B73 & Series 75 Installation and Operating Manual Sealed External Cage Liquid Level Switches Read this Manual Before Installing This manual provides information on the B73 and Series 75 Liquid Level Switches. It is important that all instructions are read carefully and followed in sequence. Detailed instructions are included in the Installation section of this manual. Conventions Used in this Manual Certain conventions are used in this manual to convey specific types of information. General technical material, support data, and safety information are presented in narrative form. The following styles are used for notes, cautions, and warnings. Notes Notes contain information that augments or clarifies an operating step. Notes do not normally contain actions. They follow the procedural steps to which they refer. Cautions Cautions alert the technician to special conditions that could injure personnel, damage equipment, or reduce a component’s mechanical integrity. Cautions are also used to alert the technician to unsafe practices or the need for special protective equipment or specific materials. In this manual, a caution indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. Warnings Warnings identify potentially dangerous situations or serious hazards. In this manual, a warning indicates an imminently hazardous situation which, if not avoided, could result in serious injury or death. WARNING! Explosion hazard. Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. Low Voltage Directive For use in Installation Category II, Pollution Degree 2. If equipment is used in a manner not specified by manufacturer, protection provided by equipment may be impaired. Notice of Copyright and Limitations Magnetrol and Magnetrol logotype are registered trademarks of Magnetrol International. Copyright © 2010 Magnetrol International, Incorporated. All rights reserved. Performance specifications are effective with date of issue and are subject to change without notice. Magnetrol reserves the right to make changes to the products described in this manual at any time without notice. Magnetrol makes no warranty with respect to the accuracy of the information in this manual. Warranty All Magnetrol mechanical level and flow controls are warranted free of defects in materials or workmanship for five full years from the date of original factory shipment. If returned within the warranty period; and, upon factory inspection of the control, the cause of the claim is determined to be covered under the warranty; then, Magnetrol will repair or replace the control at no cost to the purchaser (or owner) other than transportation. Magnetrol shall not be liable for misapplication, labor claims, direct or consequential damage or expense arising from the installation or use of equipment. There are no other warranties expressed or implied, except special written warranties covering some Magnetrol products. Quality Assurance The quality assurance system in place at Magnetrol guarantees the highest level of quality throughout the company. Magnetrol is committed to providing full customer satisfaction both in quality products and quality service. Magnetrol’s quality assurance system is registered to ISO 9001 affirming its commitment to known international quality standards providing the strongest assurance of product/service quality available. 46-620 B73 & Series 75 Liquid Level Switches B73 & Series 75 Liquid Level Switches Table of Contents 1.0 Installation 1.1 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.2 Critical Alarm Function . . . . . . . . . . . . . . . . .4 1.3 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1.5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 2.0 Reference Information 2.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . .7 2.2 Theory of Operation . . . . . . . . . . . . . . . . . . .7 2.3 Operating Cycle . . . . . . . . . . . . . . . . . . . . . . .7 2.4 Switch Differential Adjustment . . . . . . . . . . .8 2.4.1 Low Level Controls . . . . . . . . . . . . . . .8 2.4.2 High Level Controls . . . . . . . . . . . . . .10 2.5 Tandem Float Models . . . . . . . . . . . . . . . . . .10 2.5.1 Installation, Preventive Maintenance, and Troubleshooting . . . . . . . . . . . . .10 2.5.2 Differential Adjustment . . . . . . . . . . .11 3.0 Troubleshooting 3.1 Check Switch Mechanism . . . . . . . . . . . . . .11 3.2 Check Sensing Unit . . . . . . . . . . . . . . . . . . .12 4.0 Preventive Maintenance 4.1 What To Do . . . . . . . . . . . . . . . . . . . . . . . . .13 4.1.1 Keep Control Clean . . . . . . . . . . . . . .13 4.1.2 Inspect Switch Mechanisms, Terminals, and Connections Monthly . . . . . . . . .14 4.1.3 Inspect Entire Unit Periodically . . . . .14 4.2 What To Avoid . . . . . . . . . . . . . . . . . . . . . . .14 46-620 B73 & Series 75 Liquid Level Switches 5.0 Specifications 5.1 Agency Approvals . . . . . . . . . . . . . . . . . . . . .15 5.2 Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 6.0 Replacement Parts 6.1 Series 75 . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 6.1.1 Parts Identification . . . . . . . . . . . . . . .20 6.1.2 Switch and Housing Reference . . . . . .20 6.1.3 Series 75 with Material Code 1 . . . . .21 6.1.4 Series 75 with Material Code 2 . . . . .21 6.1.5 Series 75 with Material Code 3 or 4 . .21 6.2 Model B73 . . . . . . . . . . . . . . . . . . . . . . . . . .22 6.2.1 Parts Identification . . . . . . . . . . . . . . .22 6.2.2 Switch and Housing Reference . . . . . .22 6.2.3 Model B73 . . . . . . . . . . . . . . . . . . . . .22 6.3 Series 75 Tandem Float Units . . . . . . . . . . . .23 6.3.1 Parts Identification . . . . . . . . . . . . . . .23 6.3.2 Series 75 Tandem Float Units . . . . . . .23 6.3.3 Switch and Housing Reference . . . . . .23 7.0 Model Numbers 7.1 Model B73 . . . . . . . . . . . . . . . . . . . . . . . . . .24 7.2 Model Series 75 . . . . . . . . . . . . . . . . . . . . . .26 1.0 Installation Caution: If equipment is used in a manner not specified by manufacturer, protection provided by equipment may be impaired. 1.1 Unpacking Unpack the instrument carefully. Inspect all units for damage. Report any concealed damage to carrier within 24 hours. Check the contents of the packing slip and purchase order. Check and record the serial number for future reference when ordering parts. 1.2 Critical Alarm Function It is recommended that for critical alarm functions, an additional level switch be installed as a high–high or low–low level alarm for maximum protection. 1.3 Piping Figure 3 shows a typical piping installation of a Magnetrol B73 and Series 75 control to a pressure vessel. Level decals on control identify the actuation levels for a unit with a single switch at minimum specific gravity. See Section 5.2, Physical on page 18 for the actuation levels. Conduit outlet Pressure vessel Switch actuating level reference marks Shutoff valve Use pipe of sufficient strength to support the control. If necessary, provide a stand or hanger to help support its weight. All piping should be straight and free of low spots or pockets so that lower liquid line will drain towards the vessel and upper vapor line will drain toward the control. Shut-off valves are recommended for installation between the vessel and the control. If control is to be used with a low temperature liquid (one which will boil in the float chamber if outside heat is absorbed), the chamber and piping should be insulated. Such boiling in the chamber will cause false level indications. Caution: Do not insulate switch mechanism housing. Max. 12" Drain valve Figure 1 Piping Configuration 4 On controls equipped with pneumatic switch assemblies, consult bulletin on mechanism furnished for air (or gas) piping instructions. See Section 6.1.2, Switch and Housing Reference on page 20 for bulletin numbers for pneumatic switches. NOTE: D, E, and H75 models are designed for high level service only and utilize a pressure equalizing self-purging float and stem. Pressure in the chamber must be raised and lowered slowly to avoid potential float collapse. 