ON ADM1031ARQZ-REEL Intelligent temperature monitor and dual pwm fan controller Datasheet

ADM1031
Intelligent Temperature
Monitor and Dual PWM Fan
Controller
The ADM1031 is an ACPI−compliant, three−channel digital
thermometer and under/overtemperature alarm for use in personal
computers and thermal management systems. Optimized for the
PentiumRIII, the part offers a 1°C higher accuracy, which allows
system designers to safely reduce temperature guard−banding and
increase system performance.
Two PWM fan control outputs control the speed of two cooling fans
by varying output duty cycle. Duty cycle values between 33% and
100% allow smooth control of the fans. The speed of each fan can be
monitored via TACH inputs, which can be reprogrammed as analog
inputs to allow speeds for 2−wire fans to be measured via sense
resistors. The device also detects a stalled fan. A dedicated fan speed
control loop provides control without the intervention of CPU
software. It also ensures that if the CPU or system locks up, each fan
can still be controlled based on temperature measurements, and the fan
speed is adjusted to correct any changes in system temperature. Fan
speed can also be controlled using existing ACPI software.
Two inputs (4 pins) are dedicated to remote temperature−sensing
diodes with an accuracy of ±1°C, and an on−chip temperature sensor
allows ambient temperature to be monitored. The device has a
programmable INT output to indicate error conditions, and a dedicated
FAN_FAULT output to signal fan failure. The THERM pin is a
fail−safe output for overtemperature conditions that can be used to
throttle a CPU clock.
Features
• Optimized for Pentium III
Reduced Guard−banding Software
♦ Automatic Fan Speed Control, Independent of CPU
Intervention After Initial Setup
0.125°C Resolution on External Temperature Channels
Control Loop to Minimal Acoustic Noise and Battery
Consumption
Remote Temperature Measurement Accurate to 1°C
Using Remote Diode (Two Channels)
Local Sensor with 0.25°C Resolution
Pulse Width Modulation (PWM) Fan Control for 2 Fans
Programmable PWM Frequency and PWM Duty Cycle
Tach Fan Speed Measurement (Two Channels)
Analog Input to Measure Fan Speed of 2−Wire Fans
(Using Sense Resistor)
2−Wire System Management Bus (SMBus) with ARA
Support
♦
•
•
•
•
•
•
•
•
•
http://onsemi.com
QSOP−16
CASE 492
MARKING DIAGRAM
1
1031A
RQZ
#YYWW
xxx
#
YY
WW
= Specific Device Code
= Pb−Free Package
= Date Code
= Work Week
PIN ASSIGNMENT
PWM_OUT1
1
16
SCL
TACH1/AIN1
2
15
SDA
PWM_OUT2
3
TACH2/AIN2
ADM1031
14
INT(SMBALERT)
4
13
ADD
GND
5
12
D2+
VCC
6
11
D2–
THERM
7
10
D1+
FAN_FAULT
8
9
D1–
• Overtemperature THERM Output Pin for CPU
•
•
•
•
•
Throttling
Programmable INT Output Pin
Configurable Offsets for Temperature Channels 3.0 V
to 5.5 V Supply Range
Shutdown Mode to Minimize Power Consumption
Limit Comparison of All Monitored Values
This is a Pb−Free Device
Applications
• Notebook PCs, Network Servers, and Personal Computers
• Telecommunications Equipment
© Semiconductor Components Industries, LLC, 2010
May, 2010 − Rev. 4
ORDERING INFORMATION
See detailed ordering and shipping information in the package
dimensions section on page 29 of this data sheet.
