Green
Green
OFF
Output Overloaded (Out of Regulation)
Green
OFF
OFF
Fan Fault (No overtemperature shutdown)
Green
Green
Amber
Fan Fault (With overtemperature shutdown)
Green
OFF
Amber
OFF
OFF
OFF/ Amber
Power Supply Failed
AC OK
DC OK
Fan fail / OT
Enable
Switch
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Mechanical Data (H x W x D):
5.6” (141.2mm) x 1.6” (40.5mm) x 11” (279.4mm)
FNP1500/1800 12V Model Output Connector Descriptions
Rear View
Female Connector: FCI (51732-026 LF)
Mates with:
90° output connector type:
180° output connector type:
Part No. FCI (manufacturer): 51762-11202000AA LF
Part No. FCI (manufacturer): 51742-11202000AA LF
Locate information on availability of FCI connectors at http://www.stkcheck.com/evs/fcielectronics/fcisearch.asp
Connector drawings available at: http://portal.fciconnect.com/portal/page/portal/FcicntPublic/DocSrchCustDraw
IEC AC power cord with C19 connector VDE 16A: Interpower Components Ltd. 70009110250
IEC AC power cord with C19 connector UL 20A: Interpower Components Ltd. 70025110250
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Mechanical Data (H x W x D):
5.6” (141.2mm) x 1.6” (40.5mm) x 11” (279.4mm)
FNP1500/1800 48V Model Output Connector Descriptions
Rear View
Female Connector: FCI (51732-020 LF)
Mates with:
90° output connector type:
180° output connector type:
Part No. FCI (manufacturer): 51762-10602000AA LF;
Bel Power Solutions Part No.: ZES258-G
Part No. FCI (manufacturer): 51742-10602000AA LF
Locate information on availability of FCI connectors at http://www.stkcheck.com/evs/fcielectronics/fcisearch.asp
Connector drawings available at: http://portal.fciconnect.com/portal/page/portal/FcicntPublic/DocSrchCustDraw
IEC AC power cord with C19 connector VDE 16A: Interpower Components Ltd. 70009110250
IEC AC power cord with C19 connector UL 20A: Interpower Components Ltd. 70025110250
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
For parallel use in minimal configuration systems, only the inhibit pins must be shorted to logic GND. All other pins can be
left open. The power supplies will share the output current automatically (droop current share).
For parallel applications without I2C bus, but the use of all other features, it is recommended to connect all logic GND’s on a
backplane together, to connect all Vo2 -, all V o2 + and to leave the internal GND’s open.
The sense wires can be left open or connected to a common load point, the synch-start pin can be left open or connected to
a synch-start circuit, the inhibit pins can be connected together or used individually. All I2C signals (T1-T5, S1, and S2) can
be left open.
Use of a small foil capacitor > 3µF directly at the power outputs of each unit is recommended in order to prevent voltage
drops at the hot plug. For additional information on paralleling see the following Rack (Power Shelf) section.
To achieve best cooling results sufficient airflow through the unit must be ensured. Do not block or obstruct the airflow at
the rear of the unit by placing large components directly at the output connector.
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Each rack (power shelf) is 1U high with backplane and designed for up to three front-end models in parallel or in n+1 operation.
Each power shelf has:
 Massive copper bus bars for low-loss current distribution.
 Output terminals with two M4-screws on each power tab.
 Two fast-on contacts for system earthing.
 Address coding over five pole DIP switch on each unit, 37-pin D-Sub connector with I2C-lines, monitoring signals and
support functions.
 Provides a start-up synchronization circuit and EMV filters.