46-620 B73 & Series 75 Liquid Level Switches 1.4 Mounting Caution: This instrument is intended for use in Installation Category II, Pollution Degree 2. Adjust piping as required to bring control to a vertical position. Magnetrol controls must be mounted within 3° of vertical in all directions. A three degree slant is noticeable by eye, but installation should be checked with a spirit level on top and/or sides of float chamber. Controls should be mounted as close to the vessel as possible. This will result in a more responsive and accurate level change in the control. Liquid in a long line may be cooler and more dense than liquid in the vessel causing lower level indication in the control than actual level in the vessel. Caution: Never insulate the switch housing of the level control. Installation and maintenance of tandem float models are accomplished in much the same manner as described for standard models. Additional consideration must be given to the piping arrangement to allow for alignment of the two switch actuating level marks on the float chamber with the desired levels in the vessel. Caution: Operation of all buoyancy type level devices should be done in such a way as to minimize the action of dynamic forces on the float or displacer sensing element. Good practice for reducing the likelihood of damage to the control is to equalize pressure across the device slowly. 1.5 Wiring Caution: Level controls are shipped from the factory with the enclosing tube tightened and the middle set screw, on the housing base, locked to the enclosing tube. Failure to loosen the set screw prior to repositioning the conduit connection may cause the enclosing tube to loosen, resulting in the possible leakage of the process liquid or vapor. B73 and Series 75 controls are shipped with the conduit entry of the switch housing placed 180° opposite to the tank configurations to simplify installation in most cases. If this configuration is appropriate to the installation, proceed to Step 4 to begin wiring the unit. If another configuration is desired, the switch housing can be easily rotated by first following Steps 1, 2, and 3. Screw Screw Set Screw Figure 2 Switch Housing 46-620 B73 & Series 75 Liquid Level Switches NOTE: A switch or circuit breaker shall be installed in close proximity to equipment and within easy reach of operator. It shall be marked as the disconnecting equipment. 1. Loosen set screw(s) at base of switch housing. Refer to Figure 2. 2. Switch housing may be rotated 360° to allow correct positioning of conduit outlet. 5 3. Tighten set screw(s) at base of switch housing. 4. Unscrew and remove switch housing cover. The threads have been lubricated to facilitate removal. NOTE: For supply connections, use wire with a minimum rating of +167° F (+75° C) as required by process conditions. Use a minimum of 14 AWG wire for power and ground field wires. NOTE: Housing must be grounded via protective ground screw in the base of the housing. Internal Circuit (Right) Switch Internal Circuit (Left) Switch 4 1 6 3 5 Close on high level 2 NOTE: On high temperature applications (above +250° F [+121° C] in float chamber), high temperature wire should be used between control and first junction box located in a cooler area. On non-hazardous applications, flexible conduit may be used between the control and the first junction box. Close on high level Load Load Load Load Common Common Close on low level Close on low level Line Line Figure 3 Wiring Diagram for all switches except Series HS & H1 5. The switch terminals are located next to the conduit outlet to facilitate wiring. Bring supply wires through conduit outlet. Route extra wire around enclosing tube under the baffle plate, and connect them to the proper terminals. Refer to the wiring diagram, Figure 3, or your switch bulletin for this information. NOTE: For models with Series HS or H1 switches with high temperature lead wire, the leads are routed out through the conduit opening by the factory. A suitable conduit box should be provided for the connection of the leads to the control wiring. 6. Dress wiring to ensure no interference or contact with movement of mechanism or replacement of switch housing cover. Caution: Observe all applicable electrical codes and proper wiring procedures. Caution: In hazardous areas, do not power the unit until the conduit is sealed and the enclosure cover is screwed down securely. 7. Replace housing cover. 8. If control has been furnished with an explosion proof or moisture proof (gasketed) switch housing, it must be sealed at the conduit outlet with a suitable compound or non-hardening sealant to prevent entrance of air. 9. Test switch action by varying liquid level in float chamber. NOTE: If switch mechanism fails to function properly, check vertical alignment of control housing and consult installation bulletin for additional wiring information on switch mechanism furnished. See Section 6.1.2, Switch and Housing Reference on page 20. 10. Check cover to base fit to be certain gasketed joint is tight. A positive seal is necessary to prevent infiltration of moisture laden air or corrosive gasses into switch housings. 6 46-620 B73 & Series 75 Liquid Level Switches 2.0 Reference Information 2.1 Description Magnetrol’s B73 and Series 75 level switches are float operated units suitable for use on clean liquid applications for level alarm, pump control and safety shutdown functions. Series 75 units are available with tandem floats for applications where widely spaced high and low switching are required by a single control. 