Delta DRB-24V020ABA Full corrosion resistant aluminium chassi Datasheet

TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Highlights & Features
–
–
–
–
–
–
–
–
–
–
–
Full corrosion resistant Aluminium chassis
Long minimum buffering time of 250ms @ 24V/20A
Can connect in parallel to increase buffering time
Charging time of < 30 seconds
Conformal coating on PCBA to protect against chemical and
dust pollutants
Hazardous Locations approval to ATEX and Class I, Div 2
(DRB-24V020ABA)
IP20 Compliant
Overvoltage / Overcurrent / Short Circuit Protections
Meets worldwide safety requirements
RoHS Directive 2011/65/EU Compliant
Reliable design, with expected life of 10 years
Safety Standards
CB Certified for worldwide use
Model Number:
DRB-24V020AB□
Unit Weight:
0.76 kg
Dimensions (L x W x D): 121 x 70 x 120.1 mm
General Description
Delta CliQ II Buffer Module offers the most widely used output voltage of 24V and one of the longest buffering time of 0.25 sec (min) at
20A in wide input range from 22.8Vdc to 28.8Vdc. The Buffer Module utilizes maintenance-free electrolytic capacitors to store energy,
thus eliminates the need of periodic replacement as compared to costlier batteries which also have shorter functional life span. Delta CliQ
II Buffer Module comes with comprehensive protection features like overcurrent/overload, overvoltage and short circuit protection. Delta
CliQ II series of products is IP20 compliant with full corrosion resistant Aluminium chassis and conformal coating on the PCBAs to provide
protection against dust and chemical pollutants.
Model Information
CliQ II Buffer Module
Model Number
Input Voltage Range
Output Voltage
Output Current
DRB-24V020AB□
22.8-28.8Vdc
24Vdc
20A
Model Numbering
1
DR
B–
24V
020A
B
DIN Rail
Buffer Module
Output Voltage
Output Current
CliQ II Series
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
□
A - Metal Case,
with Class I, Div 2
N - Metal Case,
without Class I, Div 2
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
24Vdc
Input Voltage Range
22.8-28.8Vdc
Maximum Input Voltage
35Vdc
Input Current
Charging Moded < 0.6A
Discharging Moded 20A Max
Input Power (Standby Mode)
2.5W Average
Maximum Signal Input (Inhibit)
35V / 10mA
Max Inrush Current
< 20A
Charging Time
< 30sec
Output Ratings / Characteristics
Nominal Output Voltage
24Vdc typ. (depends on Vin)
Output Voltage Adjustment Range
22-28Vdc
Switch = “Fix 22V” Buffering starts if terminal voltage falls below 22V
Maximum Output Voltage
Factory Setting, Switch = “Vin-1V” Buffering starts if terminal voltage is decreased by > 1V
35Vdc
Output Current
20A Max
Buffering Time
250ms Min @ 24V/20A Load,5sec Min @ 24V/1A Load
(Refer to Fig. 1)
35V / 10mA
Maximum Signal Output
Signals
Inhibit Signal (I) “Low” = Shuts down Buffer Module
Ready Signal (R) “High” = Buffer Module is fully charged or in Standby Mode
Buffering Signal (B) “High” = Buffer Module is discharging or in Buffering Mode
Supply Voltage (+VS) Common +VS, 35V Max
PARD (20MHz)
< 200mVpp @ 25°C during Buffering Mode
Parallel Connection
Yes
Series Connection
No
Protective Device
Transient Voltage Suppressor (TVS) for signals
Fig.1 Buffering Time (Typical Values at “ Vin – 1V” Mode)
Mechanical
2
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Case Cover
Aluminium
Dimensions (L x W x D)
121 x 70 x 120.1 mm
Unit Weight
0.76kg
LED Indicators
Green LED Off
Unit is discharged or Vin < 22Vdc
Green LED On
Unit is fully charged
Green LED Blinking Slowly (1Hz)
Green LED Blinking Quickly (10Hz)
Cooling System
Unit is charging
Unit is discharging
Convection
Terminal
Input / Output
Wire
Input / Output
AWG 12-10
Signal
AWG 24-10
Signal
Mounting Rail
M3 x 2 Pins (Rated 300V/30A)
M3 x 5 Pins (Rated 300V/30A)
Standard TS35 DIN Rail in accordance with EN60715
Environment
Surrounding Air Temperature
Operating
-25°C to +75°C
Storage
-25°C to +85°C
Component De-rating
Vin = 22.8-28.8Vdc, Max load