1
Publication Order Number:
ADM1031/D
ADM1031
VCC
6
13
ADM1031
SERIAL BUS
INTERFACE
SLAVE
ADDRESS
REGISTER
FAN
CHARACTERISTICS
REGISTER
PWM_OUT1
1
PWM_OUT2
3
TACH2/AIN2 4
TACH1/AIN1 2
FAN SPEED
CONFIG
REGISTER
TACH SIGNAL
CONDITIONING
FAN SPEED
COUNTER
INTERRUPT
STATUS
REGISTERS
D1–
9
BANDGAP
TEMPERATURE
SENSOR
14
INT (SMBALERT)
7
THERM
8
FAN_FAULT
VALUE AND LIMIT
REGISTERS
ANALOG
MULTIPLEXER
D2– 11
SCL
LIMIT
COMPARATOR
D1+ 10
D2+ 12
SDA
16
ADDRESS
POINTER
REGISTER
FAN FILTER
REGISTER
PWM
CONTROLLERS
ADD
15
OFFSET
REGISTERS
ADC
CONFIGURATION
REGISTERS
2.5V
BANDGAP
REFERENCE
5
GND
Figure 1. Functional Block Diagram
ABSOLUTE MAXIMUM RATINGS
Parameter
Positive Supply Voltage (VCC)
Voltage on Any Input or Output Pin
Rating
Unit
6.5
V
−0.3 to +6.5
V
Input Current at Any Pin
±5
mA
Package Input Current
±20
mA
Maximum Junction Temperature (TJ max)
150
°C
−65 to +150
°C
Storage Temperature Range
Lead Temperature, Soldering
Vapor Phase (60 sec)
Infrared (15 sec)
°C
215
200
ESD Rating − All Pins
2000
V
Stresses exceeding Maximum Ratings may damage the device. Maximum Ratings are stress ratings only. Functional operation above the
Recommended Operating Conditions is not implied. Extended exposure to stresses above the Recommended Operating Conditions may affect
device reliability.
NOTE: This device is ESD sensitive. Use standard ESD precautions when handling.
THERMAL CHARACTERISTICS
Package Type
16−lead QSOP
NOTE:
qJA
qJC
Unit
105
39
°C/W
qJA is specified for the worst−case conditions, that is, a device soldered in a circuit board for surface−mount packages.
http://onsemi.com
2
ADM1031
PIN ASSIGNMENT
Pin No.
Mnemonic
Description
1
PWM_OUT1
Digital Output, Open−Drain. Pulse width modulated output to control fan speed. Requires pullup
resistor (10 kW typical).
2
TACH1/AIN1
Digital/Analog Input. Fan tachometer input to measure FAN1 fan speed. Can be reprogrammed as an
analog input to measure speed of a 2−wire fan via a sense resistor (2 W typical).
3
PWM_OUT2
Digital Output, Open−Drain. Pulse width modulated output to control FAN2 fan speed. Requires
pullup resistor (10 kW typical).
4
TACH2/AIN2
Digital/Analog Input. Fan tachometer input to measure FAN2 fan speed. Can be reprogrammed as an
analog input to measure speed of a 2−wire fan via a sense resistor (2 W typical).
5
GND
System Ground.
6
VCC
Power. Can be powered by 3.3 V standby power if monitoring in low power states is required.
7
THERM
Digital I/O, Open−Drain. An active low thermal overload output that indicates a violation of a
temperature set point (overtemperature). Also acts as an input to provide external fan control. When
this pin is pulled low by an external signal, a status bit is set, and the fan speed is set to full−on.
Requires pullup resistor (10 kW).
8
FAN_FAULT
Digital Output, Open−Drain. Can be used to signal a fan fault. Drives second fan to full speed if one
fan fails. Requires pullup resistor (typically 10 kW).
9
D1–
Analog Input. Connected to cathode of first remote temperature−sensing diode. The
temperature−sensing element is either a Pentium III substrate transistor or a general−purpose
2N3904.
10
D1+
Analog Input. Connected to anode of first remote temperature−sensing diode.
11
D2–
Analog Input. Connected to cathode of second remote temperature−sensing diode.
12
D2+
Analog Input. Connected to anode of second remote temperature−sensing diode.
13
ADD
Three−State Logic Input. Sets two lower bits of device SMBus address.
14
INT(SMBALERT)
15
SDA
Digital I/O, Serial Bus Bidirectional Data. Open−drain output. Requires pullup resistor (2.2 kW typical).
16
SCL
Digital Input, Serial Bus Clock. Requires pullup resistor (2.2 kW typical).
Digital Output, Open−Drain. Can be programmed as an interrupt (SMBus ALERT) output for
temperature/fan speed interrupts. Requires pullup resistor (10 kW typical).