2.2 Enclosing tube (non-magnetic) The design of float operated level switches is based upon the principle that a magnetic field will not be affected by non-magnetic materials such as 316 stainless steel. In this case, the float moves a magnetic attraction sleeve within a non-magnetic enclosing tube and actuates a magnetic switch mechanism. The enclosing tube provides a pressure seal to the chamber and therefore to the process. Switch Return spring Magnet Attraction sleeve Theory of Operation Swing in position HL 2.3 Operating Cycle As the liquid level rises in the chamber the float moves the magnetic attraction sleeve up within the enclosing tube and into the field of the switch mechanism magnet. Refer to Figure 4. As a result, the magnet is drawn in tightly to the enclosing tube causing the switch to trip, making or breaking an electrical circuit. As the liquid level falls, the float drops and moves the attraction sleeve out of the magnetic field, releasing the switch at a predetermined low level. Refer to Figure 5. The tension spring ensures the return of the switch in a snap action. Figure 4 Switch Tripped Swing out position LL Tandem float units incorporate two floats which operate independently. The lower float actuates the upper switch mechanism, and the upper float actuates the lower switch mechanism. The upper float is attached to the lower attraction sleeve by means of a hollow stem. The lower float attaches to the upper attraction sleeve with a solid stem, which extends upward through the upper float and stem assembly. Figure 5 Switch Released 46-620 B73 & Series 75 Liquid Level Switches 7 2.4 Switch Differential Adjustment The standard differential of Series 75 float models with one switch may be field adjusted. Adjustment may be necessary if a wider differential needs to be set to overcome switch chatter caused by the process. NOTE: This procedure may be applied to single switch models only. The differential, or the amount of level travel between switch-on and switch-off, may be adjusted by repositioning the lower jam nuts on the float stem. This adjustment is different for high level and low level controls. Refer to the appropriate section below for adjustment instructions. NOTE: Maximum differential adjustment is 1 inch. Caution: Differential adjustments should NOT be made in the field on tandem float models. Switch actuation levels have been set at the factory to meet customer specifications. Variations in actual conditions from design conditions, usually require special control modifications. Consult the factory or your local representative for assistance. 2.4.1 Low Level Controls Slight play (gap) Must be allowed (0.03" typical) Position of bottom jam nuts (normal factory setting) Replace in same position D 1.00 (25 mm) Maximum gap setting (applies to models having a single switch mechanism with a single magnet actuator only) Figure 6 Drop bottom jam nuts to increase gap setting (refer to above instructions) Figure 7 On low level controls the switch trips on the lower actuation point and resets on the higher actuation point. Widening the differential will allow the switch to trip on the original actuation point and reset at a later or higher point. The differential on low level controls may be adjusted by repositioning the lower jam nuts on the float stem. The standard factory setting is for a minimum amount of play (gap) between the top jam nuts and the attraction sleeve. Refer to Figure 6. 1. Determine what change in differential is necessary. NOTE: To widen the differential by one inch, the lower jam nuts must be set proportionately lower on the stem (i.e., in this example by 1 inch). 2. Make sure power source is turned off. 3. Unscrew and remove switch housing cover. 4. Disconnect power supply wires from switch mechanism. Pull wires out of conduit connection opening in housing base. Refer to Figure 8. 5a. Perform system shut-down procedures as required to relieve pressure from float chamber of control. Allow unit to cool. 8 46-620 B73 & Series 75 Liquid Level Switches 5b. Close shut-off valves (if so equipped) to isolate control from tank. Drain off liquid in float chamber. 5c. On installations without shut-off valves, relieve pressure from the tank. Drain liquid in tank to a level below the connections of the float chamber. NOTE: Level control, connections and pipe lines need not be removed from the tank. Switch housing cover Enclosing tube Refer to Figures 6 and 7 Conduit connection Housing base Enclosing tube nut Chamber Float Figure 8 6. Loosen enclosing tube nut with a 15⁄16" wrench. Unscrew enclosing tube counterclockwise (switch and housing base will rotate also), until it is free. Refer to Figure 8. 7. Lift enclosing tube, switch, and base off float chamber. Jam nuts and attraction sleeve are now accessible. 8. Measure the distance “D” from the top edge of the upper jam nuts to the top of the float stem. Refer to Figure 7. Record this measurement. 9. Loosen and remove upper jam nuts, guide washer and attraction sleeve. 10. Loosen and adjust lower jam nuts to the desired position. Tighten lower jam nuts securely. Refer to Figure 7. 11. Replace attraction sleeve on stem. 12. Replace upper jam nuts and guide washer on the stem in the position previously noted. Tighten upper jam nuts securely. Refer to Figure 7. NOTE: Use a new enclosing tube gasket when reassembling enclosing tube to the chamber. Make certain that all gasket surfaces are thoroughly cleaned to allow proper gasket seating. Coat enclosing tube threads with anti-seizing compound. 13. Replace enclosing tube, switch, and base on chamber. Screw tube clockwise until tightened to 75–100 foot-pounds of torque for a fiber gasket or 200–225 foot-pounds of torque for a spiral wound gasket. 14. Loosen the set screws at the base of the switch housing. Rotate switch housing to correct position and tighten set screws. Refer to Figure 2 on page 5. 15. Bring supply wires through conduit outlet. Follow steps 5 through 10 in Section 1.5, Wiring on page 5. 16. Test switch action by varying liquid level in float chamber. NOTE: If switch mechanism fails to function properly, check vertical alignment of control housing and consult installation bulletin on switch mechanism. If the unit still fails to function properly, consult the factory. 46-620 B73 & Series 75 Liquid Level Switches 9 2.4.2 High Level Controls On high level controls, the switch trips on the higher actuation point and resets on the lower actuation point. Caution: On high level controls, widening the differential requires raising the trip point a proportional amount. The reset point will remain the same. To widen the differential by raising the trip point, follow steps 1 through 16 in Section 2.4.1, Low Level Controls on pages 8–9. 2.5 Tandem Float Models Models with tandem floats are used on applications where it is advantageous to have two widely spaced high and low switching functions using a single control. The units incorporate two floats which operate independently, and are arranged so that the lower float actuates the upper switch mechanism, and the upper float actuates the lower switch mechanism. The upper float is attached to the lower attraction sleeve by means of a hollow stem. The lower float attaches to the upper attraction sleeve with a solid stem that extends upward through the upper float and stem assembly. 2.5.1 Installation, Preventive Maintenance, and Troubleshooting Installation and maintenance of tandem float models is accomplished in much the same manner as for standard models previously described. Some additional consideration must be given to the piping arrangement to allow for alignment of the two switch actuating level marks on the float chamber with the desired levels in the vessel. When troubleshooting the level sensing portion of the control, additional checks may be made of the following: 1. Inspect for binding of solid (lower) float stem within hollow (upper) float stem due to corrosion or possible damage incurred during shipment or previous maintenance. 