FNR-3-12G and FNR-3-48G Power Shelf Front View
Overall Mechanical Dimensions (W x H x D): 17.7” (449.6 mm) x 1.7” (43.1 mm) x 13” (330.2 mm)
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
A
B
C
D
E
F
G
H
I
LOCATION
DESCRIPTION
A
5-Bit DIP switch for I2C addressing of PSU 1
B
Earth connection
C
Earth connection
D
Earth connection
E
Output 1 minus
F
Output 1 plus
G
5-Bit DIP switch for I2C addressing of PSU 2
H
37-pin SUB-D connector, controlling and auxiliary power (output 2)
I
5-Bit DIP switch for I2C addressing of PSU 3
PIN
LOCATION
TYPE
Overtemperature / Fan Fail PSU1
1
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
Power Supply Present PSU 1
2
Resistor (1 kΩ) connected to logic GND
Power Supply Present PSU 2
3
Resistor (1 kΩ) connected to logic GND
Open
4
Overtemperature / Fan Fail PSU 3
5
AC Fail / Power down warning PSU 3
6
Power Supply Present PSU 3
7
DC Fail / Output voltage fault PSU 3
8
Overtemperature / Fan Fail PSU 2
9
Synch._Start_A
10
Open
11
OUTPUT CONNECTOR DESCRIPTION
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
Resistor (1 kΩ) connected to logic GND
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
Sync_start_A , Active high
The signals of several racks can be connected
together in such a way that all supplies will be
inhibited until the last supply has recovered from its
overcurrent condition, referenced to logic GND
LOW LEVEL
HIGH LEVEL
<0.4 V @ 20 mA
Pull up
Open
Pull up
Open
Pull up
V MAX
I MAX
15 V
20 mA
10 V
10 mA
10 V
10 mA
<0.4 V @ 20 mA
Pull up
<0.4 V @ 20 mA
Pull up
Open
Pull up
<0.4 V @ 20 mA
Pull up
<0.4 V @ 20 mA
Pull up
15 V
20 mA
15 V
20 mA
10 V
10 mA
15 V
20 mA
15 V
20 mA
<7V off
< 9V
15V
10mA
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Output inhibit
PSU 1-3
12
V sense +
13
V sense -
14
Open
15
NC
16
NC
17
NC
18
NC
19
AC Fail / Power-down warning PSU 1
20
DC Fail / Output voltage fault PSU 1
21
AC Fail / Power-down warning PSU 2
22
DC Fail / Output voltage fault PSU 2
23
DATA, I2C data line
24
CLOCK, I2C clock line
25
Auxiliary power +12 V
(Output 2)
Auxiliary power ground
(Output 2)
26
27
Logic Gnd
28
Output margin PSU 1
29
Output margin PSU 2
30
Output margin PSU 3
31
NC
32
NC
33
NC
34
NC
35
NC
36
NC
37
Active low (DC-DC stage off when pin is open or on
high potential)
Referenced to logic GND
Open or connected to Vo1+ at the load
Internally (PSU) connected to Vo1+ over 100 Ω
Open or connected to Vo1- at the load
Internally (PSU) connected to Vo1- over 100 Ω
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
OC-output, protected by 16 V Zener diode
and a 10 Ω resistor in series, referenced to logic GND
I2C compatible signal
referenced to logic GND
I2C compatible signal
referenced to logic GND
<0.8 V
>2.0 V
10 V
3.5 mA
dU < 3 Vpp
30 mA
dU < 3 Vpp
30 mA
<0.4 V @ 20 mA
Pull up
<0.4 V @ 20 mA
Pull up
<0.4 V @ 20 mA
Pull up
<0.4 V @ 20 mA
Pull up
15 V
20 mA
15 V
20 mA
15 V
20 mA
15 V
20 mA
5 V or 3.3 V logic
5 V or 3.3 V logic
Vo2+ Aux output, insulated from main output
Vo2- Aux output, insulated from main output
Internally connected over 10 Ω to Vo2-, Auxiliary
GND. Wire separately from auxiliary and main output
GND to minimize noise and avoid voltage drops on
signal- and I2C return. Leave open if not used.