ELECTRICAL CHARACTERISTICS TA = TMIN to TMAX, VCC = VMIN to VMAX, unless otherwise noted. (Note 1)
Parameter
Test Conditions/Comments
Min
Typ
Max
Unit
3.0
3.3
3.6
V
1.4
32
3.0
50
mA
mA
±1.0
±3.0
°C
POWER SUPPLY
Supply Voltage, VCC
Supply Current, ICC
Interface inactive, ADC active
Standby mode
TEMPERATURE−TO−DIGITAL CONVERTER
Local Sensor Accuracy
Resolution
0.25
°C
Remote Diode1 Sensor Accuracy
60°C ≤ TD ≤ 100°C
±0.5
±1.0
°C
Remote Diode2 Sensor Accuracy
60°C ≤ TD ≤ 100°C
±0.5
±1.75
°C
Resolution
Remote Sensor Source Current
High level
Low level
0.125
°C
180
11
mA
OPEN−DRAIN DIGITAL OUTPUTS (THERM, INT, FAN_FAULT, PWM_OUT)
Output Low Voltage, VOL
IOUT = –6.0 mA; VCC = 3.0 V
High−Level Output Leakage Current, IOH
VOUT = VCC; VCC = 3.0 V
http://onsemi.com
3
0.1
0.4
V
1.0
mA
ADM1031
ELECTRICAL CHARACTERISTICS TA = TMIN to TMAX, VCC = VMIN to VMAX, unless otherwise noted. (Note 1)
Parameter
Test Conditions/Comments
Min
Typ
Max
Unit
0.4
V
1.0
mA
OPEN−DRAIN SERIAL DATA BUS OUTPUT (SDA)
Output Low Voltage, VOL
IOUT = –6.0 mA; VCC = 3.0 V
High−Level Output Leakage Current, IOH
VOUT = VCC
0.1
SERIAL BUS DIGITAL INPUTS (SCL, SDA)
2.1
Input High Voltage, VIH
V
Input Low Voltage, VIL
0.8
Hysteresis
500
V
mV
DIGITAL INPUT LOGIC LEVELS (Note 2) (ADD, THERM, TACH1/2)
2.1
Input High Voltage, VIH
V
Input Low Voltage, VIL
0.8
V
DIGITAL INPUT LEAKAGE CURRENT
Input High Current, IIH
VIN = VCC
Input Low Current, IIL
VIN = 0
–1.0
mA
1.0
Input Capacitance, CIN
5.0
mA
pF
FAN RPM−TO−DIGITAL CONVERTER
60°C ≤ TA ≤ 100°C
Accuracy
±6.0
Full−Scale Count
%
255
TACH Nominal Input RPM
Divisor N = 1, Fan Count = 153
Divisor N = 2, Fan Count = 153
Divisor N = 4, Fan Count = 153
Divisor N = 8, Fan Count = 153
Conversion Cycle Time
4400
2200
1100
550
RPM
637
ms
SERIAL BUS TIMING (Note 3)
Clock Frequency, fSCLK
See Figure 2
10
100
Glitch Immunity, tSW
See Figure 2
Bus Free Time, tBUF
See Figure 2
4.7
ms
Start Setup Time, tSU;STA
See Figure 2
4.7
ms
Start Hold Time, tHD;STA
See Figure 2
4.0
ms
Stop Condition Setup Time, tSU;STO
See Figure 2
4.0
ms
SCL Low Time, tLOW
See Figure 2
1.3
ms
SCL High Time, tHIGH
See Figure 2
4.0
50
ms
SCL, SDA Rise Time, tR
See Figure 2
1000
ns
SCL, SDA Fall Time, tF
See Figure 2
300
ns
Data Setup Time, tSU;DAT
See Figure 2
250
ns
Data Hold Time, tHD;DAT
See Figure 2
300
ns
50
ns
1. Typicals are at TA = 25°C and represent most likely parametric norm. Shutdown current typ is measured with VCC = 3.3 V.
