ETC2 FAA01DM24 Timers delay on operate Datasheet

Timers
Delay on Operate
Types FAA01, FAA08
•
•
•
•
•
•
•
•
•
•
Time range 0.05 s to 300 h
Knob selection of time range
Knob adjustable time setting
Knob selection of operating mode (4 functions):
A
- delay on operate
B2
- symmetrical recycler ON first
E
- interval
J
- one shot
Automatic start
Repeatability: ±0.3% on full scale
Output: 5 A DPDT relay
48 x 48 mm housing for front panel mounting
8 or 11 pin sockets
LED indication for relay status and power supply ON
Product Description
Ordering Key
Delay on operate timer with
4 functions and selectable
time ranges from 0.05 seconds to 300 hours.
Housing
Function
Type
Item number
Output
Power supply
Housing 48 x 48 mm for
front panel mounting and on
8-pin or 11-pin socket.
FAA 01 D M24
Type Selection
Mounting
Output
Plug
Supply: 100 to 240 VAC
Front or socket
Front or socket
DPDT
DPDT
11-pin
8-pin
FAA01DM24
FAA08DM24
Time Specifications
Output Specifications
Time ranges
Selectable by front knob
Output
Output insulation resistance
Contact Ratings (AgCdO12)
Resistive loads
AC 1
Mechanical life
Electrical life
Time unit
Full scale
setting
sec
min
hrs
10h
1.2
0.05 to 1.2
0.5 to 12
3
0.125 to 3
1.25 to 3
12
0.5 to 12
5 to 120
30
1.25 to 30
12.5 to 300
Repeatability
Setting accuracy
Voltage drift
Temperature drift
Reset
Power supply interruption
Pulse width
±0.3% on full scale
(±10 ms max in the range
of 1.2 s)
±5% on full scale ±50 ms
±0.5% on full scale
(±10 ms max in the range of
1.2 s)
±2% on full scale
(±10 ms in the range
of 1.2 s)
>100 ms
>50 ms
Operating frequency
Supply Specifications
Power Supply
Rated operational voltage
throuhgt terminals:
(FAA01DM24)
2, 10
(FAA08DM24)
2, 7
Power consumption
Rated operational power
Specifications are subject to change without notice (26.07.05)
DPDT relay
> 100 MΩ (at 500 VDC)
µ
5 A @ 250 VAC / 30 VDC
≥ 1 x 107 operations
≥ 1 x 105 operations
(5 A at 250 VAC, cos ϕ = 1,
1.8 x 103 operations/h)
< 1800 operations/h
Overvoltage cat II
(IEC 60947-1)
100 to 240 VAC +10%-15%
50 / 60 Hz
100 to 240 VAC +10%-15%
50 / 60 Hz
10VA @ 240 VAC, (50 Hz)
1
FAA01, FAA08
General Specifications
Function and Time Setting
Indication for
Power supply On
Upper right knob:
Setting of function
A - delay on operate
B2 - simmetrical recycler
E - interval
J - one shot
Output ON
Environment
Degree of protection
Operating temperature
Ambient humidity
Housing dimesions
Weight
CE marking
EMC
Immunity
Emission
LED, green
(flashing when timing)
LED, red
IP 40
(front panel)
-10 to +55 °C (14 to 131 °F)
35 to 85% RH
48 x 48 mm
Approx. 95 g
Yes
Electromagnetic Compatibillity
According to EN 61000-6-1
According to EN 61000-6-3
Lower right knob:
Time unit selector
sec (seconds)
min (minuts)
hrs (hours)
10h (10 hours)
Lower left knob:
Time range selector
1.2, 3, 12 and 30
Centre knob:
Time setting on relative
scale
Mode of Operation
Function A
Delay on operate
The set delay period begins
as soon as the power supply
is connected. At the end of
the set delay the relay operates and doesn’t release
until the power supply is
interrupted for at least 100
ms.
Function B2
Symmetrical recycler
(ON first)
The relay operates and the
time period start as soon as
the power is applied. At the
end of the first set time period, the relay releases. At the
end of the second time period (equal to the first), the
relay operates again. This
sequence continues with
equal ON- and OFF- time
periods until the power supply is interrupted for at least
100 ms.
Function E
Interval
The relay operates and the
time period begins as soon
as the power is applied. The
relay releases at the end of
the time period or when the
power supply is disconnected for at least 100 ms.
Function J
One shot
The time period begins as
soon as the power supply is
connected and at the end of
this period the relay operates
for 1s.
Range and operation mode selection
Power indicator (green)
(Flashes when timer operates;
on when timer stops operating)
Operating mode display window
Operating mode selector
(function A, B2, E, J)
Output indicator (red)
(Lit when output is ON)
Scale range display windows
Time range selector
(1.2, 3, 12 and 30 at full scale)
Time unit display window
Time unit selector (sec, min, hrs, 10h)
Time setting knob (set time)
2
Specifications are subject to change without notice (26.07.05)
FAA01, FAA08
Wiring Diagrams
FAA01
FAA08
L(+)
µ
m
4
2
10
L(+)
mµ
3
8
m
µ
4
2
9
7
11
1
m
µ
5
3
6
8
1
N(-)
N(-)
Operating Diagrams
Function B2 - Symmetrical Recycler (ON first)
Function A - Delay ON operate
Power supply
Power supply
T
Relay
T
Relay
LED “POWER”
T
T
T
T
T
LED “POWER”
Function E - Interval
Function J - One Shot
Power supply
Power supply
1s±0.6s
T
T
Relay
Relay
LED “POWER”
LED “POWER”
T
1s±0.6s
T
Dimensions
FAA01 - FAA08
81,6
81.6
60,2
68.2
15
15
9
6
39
39
48
48
48
48
Specifications are subject to change without notice (26.07.05)