2. Make certain that retaining (snap) rings, used to locate lower attraction sleeve, are locked in place. An extreme shock or hammer, such as during blow-down on a water column boiler control, may damage a ring causing it to snap out of its retaining groove in the hollow (upper) float stem. 10 46-620 B73 & Series 75 Liquid Level Switches 2.5.2 Differential Adjustment Caution: No differential adjustment should be made on tandem float models in the field. Switch actuation levels have been set at the factory to meet customer specifications. Variations in actual conditions, from design conditions, usually require special control modifications. 3.0 Troubleshooting Usually the first indication of improper operation is failure of the controlled equipment to function, i.e., pump will not start (or stop), signal lamps fail to light, etc. When these symptoms occur, whether at time of installation or during routine service thereafter, check the following potential external causes first: a. Fuses may be blown b. Reset button(s) may need resetting c. Power switch may be open d. Controlled equipment may be faulty e. Wiring leading to control may be defective If a thorough inspection of these possible conditions fails to locate the trouble, proceed next to a check of the control's switch mechanism. 3.1 Check Switch Mechanism 1. Pull disconnect switch or otherwise disconnect power to the control. 2. Remove switch housing cover. 3. Disconnect power wiring from switch assembly. 4. Swing magnet assembly in and out by hand to check carefully for any sign of binding. Assembly should require minimal force to move it through its full swing. 5. If binding exists, magnet may be rubbing enclosing tube. If magnet is rubbing, loosen magnet clamp screw and shift magnet position. Retighten magnet clamp screw. 6. If switch magnet assembly swings freely and mechanism still fails to actuate, check installation of control to be certain it is within the specified 3° of vertical. 7. Check the continuity of microswitch with ohmmeter. Replace immediately if defective. 8. If switch mechanism is operating satisfactorily, proceed to check sensing unit. NOTE: As a matter of good practice, spare switches should be kept on hand at all times. 46-620 B73 & Series 75 Liquid Level Switches 11 3.2 Check Sensing Unit 1. Reconnect power supply. Being careful to avoid electrical shock, manually actuate switch mechanism (use a nonconductive tool on electrical switch mechanisms) to determine whether controlled equipment will operate. Caution: With electrical power on, care should be taken to avoid contact with switch leads and connections at terminal block. 2. If controlled equipment responds to manual actuation test, trouble may be located in the level sensing portion of the control, float(s), stem(s), and magnetic attraction sleeve(s). 3. Check to be certain liquid is entering float chamber. A valve may be closed or piping plugged. Caution: Be certain to pull disconnect switch or otherwise ensure that electrical circuit(s) through control is deactivated. Close operating medium supply valve on controls equipped with pneumatic switch mechanisms. 4. With liquid in chamber, proceed to check level sensing action by removing switch housing assembly and enclosing tube. 5. Disconnect wiring from supply side of switch mechanism(s) and remove electrical conduit or operating medium line connections to switch housing. 6. Perform system shutdown to relieve pressure from float chamber of control and allow unit to cool. 7. Close shutoff valves (if equipped) to isolate control from vessel. Drain off liquid in chamber if necessary 8. On installations without shutoff valves, relieve pressure from vessel and drain off liquid head above control mounting level. NOTE: Control chamber, connections, and pipe lines need not be removed from vessel or boiler. 9. Remove switch housing assembly by loosening hex nut, which is located immediately below housing base. 10. With switch housing assembly removed, inspect attraction sleeve(s) and inside of enclosing tube for excessive corrosion or solids buildup which could restrict movement, preventing sleeve(s) from reaching field of switch magnet(s). 11. If differential has been changed in the field by repositioning the lower jam nuts on the float stem, check tightness and position of the jam nuts. Refer to Figure 7 on page 8. 12 46-620 B73 & Series 75 Liquid Level Switches NOTE: Differential adjustment affects a change in the amount of level travel between switch-on and switch-off actuations. Do not attempt adjustment without first consulting factory for assistance in computing level differential change for your control. 12. Check float to be certain it is buoyant in the liquid (float chamber or vessel must have adequate liquid level). If float is determined to be filled with liquid, or it is collapsed, it must be replaced immediately. Do not attempt to repair a float. See Section 2.5, Tandem Float Models on page 10. If all components in the control are in operating condition, the trouble must be located external to the control. Repeat inspection of external conditions previously described. NOTE: If difficulties are encountered which cannot be identified, consult the factory or your local representative for assistance. A complete description of the trouble should be provided along with information concerning your piping and mounting arrangement, plus a description of your operating sequence. Sketches or photographs showing the installation are also beneficial. When communicating about your control, be certain to always specify the complete Model and Serial numbers. 4.0 Preventive Maintenance Periodic inspections are a necessary means to keep your Magnetrol level control in good working order. This control is a safety device to protect the valuable equipment it serves. A systematic program of preventive maintenance must be implemented when the control is placed into service. If the following is observed, your control will provide reliable protection of your capital equipment for many years. 4.1 What To Do 4.1.1 Keep Control Clean Be sure the switch housing cover is always in place on the control. This cover is designed to keep dust and dirt from interfering with switch mechanism operation. In addition, it protects against damaging moisture and acts as a safety feature by keeping bare wires and terminals from being exposed. Should the housing cover or any seals become damaged or misplaced, obtain a replacement immediately. 46-620 B73 & Series 75 Liquid Level Switches 13 4.1.2 Inspect Switch Mechanisms, Terminals, and Connections Monthly 1. Switches should be inspected for excessive wear on actuating lever or misalignment of adjustment screw at point of contact between screw and lever. Such wear can cause false switch actuating levels. See Section 6.1.2, Switch and Housing Reference on page 20 for bulletin supplied with control should switch adjustment or replacement be necessary. 2. DO NOT operate your control with defective or mal-adjusted switch mechanisms. See Section 6.1.2, Switch and Housing Reference on page 20 for bulletin on switch mechanisms furnished for service instructions. 3. Level controls may sometimes be exposed to excessive heat or moisture. Under such conditions, insulation on electrical wiring may become brittle, eventually breaking or pealing away. The resulting exposed wires can cause short circuits. NOTE: Check wiring carefully and replace at the first sign of brittle insulation. 4. Vibration may sometimes cause terminal screws to work loose. Check all terminal connections to be certain that screws are tight. 