2. ADD is a three−state input that can be pulled high, low, or left open−circuit.
3. Timing specifications are tested at logic levels of VIL = 0.8 V for a falling edge and VIH = 2.2 V for a rising edge.
tLOW
tR
tF
tHD:STA
SCL
tHD:STA
tHD:DAT
tHIGH
tSU:STA
tSU:DAT
tSU:STO
SDA
tBUF
P
S
S
Figure 2. Diagram for Serial Bus Timing
http://onsemi.com
4
kHz
P
ADM1031
TYPICAL CHARACTERISTICS
17
10
5
DXP TO GND
0
DXP TO VCC (3.3 V)
–5
–10
–15
–20
15
REMOTE TEMPERATURE ERROR (°C)
REMOTE TEMPERATURE ERROR (°C)
15
13
11
9
7
5
3
1
–1
1
3.3
10
30
VIN = 100mV p−p
100
VIN = 200mV p−p
0
500k
2M
Figure 3. Temperature Error vs. PCB Track
Resistance
10M
100M
400M
110
100
6
90
5
80
4
70
READING (°C)
REMOTE TEMPERATURE ERROR (°C)
6M
Figure 4. Temperature Error vs. Power Supply
Noise Frequency
7
3
VIN = 40mV p−p
2
60
50
40
30
1
20
0
10
VIN = 20mV p−p
–1
0
100k
1M
100M
200M
300M
400M
0
500M
0
10
20
30
FREQUENCY (Hz)
50
60
70
80
90
100
110
Figure 6. Pentium III Temperature Measurement
vs. ADM1031 Reading
1
0
–1
–2
–3
–4
–5
–6
–7
–8
110
100
90
SUPPLY CURRENT (mA)
–9
–10
–11
–12
–13
–14
–15
–16
40
PIII TEMPERATURE (°C)
Figure 5. Temperature Error vs. Common−Mode
Noise Frequency
REMOTE TEMPERATURE ERROR (°C)
4M
FREQUENCY (Hz)
LEAKAGE RESISTANCE (MW)
80
70
VCC = 5.0 V
60
50
40
30
20
VCC = 3.3 V
10
1
2.2
3.3
4.7
10
0
47
22
DXP, DXN CAPACITANCE (nF)
0
1
5
10
25
50
75
100
250
500
750 1000
SCLK FREQUENCY (kHz)
Figure 7. Temperature Error vs. Capacitance
Between D+ and D–
Figure 8. Standby Current vs. Clock Frequency
http://onsemi.com
5
ADM1031
TYPICAL CHARACTERISTICS
7
200
180
6
160
5
4
3
2
1
120
100
80
ADD = Hi−Z
60
ADD = GND
40
ADD = VCC
20
0
–1
140
SUPPLY CURRENT (mA)
REMOTE TEMPERATURE ERROR (°C)
VIN = 30mV p−p
VIN = 20mV p−p
100k
0
1M
100M
200M
0
300M
400M
–20
500M
0
1.1
1.3
1.5
FREQUENCY (Hz)
0.08
0.08
0
0
–0.08
–0.08
–0.16
–0.16
–0.24
–0.24
–0.32
–0.40
–0.48
–0.64
–0.72
–0.72
––0.80
––0.80
80
85
100
105
120
20
0
40
TEMPERATURE (°C)
60
80
85
100
105
120
TEMPERATURE (°C)
Figure 11. Local Sensor Temperature Error
Figure 12. Remote Temperature Sensor Error
1.30
120
110
1.25
100
1.20
90
1.15
TEMPERATURE (°C)
SUPPLY CURRENT (mA)
4.5
2.9
–0.48
–0.56
60
2.5
–0.40
–0.64
40
2.1
–0.32
–0.56
20
1.9
Figure 10. Standby Supply Current vs. Supply
Voltage
ERROR (°C)
ERROR (°C)
Figure 9. Temperature Error vs. Differential−Mode
Noise Frequency
0
1.7
SUPPLY VOLTAGE (V)
1.10
1.05
1.00
0.95
80
70
60
50
40
30
0.90
20
0.85
10
0.80
2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6 4.8 5.0
0
SUPPLY VOLTAGE (V)
0
1
2
3
4
5
6
7
8
9
TIME (Sec)
Figure 13. Supply Current vs. Supply Voltage
Figure 14. Response to Thermal Shock
http://onsemi.com
6
10
ADM1031
Functional Description
defines the range over which auto fan control is provided,
and hence determines the temperature at which the fan is run
at full speed.