- Tambient = 50°C
- Tj < 85% of Tjmax
Operating Humidity
< 95% RH (Non-Condensing)
Operating Altitude
2,500 Meters
Shock Test (Non-Operating)
IEC60068-2-27, 30G (300m/S²) for a duration of 18ms
Vibration (Non-Operating)
IEC60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction
Pollution Degree
2
Protections
Overvoltage
32V +10%
Overload / Overcurrent
Short Circuit
Penetration Protection
30A Max
No Damage
> 3.5mm (eg. screws, small parts)
Reverse Polarity Protection
Yes
Degree of Protection
IP20
Protection Against Shock
Class I without PE* connection
*PE: Primary Earth
3
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Reliability Data
MTBF(at Vin-1V Mode)
> 800,000 hrs. as per Telcordia SR-332 at Standby
Mode (Buffer Module in Ready State)
10 years (Standby Mode @ 40°C)
Expected Cap Life Time
Safety Standards / Directives
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety (Information Technology Equipment)
SIQ to EN60950-1, UL/cUL recognized to UL60950-1,
CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01,
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
CSA to CSA C22.2 No. 213-M1987, ANSI / ISA
12.12.01:2007 (Class I, Division 2, Group A, B, C, D, T4)
EN60079-0:2009, EN60079-15:2010
(
II 3G Ex nA nC IIc T4 Gc)
Certificate No. ESP 12 ATEX 1 491 X
For IEC60079-0, IEC60079-15
II 3G ATEX 94/9/EC;
IECEX Test Report
CE
In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
Material and Parts
RoHS Directive 2011/65/EU Compliant
Galvanic Isolation
Input & Output to Ground
1.5KVac
Signal to Ground
1.5KVac
EMC
EMC / Emissions
CISPR22, EN55022, EN55011, FCC Title 47: Class B
Component Power Supply for General Use
EN61204-3
Immunity to
EN55024, EN61000-6-2
Level 4 Criteria A1)
Air Discharge: 15kV
Contact Discharge: 8kV
1)
Level 3 Criteria A
80MHz–1GHz, 10V/M with 1kHz tone / 80% modulation
Electrostatic Discharge
EN61000-4-2
Radiated Field
EN61000-4-3
Electrical Fast Transient / Burst
EN61000-4-4
Level 3 Criteria A1)
2kV
Surge
IEC6100-4-5
Level 3 Criteria A1)
2)
Common Mode : 2kV
3)
Differential Mode : 1kV
Conducted
EN61000-4-6
Level 3 Criteria A
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields
EN61000-4-8
Level 3 Criteria A1)
10A/Meter
1)
1)
Voltage Dips
EN61000-4-11
Level 3 Criteria A
Additional 100% dip; 1 cycle (20ms); No Damage
Low Energy Pulse Test (Ring Wave)
IEC61000-4-12
Level 3 Criteria A1)
2)
Common Mode : 2kV
3)
Differential Mode : 1kV
Note: Product intended to be used as Apparatus with AC-DC Power Supply, EMC compliance to be verified in correspondence to the connected units.
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
4
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Block Diagram
Device Description
1)
2)
3)
5
Input / Output terminal block connector
Signal terminal block connector
Select switch (operation mode)
4)
5)
LED display status
Universal mounting rail system
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Dimensions
L x W x D: 121 x 70 x 120.1 mm
Engineering Data
De-rating
Note
1.
2.
3.
4.
Fig. 2
6
De-rating for Vertical Mounting Orientation
> 70°C de-rate power by 5% / °C
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
Components may degrade, or be damaged,
when the buffer module is continuously used
outside the shaded region, refer to the graph
shown in Fig. 2.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 20mm with adjacent units
while the device is in operation.
Depending on the surrounding air temperature
and output load delivered by the buffer
module, the device housing can be very hot!
If the device has to be mounted in any other
orientation, please do not hesitate to contact
[email protected] for more details.
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Assembly & Installation
The buffer module can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed with input / output
terminal block at the top.
Each device is delivered ready to install.