5. On units with pneumatic switches, air (or gas) lines subjected to vibration, may eventually crack or become loose at connections causing leakage. Check lines and connections carefully and repair or replace if necessary. NOTE: As a matter of good practice, spare switches should be kept on hand at all times. 4.1.3 Inspect Entire Unit Periodically Isolate control from vessel. Raise and lower liquid level to check for switch contact and reset. 4.2 What To Avoid Caution: Operation of all buoyancy type level devices should be done in such a way as to minimize the action of dynamic forces on the float or displacer sensing element. Good practice for reducing the likelihood of damage to the control is to equalize pressure across the device very slowly. 1. Never leave switch housing cover off the control longer than necessary to make routine inspections. 2. Never place a jumper wire across terminals to “cut-out” the control. If a “jumper” is necessary for test purposes, be certain it is removed before placing control into service. 14 46-620 B73 & Series 75 Liquid Level Switches 3. Never attempt to make adjustments or replace switches without reading instructions carefully. Certain adjustments provided for in level controls should not be attempted in the field. When in doubt, consult the factory or your local representative. 4. Never use lubricants on pivots of switch mechanisms. A sufficient amount of lubricant has been applied at the factory to ensure a lifetime of service. Further oiling is unnecessary and will only tend to attract dust and dirt which can interfere with mechanism operation. 5.0 Specifications 5.1 Agency Approvals Agency Approved Model Area Classification FM All with an electric switch mechanism and a housing listed as TYPE 4X/7/9 Class I, Div 1, Groups C & D Class II, Div 1, Groups E, F & G All with an electric switch mechanism and a housing listed as TYPE 4X/7/9 Class I, Div 1, Group B Class I, Div 1, Groups B, C & D Class II, Div 1, Groups E, F & G All with a Series F, HS, or H1 electric switch mechanism and a housing listed as CSA TYPE 4X Class I, Div 2, Groups B, C & D All with an electric switch mechanism and a housing listed as TYPE 4X/7/9 Class I, Div 1, Groups C & D Class II, Div 1, Groups E, F & G All with an electric switch mechanism and a housing listed as TYPE 4X/7/9 Class I, Div 1, Group B Class I, Div 1, Groups B, C & D Class II, Div 1, Groups E, F & G All with an electric switch mechanism and an ATEX housing ATEX II 2 G EEx D IIC T6 94/9/EC IEC ExEx d IIC T6 IP66 Low voltage directives 2006/95/EC Installation Category II Pollution Degree 2 CSA ATEX / IEC Ex CE Per Harmonized Standard EN 61010-1/1993 & Amendment No. 1 Models with two HS or two H1 switches are not ATEX approved. Maximum Process Temperature Temperature Classification < 85° C T6 < 100° C T5 < 135° C T4 Heat extensions (between process connection and housing) shall never be insulated. < 200° C T3 < 300° C T2 Special conditions for safe use: < 450° C T1 IEC Installation Instructions: The cable entry and closing devices shall be Ex d certified suitable for the conditions of use and correctly installed. For ambient temperatures above +55° C or for process temperatures above +150° C, suitable heat resistant cables shall be used. When the equipment is installed in process temperatures higher than +85° C the temperature classification must be reduced according to the following table as per IEC60079-0. 46-620 B73 & Series 75 Liquid Level Switches These units are in conformity with IECEx KEM 05.0020X Classification Ex d IIC T6 Tambient -40° C to +70° C 15 5.2 Physical STAINLESS STEEL CHAMBERS WITH 1-INCH CONNECTIONS INCHES Min. SG NPT & Socket Weld A B C Flanged Upper Side/Btm A B C Flanged Side/Side A B C MILLIMETERS Actuating Levels NPT & Socket Weld HL A LL Flanged Upper Side/Btm Flanged Side/Side B C A B C C HL B73 0.59 6.36 3.34 17.44 9.25 6.25 20.32 9.90 6.25 21.00 1.22 2.10 151 84 442 235 159 515 251 159 532 30 53 C75 0.60 8.50 3.61 22.06 11.56 6.68 25.12 12.21 6.68 25.75 2.75 3.62 216 92 560 294 170 638 310 170 654 70 92 J75 0.57 9.25 3.61 23.06 12.31 6.68 26.12 12.96 6.68 26.75 2.93 3.78 235 92 586 313 170 663 329 170 679 74 96 216 69 555 294 144 633 310 144 651 62 89 66 548 294 141 625 310 141 646 62 89 78 557 294 155 635 310 155 652 65 89 O75 0.85 8.50 2.71 21.87 11.56 5.68 24.93 12.21 5.68 25.62 2.44 3.50 O75 0.85 8.50 2.59 21.56 11.56 5.56 24.62 12.21 5.56 25.43 2.44 3.50 216 P75 0.75 8.50 3.09 21.93 11.56 6.12 25.00 12.21 6.12 25.68 2.56 3.50 216 A B Actuating Levels LL Levels ± 0.25" (6 mm) STAINLESS STEEL CHAMBERS WITH 11⁄2-INCH CONNECTIONS INCHES Min. SG NPT & Socket Weld A B C Flanged Upper Side/Btm A B C Flanged Side/Side A B C MILLIMETERS Actuating Levels NPT & Socket Weld HL A LL Flanged Upper Side/Btm Flanged Side/Side A B Actuating Levels B C A B C C HL LL C75 0.60 8.50 4.22 12.56 12.56 7.68 16.63 13.21 7.68 17.31 2.13 3.00 215 107 319 319 195 422 335 195 439 54 76 J75 0.57 9.25 4.22 13.56 13.31 7.68 17.63 13.96 7.68 18.25 2.75 3.50 234 107 344 338 195 448 354 195 464 70 89 Levels ± 0.25" (6 mm) STAINLESS STEEL CHAMBERS WITH 2-INCH CONNECTIONS INCHES Min. SG NPT & Socket Weld A B C Flanged Upper Side/Btm A B C Flanged Side/Side A B C MILLIMETERS Actuating Levels NPT & Socket Weld HL A LL Flanged Upper Side/Btm Flanged Side/Side B C A B C C75 0.60 8.25 4.37 12.69 12.56 7.68 17.00 13.21 7.68 17.69 1.75 2.63 209 110 322 319 195 431 335 195 A B J75 0.57 9.00 4.34 13.69 13.31 7.68 18.00 13.96 7.68 18.69 2.98 3.13 228 110 348 338 195 457 354 195 Actuating Levels C HL LL 449 44 69 475 60 80 Levels ± 0.25" (6 mm) Minimum SG given is for single switch units with -1 materials of construction. Consult factory for other configurations. Switch actuating levels (HL & LL) are given for minimum specific gravity materials of construction –1 and single switch units. Consult factory for other configurations. 304 Stainless steel only 316 Stainless steel only Standard process connections are a combination of 1" NPT and 1" socket weld coupling. These dimensions increase by 2.19 (55) with Series HS switches with terminal blocks. Allow overhead clearance of 10.00 (254) for cover removal. All housings rotatable 360°. 16 46-620 B73 & Series 75 Liquid Level Switches Inches (mm) D D E E D E F F F C C HL HL LL LL C A A HL LL A B B B Series 75 Flanged Upper Side/Bottom Series 75 Threaded and Socket Weld Upper Side/Bottom Series 75 Flanged Side/Side D E D 6.25 (158) E D F 6.25 (158) E F F 6.25 (158) plugged F F F plugged C HL plugged C HL C HL LL LL A A LL A B Model B73 Threaded and Socket Weld Upper Side/Bottom B B Model B73 Upper Side/Bottom Flanged Housing 46-620 B73 & Series 75 Liquid Level Switches Model B73 Side/Side Flanged D E NEMA 1 4.70 5.00 (119) (127) TYPE 4X/7/9 Group B 5.93 (151) 3.87 (98) Conduit Connections F Electrical Switches TYPE 4X/7/9: 1" NPT Group B: 1" NPT Pneumatic Switches 1 NEMA 1: ⁄4" NPT 17 5.2 Physical CARBON STEEL CHAMBERS WITH 1-INCH CONNECTIONS INCHES Min. SG NPT & Socket Weld A B73 0.59 B75 0.67 B C 6.36 3.34 17.44 Flanged Upper Side/Btm A B C Flanged Side/Side A B MILLIMETERS Actuating Levels C HL LL NPT & Socket Weld A 9.25 6.25 20.32 9.90 6.25 21.00 1.22 2.10 151 A B C 515 A B C 251 159 532 649 310 170 666 F75 0.55 10.91 5.33 24.91 13.78 8.19 27.78 14.39 8.19 28.39 1.76 2.35 277 135 633 