The ADM1031 is a temperature monitor and dual PWM
fan controller for microprocessor−based systems. The
device communicates with the system via a serial System
Management Bus (SMBus). The serial bus controller has a
hardwired address pin for device selection (Pin 13), a serial
data line for reading and writing addresses and data (Pin 15),
and an input line for the serial clock (Pin 16). All control and
programming functions of the ADM1031 are performed
over the serial bus. The device also supports Alert Response
Address (ARA).
Serial Bus Interface
Control of the ADM1031 is carried out via the SMBus.
The ADM1031 is connected to this bus as a slave device,
under the control of a master device, for example, the 810
chipset.
The ADM1031 has a 7−bit serial bus address. When the
device is powered up, it does so with a default serial bus
address. The five MSBs of the address are set to 01011; the
two LSBs are determined by the logical state of Pin 13
(ADD). This is a three−state input that can be grounded,
connected to VCC, or left open−circuit to give three different
addresses. The state of the ADD pin is only sampled at
powerup, so changing ADD with power on has no effect
until the device is powered off, then on again.
Internal Registers
Brief descriptions of the ADM1031’s principal internal
registers are given below. For more detailed information on
the function of each register, see Table 14 through Table 29.
Configuration Register
This register controls and configures various functions on
the device.
Table 1. ADD Pin Truth Table
ADD Pin
Address Pointer Register
This register contains the address that selects one of the
other internal registers. When writing to the ADM1031, the
first byte of data is always a register address, which is written
to the address pointer register.
A1
A0
GND
0
0
No Connect
1
0
VCC
0
1
If ADD is left open−circuit, then the default address is
0101110. The facility to make hardwired changes at the
ADD pin allows the user to avoid conflicts with other
devices sharing the same serial bus; for example, if more
than one ADM1031 is used in a system.
Status Registers
These registers provide status of each limit comparison.
Value and Limit Registers
Theses registers store the results of temperature and fan
speed measurements, along with their limit values.
Serial Bus Protocol
1. The master initiates data transfer by establishing a
START condition, defined as a high−to−low
transition on the serial data line SDA while the
serial clock line SCL remains high. This indicates
that an address/data stream follows. All slave
peripherals connected to the serial bus respond to
the START condition, and shift in the next eight
bits, consisting of a 7−bit address (MSB first) plus
an R/W bit that determines the direction of the
data transfer, that is, whether data is written to or
read from the slave device.
The peripheral whose address corresponds to the
transmitted address responds by pulling the data
line low during the low period before the ninth
clock pulse, known as the Acknowledge Bit. All
other devices on the bus now remain idle while the
selected device waits for data to be read from or
written to it. If the R/W bit is a 0, then the master
writes to the slave device. If the R/W bit is a 1,
then the master reads from the slave device.
2. Data is sent over the serial bus in sequences of
nine clock pulses, eight bits of data, followed by
an acknowledge bit from the slave device.
Transitions on the data line must occur during the
low period of the clock signal and remain stable
Fan Speed Configuration Register
This register is used to program the PWM duty cycle for
each fan.
Offset Registers
These registers allow the temperature channel readings to
be offset by a 5−bit twos complement value written to these
registers. These values are automatically added to the
temperature values (or subtracted from if negative). This
allows the systems designer to optimize the system if
required, by adding or subtracting up to 15°C from a
temperature reading.
Fan Characteristics Registers
These registers are used to select the spin−up time, PWM
frequency, and speed range for the fans used.
THERM Limit Registers
These registers contain the temperature values at which
THERM is asserted.
TMIN/TRANGE Registers
These registers are read/write registers that hold the
minimum temperature value below which the fan does not
run when the device is in automatic fan speed control mode.
These registers also hold the temperature range value that
http://onsemi.com
7
ADM1031
internal data register to be written to, which is stored in the
address pointer register. The second data byte is the data to
be written to the internal data register.
during the high period, as a low−to−high transition
when the clock is high can be interpreted as a stop
signal. The number of data bytes that can be
transmitted over the serial bus in a single read or
write operation is limited only by what the master
and slave devices can handle.
3. When all data bytes have been read or written,
stop conditions are established. In write mode, the
master pulls the data line high during the tenth
clock pulse to assert a stop condition. In read
mode, the master device overrides the
acknowledge bit by pulling the data line high
during the low period before the ninth clock pulse.