Mounting
Dismounting
Fig. 3.1 Mounting
Fig. 3.2 Dismounting
Snap on the DIN rail as shown in Fig. 3.1:
1. Tilt the unit upwards and insert it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom front side for locking.
4. Shake the unit slightly to ensure that it is secured.
To uninstall, pull or slide down the latch with screw driver as
shown in Fig 3.2. Then slide the unit in the opposite direction,
release the latch and pull out the unit from the rail.
Safety Instructions
–
–
–
–
–
–
–
–
7
ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the unit. If mains are not turned
OFF, there is risk of explosion / severe damage.
To guarantee sufficient convection cooling, keep a distance of
50mm above and below the device as well as a lateral distance of
20mm to other units.
Note that the enclosure of the device can become very hot depending
on the surrounding air temperature and load of the power supply. Risk
of burns!
Only plug in and unplug connectors when power is turned off!
DO NOT insert any objects into the unit.
Hazardous voltages may be present for up to 5 minutes after the input
mains voltage is disconnected. Do not touch the unit during this time.
The power supplies unit must be installed in an IP54 enclosure.
The power supplies are built in units and must be installed in a cabinet
or room (condensation free environment and indoor location) that is
relatively free of conductive contaminants.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Functions
Buffering, Ready, and Inhibit Signal
Buffering Signal (B)
Maximum Signal Voltage
Maximum Signal Current
Isolation (Signal Port to Power Port)
Ready Signal (R)
“High” = Buffer Module is discharging or in Buffering
35Vdc
10mA
1.5KVac
“High” = Buffer Module is fully charged or in Standby Mode
Maximum Signal Voltage
35Vdc
Maximum Signal Current
10mA
Isolation (Signal Port to Power Port)
Inhibit Signal (I)
1.5KVac
“Low” = Shuts down Buffer Module
Maximum Signal Voltage
35Vdc
Maximum Signal Current
10mA
Shut-down Threshold
6Vdc Min / 10Vdc Max
Isolation (Signal Port to Power Port)
1.5KVac
Operating Diagram
Wiring Schematics
Typical Application Notes can be found on Page 9.
8
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Typical Application Notes
Fig. 4.1 General Connection/Wiring Diagram
Fig. 4.2 Paralleling of Buffer Units
Fig. 4.3 Decoupling of Buffered Branches
Fig. 4.4 General Signals Wiring
Fig. 4.5 Signals Supplied from an External Voltage
Fig. 4.6 Connection Diagram with Redundant Operation
9
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Connectable Power Supplies
The buffer module is recommended to be connected with the following power supplies:
CliQ Series
CliQ II Series
- DRP024V060W1AZ
- DRP024V060W1AA
- DRP024V120W1AA
- DRP024V240W1AA
- DRP024V480W1AA
- DRP024V060W3AA
- DRP024V120W3AA
- DRP024V240W3AA
- DRP024V480W3AA
– DRP024V060W1BA
– DRP024V120W1BA
– DRP024V240W1BA
– DRP024V480W1BA
More new products can be found at www.DeltaPSU.com
Inrush Current
Inrush current is the peak, instantaneous, input current measured
and occurs when input voltage is first applied. For DC input
voltage the maximum peak value of inrush will occur during the
first applied DC voltage.
Overload & Overcurrent Protections
When the output current exceeds 120% of IO (Max load) buffer
module will shut down and latch. Normal operation of buffer
module can be resumed upon removal of fault and power supply
input is recycled (ON/OFF) or input to buffer module is recycled.
Short Circuit Protection
Overvoltage Protection
The buffer module’s overvoltage protection will be activated when
DC input to the module exceeds the maximum specifed input
voltage. The overvoltage limits are same as power supply limits,
32V ± 10%. Buffer module will shut down and latch during
overvoltage mode, and will return to normal operation upon
removal of fault and power supply input is recycled (ON/OFF) or
input to buffer module is recycled.
10
Buffer module is protected by short circuit during buffering mode,
in the event of short circuit the module will shut down and latch.
Operation can be resumed upon removal of fault and power
supply input is recycled (ON/OFF) or input to buffer module is
recycled.
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)
TECHNICAL DATASHEET
CliQ II Buffer Module
24V 20A / DRB-24V020AB□
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EC limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
electrical and electronic equipment”.
This product conforms to this standard.
Conformal Coating
The Protective Coating Technology
Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including
under device, and prevents leakage. The conformal coating dipping can be applied to PCBs or circuit board.
The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants
such as salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem
especially in highly conversing atmosphere.
11
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (October 2013, Rev. 01)