350 208 706 366 208 721 G75 0.53 2.25 2.92 Actuating Levels HL LL 30 53 65 82 69 87 44 59 57 74 73 91 240 110 595 313 183 668 329 183 685 K75 0.39 11.69 5.33 25.69 14.56 8.19 28.56 15.21 8.19 29.21 2.15 2.77 297 135 653 370 208 754 386 208 742 54 70 L75 0.40 9.44 4.33 23.44 12.31 7.19 26.31 12.96 7.19 26.96 2.45 3.19 240 110 595 313 183 668 329 183 685 62 81 N75 0.32 11.69 5.33 25.69 14.56 8.19 28.56 15.21 8.19 29.21 2.17 2.86 297 135 653 370 208 754 386 208 742 55 72 54 70 J75 0.48 9.44 4.33 23.44 12.31 7.19 26.31 12.96 7.19 26.96 2.72 3.44 221 C 84 442 235 159 Flanged Side/Side 97 576 294 170 C75 0.55 8.69 3.80 22.69 11.56 6.69 25.56 12.21 6.69 26.21 2.56 3.24 B Flanged Upper Side/Btm S75 0.60 11.16 5.33 27.06 Consult Factory 2.90 3.62 2.13 2.78 283 135 687 Consult Factory V75 0.74 9.02 4.15 23.27 11.56 6.68 25.81 12.21 6.68 26.46 2.63 3.38 229 105 591 294 170 656 313 170 672 69 86 Z75 0.68 9.77 4.68 24.16 12.31 7.18 26.70 12.96 7.18 27.35 2.38 3.19 248 119 614 313 182 678 329 182 695 60 81 Levels ± 0.25" (6 mm) CARBON STEEL CHAMBERS WITH 11⁄2-INCH CONNECTIONS INCHES Min. SG B75 0.67 NPT & Socket Weld A B C Flanged Upper Side/Btm A B C Flanged Side/Side A B C 1.93 2.61 NPT & Socket Weld A B C Flanged Upper Side/Btm A B C Flanged Side/Side A B C 227 107 586 319 195 678 336 195 694 F75 0.55 11.06 5.75 26.19 14.78 9.19 29.92 15.39 9.19 30.53 1.08 1.66 281 146 665 375 233 760 391 233 775 C75 0.55 G75 0.53 8.94 4.22 23.06 12.56 7.69 26.69 13.21 7.69 27.34 MILLIMETERS Actuating Levels HL LL 1.59 2.25 49 66 49 66 27 42 40 57 56 74 244 121 612 338 208 705 355 208 722 K75 0.39 12.06 5.75 27.14 15.56 9.19 30.64 16.21 9.19 31.29 1.77 2.39 306 146 689 395 233 778 412 233 795 44 60 L75 0.40 9.62 4.75 24.09 13.31 8.19 27.75 13.96 8.19 28.42 1.78 2.52 244 121 612 338 208 705 355 208 722 44 64 N75 0.32 12.06 5.75 27.14 15.56 9.19 30.64 16.21 9.19 31.29 1.81 2.49 306 146 689 395 233 778 412 233 306 J75 0.48 9.62 4.75 24.09 13.31 8.19 27.75 13.96 8.19 28.42 1.93 2.61 Actuating Levels HL LL S75 0.60 Consult Factory 2.23 2.95 n/a n/a Consult Factory 45 63 n/a n/a V75 0.74 8.82 4.22 23.20 12.56 7.68 26.94 13.21 7.68 27.79 1.94 2.69 224 107 589 319 195 684 336 195 706 49 68 Z75 0.68 9.51 4.75 24.09 13.31 8.18 27.89 13.96 8.18 28.54 1.69 2.59 242 121 612 338 208 708 355 208 725 43 66 Levels ± 0.25" (6 mm) CARBON STEEL CHAMBERS WITH 2-INCH CONNECTIONS INCHES Min. SG B75 0.67 NPT & Socket Weld A B C Flanged Upper Side/Btm A B C Flanged Side/Side A B C 1.48 2.16 NPT & Socket Weld A B C Flanged Upper Side/Btm A B C Flanged Side/Side A B C 221 110 589 319 195 662 336 195 704 F75 0.55 10.94 5.88 26.32 14.78 9.19 30.16 15.39 9.19 30.77 0.78 1.36 278 149 669 375 233 766 391 233 782 C75 0.55 G75 0.53 8.69 4.34 23.20 12.56 7.69 26.07 13.21 7.69 27.72 MILLIMETERS Actuating Levels HL LL 1.31 1.97 37 54 41 59 19 34 33 50 49 67 241 124 615 338 208 712 355 208 728 K75 0.39 11.94 5.88 27.32 15.56 9.19 30.94 16.21 9.19 31.59 1.59 2.21 303 149 694 395 233 786 412 233 802 40 56 L75 0.40 9.50 4.88 24.21 13.31 8.19 28.02 13.96 8.19 28.67 1.50 2.24 241 124 615 338 208 712 355 208 728 38 56 N75 0.32 11.94 5.88 27.32 15.56 9.19 30.94 16.21 9.19 31.59 1.63 2.31 303 149 694 395 233 786 412 233 802 40 58 J75 0.48 S75 0.60 9.50 4.88 24.21 13.31 8.19 28.02 13.96 8.19 28.67 1.64 2.36 Actuating Levels HL LL Consult Factory 1.95 2.67 n/a n/a V75 0.74 8.49 4.34 23.27 12.56 7.68 27.34 13.21 7.68 27.99 1.88 2.63 216 110 n/a n/a 591 Consult Factory 319 195 694 336 195 711 48 67 Z75 0.68 9.31 4.87 24.16 13.31 8.18 28.16 13.96 8.18 28.81 1.44 2.25 236 124 614 338 208 715 355 208 732 37 57 Levels ± 0.25" (6 mm) Minimum SG given is for single switch units with -1 materials of construction. Consult factory for other configurations. Switch actuating levels (HL & LL) are given for minimum specific gravity materials of construction –1 and single switch units. Consult factory for other configurations. Standard process connections are a combination of 1" NPT and 1" socket weld coupling. 18 46-620 B73 & Series 75 Liquid Level Switches Inches (mm) D D E E D E F F F C HL C HL LL LL C A A HL LL A B B B Series 75 Flanged Upper Side/Bottom Series 75 Threaded and Socket Weld Upper Side/Bottom Series 75 Flanged Side/Side D E D 6.25 (158) E D F 6.25 (158) E F 6.25 (158) F F plugged HL plugged plugged F C F C HL C HL LL LL A A LL A B Model B73 Threaded and Socket Weld Upper Side/Bottom B Model B73 Upper Side/Bottom Flanged These dimensions increase by 2.19 (55) with Series HS switches with terminal blocks. Allow overhead clearance of 10.00 (254) for cover removal. All housings rotatable 360°. 46-620 B73 & Series 75 Liquid Level Switches B Housing Model B73 Side/Side Flanged D E NEMA 1 4.70 5.00 (119) (127) TYPE 4X/7/9 Group B 5.93 (151) 3.87 (98) Conduit Connections F Electrical Switches TYPE 4X/7/9: 1" NPT Group B: 1" NPT Pneumatic Switches 1 NEMA 1: ⁄4" NPT 19 6.0 Replacement Parts 6.1 Series 75 6.1.1 Parts Identification 1 Item 1 2 3 4 5 6 7 8 9 10 4 5 3 2 9 8 6 10 Description Housing cover Housing base Switch mechanism Jam nuts Lock washer Attraction sleeve Stop tube (not shown) Enclosing tube E-tube gasket Chamber assembly IMPORTANT: When ordering, please specify: A. Model and serial numbers or control. B. Name and/or number of replacement assembly. Many Model 75 controls are specially tailored to meet customer specifications and, therefore, may contain special parts. When ordering, always provide serial number of control. 6.1.2 Switch and Housing Reference Dry contact Hermetically sealed Bleed type pneumatic Non-bleed type pneumatic High temperature dry contact 20 Series Type B, C, D HS, H1 J K F, R, 8, 9 Bulletin # 42-683 42-694 42-685 42-486 42-799 46-620 B73 & Series 75 Liquid Level Switches 6.1.3 Series 75 with Material Code 1 All Models except S75, V75 & Z75 Housing cover Housing base Switch mechanism Attraction sleeve kit: includes items 4, 5, 6 & 7 Enclosing tube - models w/electric switches* Enclosing tube - models w/J or K switches E-tube gasket - Models B, E, F, G, H, K E-tube gasket - Models C, J, L, M, N Chamber assembly S75, V75 & Z75 Only See Section 6.1.2, Switch and Housing Reference on previous page for switch and housing bulletin furnished. 089-3409-009 089-3409-002 Z32-6325-004 Z32-6325-006 Z32-6325-001 Z32-6325-003 012-1204-001 012-1204-001 012-1301-002 012-1204-001 Available as complete sensing units only with all parts listed under items 4 through 10 assembled. When ordering, specify specify model and serial number of control. *Consult factory for Series G, H & I switches 6.1.4 Series 75 with Material Code 2 All Models except S75, V75 & Z75 Housing cover Housing base Switch mechanism Attraction sleeve kit: includes items 4, 5, 6 & 7 Enclosing tube - models w/electric switches* Enclosing tube - models w/J or K switches E-tube gasket - Models B, E, F, G, H, K E-tube gasket - Models C, J, L, M, N Chamber assembly S75, V75 & Z75 Only See Section 6.1.2, Switch and Housing Reference on previous page for switch and housing bulletin furnished. 