This is known as No Acknowledge. The master
then takes the data line low during the low period
before the tenth clock pulse, then high during the
tenth clock pulse to assert a stop condition.
Any number of bytes of data can be transferred over the
serial bus in one operation, but it is not possible to mix read
and write in one operation, because the type of operation is
determined at the beginning and cannot subsequently be
changed without starting a new operation.
In the case of the ADM1031, write operations contain
either one byte or two bytes, and read operations contain one
byte, and perform the functions described next.
Reading Data from a Register
When reading data from a register there are two
possibilities:
1. If the ADM1031’s address pointer register value is
unknown or not the desired value, it is first
necessary to set it to the correct value before data
can be read from the desired data register. This is
done by performing a write to the ADM1031 as
before, but only the data byte containing the
register address is sent, as data is not to be written
to the register. This is shown in Figure 16.
A read operation is then performed consisting of
the serial bus address, R/W bit set to 1, followed
by the data byte read from the data register. This is
shown in Figure 17.
2. If the address pointer register is known to be
already at the desired address, data can be read
from the corresponding data register without first
writing to the address pointer register, so Figure 16
can be omitted.
Notes
• Although it is possible to read a data byte from a data
Writing Data to a Register
To write data to one of the device data registers or read
data from it, the address pointer register must be set so that
the correct data register is addressed; data can then be
written to that register or read from it. The first byte of a
write operation always contains an address that is stored in
the address pointer register. If data is to be written to the
device, the write operation contains a second data byte that
is written to the register selected by the address pointer
register.
This is illustrated in Figure 15. The device address is sent
over the bus followed by R/W set to 0. This is followed by
two data bytes. The first data byte is the address of the
•
•
register without first writing to the address pointer
register, if the address pointer register is already at the
correct value, it is not possible to write data to a register
without writing to the address pointer register. This is
because the first data byte of a write is always written
to the address pointer register.
In Figure 15, Figure 16, and Figure 17, the serial bus
address is shown as the default value 01011(A1)(A0),
where A1 and A0 are set by the three−state ADD pin.
The ADM1031 also supports the Read Byte protocol, as
described in the system management bus specification.
1
9
1
9
SCL
0
SDA
1
0
1
1
A1
A0
R/W
D7
D6
D5
D4
D3
D2
D1
D0
ACK. BY
ADM1031
START BY
MASTER
ACK. BY
ADM1031
FRAME 2
ADDRESS POINTER REGISTER BYTE
FRAME 1
SERIAL BUS ADDRESS BYTE
1
9
SCL (CONTINUED)
SDA (CONTINUED)
D7
D6
D5
D4
D3
D2
D1
D0
ACK. BY
ADM1031
STOP BY
MASTER
FRAME 3
DATA BYTE
Figure 15. Writing a Register Address to the Address Pointer Register, then Writing Data to the Selected Register
http://onsemi.com
8
ADM1031
1
9
1
9
SCL
SDA
0
1
0
1
1
A1
A0
R/W
D7
D6
D5
D4
D3
D2
D1
D0
ACK. BY
ADM1031
START BY
MASTER
ACK. BY
ADM1031
FRAME 1
SERIAL BUS ADDRESS BYTE
STOP BY
MASTER
FRAME 2
ADDRESS POINTER REGISTER BYTE
Figure 16. Writing to the Address Pointer Register Only
1
9
1
9
SCL
SDA
0
START BY
MASTER
1
0
1
1
A1
A0
R/W
D7
D6
D5
D4
D3
D2
D1
STOP BY
NO ACK.
BY MASTER MASTER
ACK. BY
ADM1031
FRAME 1
SERIAL BUS ADDRESS BYTE
D0
FRAME 2
DATA BYTE FROM ADM1031
Figure 17. Reading Data from a Previously Selected Register
Alert Response Address
External Measurement
Alert Response Address (ARA) is a feature of SMBus
devices that allows an interrupting device to identify itself
to the host when multiple devices exist on the same bus.
The INT output can be used as an interrupt output or can
be used as an SMBALERT. One or more INT outputs can be
connected to a common SMBALERT line connected to the
master. If a device’s INT line goes low, the following
procedure occurs:
1. SMBALERT is pulled low.
2. Master initiates a read operation and sends the
Alert Response Address (ARA = 0001 100). This
is a general call address that must not be used as a
specific device address.