Open or connected to V senseV sense- (+8 % Vo1) or V sense+ (-8 % Vo1)
Open or connected to V senseV sense- (+8 % Vo1) or V sense+ (-8 % Vo1)
Open or connected to V senseV sense- (+8 % Vo1) or V sense+ (-8 % Vo1)
60V
60V
60V
Because of hiccup overcurrent protection, when a supply reaches an overcurrent limit, the output voltage will immediately
turn OFF and after a delay turn ON again. In parallel use, all power supplies have to start synchronized because of the
internal hiccup behavior. Otherwise, the supply which has reached overcurrent first will go to hiccup; this will overload the
other supplies, which then will also go to hiccup. When the first supply has recovered from hiccup (hiccup dead time), the
others remain in hiccup. This will immediately drive the first one into hiccup once again. This means that without a start-up
circuit, a system with several power supplies can never recover from an overload condition or start-up into full load.
The following additional circuit, required to reach synchronized startup, is already implemented inside the
FNR-3-12G and FNR-3-48G shelves.
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
The following connection between the shelves is required to achieve a parallel operation. The synch-start circuits inside the
shelves inhibit all power supplies until the last one has recovered from its overcurrent condition and then synchronize the
restart of the outputs.
DESCRIPTION
Auxiliary power +12 V
(Output 2)
Logic ground
Output inhibit_A
PSU 1-3
Synch. Startup 1
PSU 1-3
PIN
LOCATION, DEFINITION
26
LOW LEVEL
HIGH LEVEL
V MAX
I MAX
10 V
3.5 mA
Vo2+, Aux output, insulated from main output
28
Logic_GND ,Internally connected over 10 Ω to
Vo2-, ( Auxiliary power ground (Output 2))
12
Inhibit_A ,Active low (DC-DC stage off)
Referenced to Logic_GND
<0.8 V
>2.0 V
The synch_start pin is connected to the
overcurrent signal of the PSU1-3. In the case of
an overcurrent shutdown, this signal goes high.
Referenced to Vo1Sync_start_A , Active high
The signals of several racks can be connected
together in such a way that all supplies will be
inhibited until the last supply has recovered
from its
overcurrent condition.
Referenced to Logic_GND
<7V off
> 9V
R5
(at PSU)
Synch. Startup_A
Rack FNR-3-12G &
Rack FNR-3-48G 1-N
Pin on the D-Sub connector on the
backplane
TYPE
10
15V
10mA
NOTE: The Sync-Start pins can be wired together only if the power supplies are connected with a minimal voltage drop on power ground
as achieved on a backplane with massive copper bus bars. If there is a less ideal connection, it is recommended to use an opto-coupler for
each unit (IC1, D3, D2).
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Center Angular Brackets are set in the middle for shelf mounting:
Center Angular Bracket sets can be ordered: Bel Power Solutions part no.: HZZ01222
Note: Each Center Angular Bracket set contains 2 brackets and 8 screws.
Filler for covering empty shelf slots:
Filler can be ordered: Bel Power Solutions part no.: XAK.00043.0
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
Plastic cover set for the bus bars:
Plastic cover set can be ordered: Bel Power Solutions part no.: XEB.00031.0
Note1: Available upon special request.
Note2: Each plastic cover set contains 2 pieces.
The handle has been designed to allow easy plug-in and -out in a rack system. The handle (lever) fits into a counter piece
(fulcrum) which is fixed to the bottom of the rack. During the plug, the fulcrum holds the unit down and guides it towards the
output connector. The Bel Power Solutions part number of the fulcrum and its associated mounting accessories is:
HZZ01223.
Individual fulcrum sets can be also ordered: Bel Power Solutions part no.: HZZ01223.
Note: Each HZZ01223 set contain 2 fulcrums, 2 supports, and mounting accessories.
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
FNP1500/FNP1800
I2C <to>USB
Interface
I2C Management Software: All FNP front-ends can be controlled via Bel Power Solutions GUI-driven I2C Management
software and an I2C-to-USB interface (P/N HZZ02002G). An I2C Programming Manual describes the complete range of
parameters that can be programmed to the FNP1500/1800 front-ends. This manual is available by searching on "FNP1500"
at www.belpowersolutions.com.
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending
on the date manufactured. Specifications are subject to change without notice.
866.513.2839
[email protected]
© 2015 Bel Power Solutions, Inc.
BCD.00247_AB
Similar pages