089-3410-012 089-3410-002 Z32-6325-005 Z32-6325-006 Z32-6325-002 Z32-6325-003 012-1204-001 012-1204-001 012-1301-002 012-1204-001 Available as complete sensing units only with all parts listed under items 4 through 10 assembled. When ordering, specify model and serial number of control. *Consult factory for Series G, H & I switches 6.1.5 Series 75 with Material Code 3 or 4 All Models w/Material Code 3 Housing cover Housing base Switch mechanism Attraction sleeve kit: includes items 4, 5, 6 & 7 Enclosing tube - models w/electric switches Enclosing tube - models w/J or K switches Enclosing tube gasket Chamber assembly 46-620 B73 & Series 75 Liquid Level Switches All Models w/Material Code 4 See Section 6.1.2, Switch and Housing Reference on previous page for switch and housing bulletin furnished. 089-3410-010 089-3410-001 Z32-6325-005 Z32-6325-005 Z32-6325-002 Z32-6325-002 012-1301-002 012-1301-002 Available as complete sensing units only with all parts listed under items 4 through 10 assembled. When ordering, specify specify model and serial number of control. 21 6.2 Model B73 1 4 5 3 2 7 6 8 9 6.2.1 Parts Identification Item 1 2 3 4 5 6 7 8 9 Description Housing cover Housing base Switch mechanism Jam nuts Lock washer Attraction sleeve Enclosing tube E-tube gasket Chamber assembly IMPORTANT: When ordering, please specify: A. Model and serial numbers or control. B. Name and/or number of replacement assembly. Many Model 75 controls are specially tailored to meet customer specifications and, therefore, may contain special parts. When ordering, always provide serial number of control. 6.2.2 Switch and Housing Reference Dry contact Hermetically sealed Hermetically sealed Bleed type pneumatic Non-bleed type pneumatic Series Type B, C, D F HS, H1 J K Bulletin # 42-683 42-799 42-694 42-685 42-486 6.2.3 Model B73 Model B73-1 Housing cover Housing base Switch mechanism Attraction sleeve kit includes items 4, 5, & 6 Enclosing tube E-tube gasket Chamber assembly 22 Model B73-2 or B73-4 Model B73-3 See Section 6.2.2, Switch and Housing Reference above for switch and housing bulletin furnished. 089-3409-012 089-3410-009 089-3410-011 Z32-6325-001 Z32-6325-002 Z32-6325-002 012-1301-002 012-1301-002 012-1301-002 Available as complete sensing units only with all parts listed under items 4 through 10 assembled. When ordering, specify specify model and serial number of control. 46-620 B73 & Series 75 Liquid Level Switches 6.3 Series 75 Tandem Float Units 1 3 10 4 6.3.1 Parts Identification 8 2 Item 1 2 3 4 5 6 7 8 9 10 11 5 9 6 11 Description Housing cover Housing base Switch mechanism Jam nuts Upper attraction sleeve Lower attraction sleeve Spacer washer (not shown) Retaining ring E-tube gasket Enclosing tube Chamber assembly 6.3.2 Series 75 Tandem Float Units Models B, C, G, J, L, & M Housing cover Housing base Switch mechanism Attraction sleeve kit: includes items 4, 5, 6, 7 & 8 E-tube gasket Enclosing tube Chamber assembly Models F, K, & N See Section 6.3.3, Switch and Housing Reference below for switch and housing bulletin furnished. 089-3411-001 (Mat’l Code 1) 089-3413-001 (Mat’l Code 1) 089-3412-001 (Mat’l Code 2, 3, & 4) 089-3414-001 (Mat’l Code 2, 3, & 4) 012-1204-001 012-1204-001 Z32-6325-004 (Mat’l Code 1) / Z32-6325-004 (Mat’l Code 1) / Z32-6325-005 (Mat’l Code 2) / Z32-6325-005 (Mat’l Code 2) / Available as complete sensing units only with all parts listed under items 4 through 10 assembled. When ordering, specify model and serial number of control. 6.3.3 Switch and Housing Reference Dry contact Hermetically sealed Bleed type pneumatic Non-bleed type pneumatic High temperature dry contact 46-620 B73 & Series 75 Liquid Level Switches Series Type B, C, D HS, H1 J K F, R, 8, 9 Bulletin# 42-683 42-694 42-685 42-486 42-799 23 7.0 Model Numbers 7.1 Model B73 MODEL NUMBER CODE Pressure Rating psig @ ° F bar @ ° C 100 450 38 232 Model Min. No. SG Materials of Construction B73-1 0.59 Carbon steel chamber, 316 stainless steel float, 400 stainless steel trim B73-2 0.59 Carbon steel chamber, 316 stainless steel float, 316 stainless steel trim 304 stainless steel chamber, 316 stainless steel float, 304 stainless steel trim B73-3 0.59 B73-4 0.59 400 275 28 20 316 stainless steel chamber, 316 stainless steel float, 316 stainless steel trim TANK CONNECTION TYPE AND SIZE B20 1" NPT threaded side/bottom B30 N30 1" socket weld side/bottom 1" 150 lb. flanged upper side/bottom N40 1" 300 lb. flanged upper side/bottom S30 1" 150 lb. flanged side/side S40 1" 300 lb. flanged side/side Models are limited to maximum temperature rating of selected switch mechanism. See Switch Mechanism chart on page 27. Consult factory for TYPE 4X/7/9 cast iron housings. Process temperature based on +100° F (+38° C) ambient. Drain or uncontrolled housing heater available in TYPE 4X/7/9 enclosures. Consult factory for standard part number. On steam & other condensing applications, temperature downrated to +400° F (+204° C) process @ +100° F (+38° C) ambient. 24 46-620 B73 & Series 75 Liquid Level Switches ELECTRIC SWITCH MECHANISM AND ENCLOSURE Model B73-1 Only Models B73-2, B73-3, B74-4 TYPE 4X/7/9 Aluminum Enclosure Class I, Div 1 Class I, Div 1 Process Groups Groups Temperature One Set Point C&D B, C & D Range °F (°C) Contacts Switch Description -40 to +250 (-40 to +121) Series B Snap -40 to +450 (-40 to +232) Series C Snap -40 to +250 (-40 to +121) Series D Snap Series F Hermetically Sealed Snap Series HS Hermetically Sealed 5 amp Snap with wiring leads Series HS Hermetically Sealed 5 amp Snap with terminal block SPDT DPDT SPDT DPDT ATEX Class I, Div 1 Class I, Div 1 Groups Groups C&D B, C & D ATEX BKP BNP BKT BNT BAC BBC BKQ BNQ BKS BNS BA9 BB9 CKP CNP CKT CNT CAC CBC CKQ CNQ CKS CNS CA9 CB9 DKQ DNQ DKS DNS DA9 DB9 SPDT n/a DPDT SPDT FKP FKT FAC FKQ FKS FA9 DPDT FNP FNT FBC FNQ FNS FB9 -50 to +450 (-46 to +232) -50 to +450 (-46 to +232) -50 to +450 (-46 to +232) SPDT n/a HMC HEK n/a DPDT n/a HMF HET n/a SPDT n/a HM3 HM4 HA9 DPDT n/a HM7 HM8 HB9 PNEUMATIC SWITCH MECHANISM AND ENCLOSURE Switch Description Series J Bleed Type Series K Non-Bleed Maximum Supply Pressure psig bar Maximum Process Temperature °F °C 100 60 60 100 40 400 400 450 400 400 7 4 4 7 3 204 204 232 204 204 46-620 B73 & Series 75 Liquid Level Switches Bleed Orifice Diameter inches mm .063 .094 .055 — — 1.6 2.3 1.4 — — Models with Material of Construction Code 1 Code 2, 3 or 4 NEMA 1 NEMA 1 JDG JEG JFG — KOG JDE JEE JFE KOE — 25 7.2 Series 75 MODEL NUMBER CODE Min. S.G. for models with Model Material of Construction Code Code 1 2 3&4 CARBON STEEL CHAMBER B75 0.67 0.71 n/a C75 0.55 0.59 n/a F75 0.55 0.56 n/a G75 0.53 0.56 n/a J75 0.48 0.51 n/a K75 0.39 0.40 n/a L75 0.40 0.42 n/a N75 0.32 0.33 n/a S75 0.60 n/a n/a V75 0.74 0.81 n/a Z75 0.68 0.71 n/a STAINLESS STEEL CHAMBER C75 n/a n/a 0.60 J75 n/a n/a 0.57 O75 n/a n/a 0.85 P75 n/a n/a 0.75 psig @ ° F 750 900 100 550 1000 500 1000 750 400 600 300 450 1500 2240 2193 870 435 870 653 — — — — 1275 1913 1913 716 400 800 600 250 375 185 280 1045 1455 1425 500 400 500 400 435 — 435 — 400 225 400 225 Pressure Rating bar @ ° C 399 482 1000 38 288 538 357 357 523 338 — — — — 523 728 713 138 138 200 130 — — — — n/a n/a n/a 69 34 69 52 28 41 21 31 103 154 151 60 30 60 45 — — — — 88 132 132 49 28 55 41 17 26 13 19 72 100 98 25 25 36 23 — — — — 36 50 49 10 10 14 9 — — — — n/a n/a n/a 385 — 385 — 380 — 380 — 34 28 34 28 30 — 30 — 28 16 28 16 26 — 26 — 26 — 26 — MATERIALS OF CONSTRUCTION 1 2 3 4 Carbon steel chamber, 316 stainless steel float, 400 stainless steel trim Carbon steel chamber, 316 stainless steel float, 316 stainless steel trim 304 Stainless steel chamber, 316 stainless steel float, 316 stainless steel trim 316 Stainless steel chamber, 316 stainless steel float, 316 stainless steel trim TANK CONNECTION TYPE AND SIZE Size 2" 11⁄2" Type Material 1" Threaded Side/Bottom CS B20 C20 D20 SS B20 C20 D20 Socket Weld Side/Bottom CS B20 C30 D30 SS B30 C30 D30 Cage Mounting Flange Rating (lbs.) 150 300 600 900 150 300 N50 N60 P40 Flanged Upper Side/Bottom CS N30 N40 SS N30 N40 Flanged Side/Side CS S30 S40 SS S30 S40 P30 600 900 150 300 600 900 P50 P60 Q30 Q40 Q50 Q60 V30 V40 V50 V60 Consult Factory S50 S60 T30 T40 T50 T60 Consult Factory PNEUMATIC SWITCH MECHANISM AND ENCLOSURE Switch Description Series J Bleed Type Series K Non-Bleed Maximum Supply Pressure psig bar Maximum Bleed Process Orifice Temperature Diameter °F ° C inches mm Excluding S75, V75 & Z75 S75, V75 & Z75 NEMA 1 NEMA 1 100 60 60 7 4 4 400 400 700 204 204 371 .063 .094 .055 1.6 2.3 1.3 JDE JEE JFE JKE JLE JME 100 7 400 204 — — KOE KPE Electric switch mechanism and enclosure codes on the following page. See Notes on back cover. 26 46-620 B73 & Series 75 Liquid Level Switches ELECTRIC SWITCH MECHANISM AND ENCLOSURE Switch Description Series B Snap Switch Series C Snap Switch Series D DC Current Snap Switch Series F Hermetically Sealed Snap Switch Series HS Hermetically Sealed 5-amp Snap Switch with Wiring Leads All Models with Material of Construction Code 1 except Models S75, V75 & Z75 Process Temperature Set Contacts TYPE 4X/7/9 Aluminum Enclosure Range Points ATEX ATEX °F (°C) Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1 Ex II 2 G EEx Ex II 2 G EEx Groups C&D Group B Groups C&D Group B d IIC T6 d IIC T6 1 BKA BKJ BCC BKB BKK BC9 SPDT 2 BLA BLJ BDC BLB BLK BD9 -40 to +250 3 BMA BMJ BEC BMB BMK BE9 (-40 to +121) 1 BNA BNJ BFC BNB BNK BF9 DPDT 2 BOA BOJ BGC BOB BOK BG9 1 CKA CKJ CCC CKB CKK CC9 SPDT 2 CLA CLJ CDC CLB CLK CD9 -40 to +450 3 CMA CMJ CEC CMB CMK CE9 (-40 to +232) 1 CNA CNJ CFC CNB CNK CF9 DPDT 2 COA COJ CGC COB COK CG9 1 DKB DKK DC9 DKB DKK DC9 SPDT 2 DLB DLK DD9 DLB DLK DD9 -40 to +250 3 DMB DMK DE9 DMB DMK DE9 (-40 to +121) 1 DNB DNK DF9 DNB DNK DF9 DPDT 2 DOB DOK DG9 DOB DOK DG9 1 FKA FKJ FCC FKB FKK FC9 SPDT 2 FLA FLJ FDC FLB FLK FD9 -50 to +750 (-46 to +399) 1 FNA FNJ FFC FNB FNK FF9 DPDT 2 FOA FOJ FGC FOB FOK FG9 1 HMJ HMK HMJ HMK SPDT 2 HMN HMP HMN HMP -50 to +550 N/A N/A (-46 to +288) 1 HMS HMT HMS HMT DPDT 2 HMY HMZ HMY HMZ Series HS Hermetically Sealed 5-amp Snap Switch with Terminal Block -50 to +550 (-46 to +288) Series H1 Hermetically Sealed 1-amp Snap Switch with Wiring Leads -50 to +750 (-46 to +399) Series R High Temperature Snap Switch -40 to +750 (-40 to +399) Series 8 Hermetically Sealed Snap Switch -50 to +750 (-46 to +399) Series 9 High Temperature Hermetically Sealed Snap Switch -50 to +750 (-46 to +399) Switch Description Series R High Temperature Snap Switch Series 9 High Temperature Hermetically Sealed Snap Switch All models with Material of Construction Codes 2 and all Models S75, V75 & Z75 SPDT 1 HM3 HM4 HA9 HM3 HM4 HA9 DPDT 1 HM7 HM8 HB9 HM7 HM8 HB9 SPDT 1 HKJ HKK HKJ HKK HKN HKP RKB RLB RNB ROB 8KB 8LB 8MB 8NB 8OB 9KB 9LB 9MB 9NB 9OB RKK RLK RNK ROK 8KK 8LK 8MK 8NK 8OK 9KK 9LK 9MK 9NK 9OK N/A DPDT SPDT DPDT SPDT DPDT SPDT DPDT 2 HKN HKP 1 2 1 2 1 2 3 1 2 1 2 3 1 2 RKB RLB RNB ROB 8KA 8LA 8MA 8NA 8OA 9KA 9LA 9MA 9NA 9OA RKK RLK RNK ROK 8KJ 8LJ 8MJ 8NJ 8OJ 9KJ 9LJ 9MJ 9NJ 9OJ RC9 RD9 RF9 RG9 8CC 8DC 8EC 8FC 8GC 9CC 9DC 9EC 9FC 9GC N/A RC9 RD9 RF9 RG9 8C9 8D9 8E9 8F9 8G9 9C9 9D9 9E9 9F9 9G9 Process Cast Iron Cast Iron CS/Aluminum CS/Aluminum Set Temp. Range Contacts Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1 Points NEMA 4X NEMA 4X °F (°C) Groups C&D Group B Groups C&D Group B 1 R1M RKM RKW R1M RKM RKW SPDT 2 R3M RLM RLW R3M RLM RLW -40 to +1000 (-40 to +538) 1 RDM RNM RNW RDM RNM RNW DPDT 2 REM ROM ROW REM ROM ROW 1 9AD 9KD 9KV 9AM 9KM 9KW SPDT 2 9BD 9LD 9LV 9BM 9LM 9LW -50 to +1000 3 9CD 9MD 9MV 9CM 9MM 9MW (-46 to +538) 1 9DD 9ND 9NV 9DM 9NM 9NW DPDT 2 9ED 9OD 9OV 9EM 9OM 9OW See Notes on back cover. 46-620 B73 & Series 75 Liquid Level Switches 27 NOTES (FOR SECTION 7.2) Minimum specific gravity ratings apply only to single stage units. Consult factory for two or three stage units. Models are limited to maximum temperature rating of selected switch mechanism. See Switch Mechanism charts on pages 26 and 27. Use caution when specifying carbon steel and stainless steel for temperatures greater than +800° F (+427° C), as they become sensitized. S75, V75 & Z75 contain 17-7 ph float. The O75 and P75 are not available with 11⁄2" and 2" process connections. Valid for Models V75 & Z75 only. Consult factory for TYPE 4X/7/9 cast iron housings. 11 12 Process temperature based on +100° F (+38° C) ambient. Drain or uncontrolled housing heater available in TYPE 4X/7/9 enclosures. Consult factory for standard part number. HS and H1 switches can be used with materials of construction code 1 only on models S75, V75 & Z75. On steam and other condensing applications, temperature down-rated to +400° F (+204° C) process at +100° F (+38° C) ambient. R series switch supplied in cast iron switch enclosure. ASSURED QUALITY & SERVICE COST LESS Service Policy Return Material Procedure Owners of Magnetrol controls may request the return of a control or any part of a control for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Controls returned under our service policy must be returned by Prepaid transportation. Magnetrol will repair or replace the control at no cost to the purchaser (or owner) other than transportation if: So that we may efficiently process any materials that are returned, it is essential that a “Return Material Authorization” (RMA) number be obtained from the factory, prior to the material's return. This is available through Magnetrol’s local representative or by contacting the factory. Please supply the following information: 1. Returned within the warranty period; and 2. The factory inspection finds the cause of the claim to be covered under the warranty. If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labor and the parts required to rebuild or replace the equipment. In some cases it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the control to be replaced. In such cases, credit for the materials returned will be determined on the basis of the applicability of our warranty. 1. 2. 3. 4. 5. Company Name Description of Material Serial Number Reason for Return Application Any unit that was used in a process must be properly cleaned in accordance with OSHA standards, before it is returned to the factory. A Material Safety Data Sheet (MSDS) must accompany material that was used in any media. All shipments returned to the factory must be by prepaid transportation. All replacements will be shipped F.O.B. factory. No claims for misapplication, labor, direct or consequential damage will be allowed. 5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com 145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306 Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93 Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317 Copyright © 2010 Magnetrol International, Incorporated. All rights reserved. Printed in the USA. CSA logotype is a registered trademark of Canadian Standards Association BULLETIN: 46-620.16 EFFECTIVE: August 2010 SUPERSEDES: March 2008