3. The device whose INT output is low responds to
the alert response address, and the master reads its
device address. The address of the device is now
known and can be interrogated in the usual way.
4. If more than one device’s INT output is low, the
one with the lowest device address has priority, in
accordance with normal SMBus arbitration.
5. Once the ADM1031 has responded to the alert
response address, it resets its INT output.
However, if the error condition that caused the
interrupt persists, then INT is reasserted on the
next monitoring cycle.
The ADM1031 can measure the temperatures of two
external diode sensors or diode−connected transistors,
connected to Pins 9 and 10, and Pins 11 and 12.
These pins are dedicated temperature input channels. The
function of Pin 7 is as a THERM input/output and is used to
flag overtemperature conditions.
The forward voltage of a diode or diode−connected
transistor, operated at a constant current, exhibits a negative
temperature coefficient of about –2 mV/°C. Unfortunately,
the absolute value of VBE, varies from device to device, and
individual calibration is required to null this out. As a result,
the technique is unsuitable for mass production.
The technique used in the ADM1031 is to measure the
change in VBE when the device is operated at two different
currents.
This is given by: DVBE = KT/q × In (N)
where:
K is Boltzmann’s constant.
q is charge on the carrier.
T is absolute temperature in Kelvins.
N is ratio of the two currents.
Figure 18 shows the input signal conditioning used to
measure the output of an external temperature sensor. This
figure shows the external sensor as a substrate transistor,
provided for temperature monitoring on some
microprocessors, but it could equally well be a discrete
transistor.
Temperature Measurement System
Internal Measurement
The ADM1031 contains an on−chip bandgap temperature
sensor. The on−chip ADC performs conversions on the
output of this sensor and outputs the temperature data in
10−bit twos complement format. The resolution of the local
temperature sensor is 0.25°C. The format of the temperature
data is shown in Table 2.
http://onsemi.com
9
ADM1031
The extended temperature resolution for the local and
remote channels is stored in the extended temperature
resolution register (Register 0×06), and is outlined in Table 27.
VDD
I
N× I
IBIAS
REMOTE
SENSING
TRANSISTOR
Table 4. Local Sensor Extended Temperature
Resolution
VOUT+
D+
TO
ADC
D–
BIAS
DIODE
Local Temperature Low Bits
0.00°C
00
0.25°C
01
0.50°C
10
0.75°C
11
VOUT–
LOW−PASS
FILTER
fC = 65kHz
Figure 18. Signal Conditioning
To prevent ground noise interfering with the
measurement, the more negative terminal of the sensor is not
referenced to ground, but biased above ground by an internal
diode at the D– input. If the sensor is used in a very noisy
environment, a capacitor of value up to 1000 pF can be
placed between the D+ and D– inputs to filter the noise.
To measure DVBE, the sensor is switched between
operating currents of I and N × I. The resulting waveform is
passed through a 65 kHz low−pass filter to remove noise,
then to a chopper−stabilized amplifier that performs the
functions of amplification and rectification of the waveform
to produce a dc voltage proportional to DVBE. This voltage
is measured by the ADC to give a temperature output in
11−bit twos complement format. To further reduce the
effects of noise, digital filtering is performed by averaging
the results of 16 measurement cycles. An external
temperature measurement nominally takes 9.6 ms.
If a discrete transistor is used, then the collector is not
grounded, and is linked to the base. If a PNP transistor is
used, the base is connected to the D– input and the emitter
to the D+ input. If an NPN transistor is used, the emitter is
connected to the D– input and the base to the D+ input.
One LSB of the ADC corresponds to 0.125°C, so the
ADM1031 can theoretically measure temperatures from
–127°C to +127.75°C, although –127°C is outside the
operating range for the device. The extended temperature
resolution data format is shown in Table 3 and Table 4.
Table 2. Temperature Data Format − (Local
Temperature and Remote Temperature High Bytes)
Temperature (5C)
Digital Output
−128°C
1000 0000
−125°C
1000 0011
−100°C
1001 1100
−75°C
1011 0101
−50°C
1100 1110
−25°C
1110 0111
−1°C
1111 1111
0°C
0000 0000
+1°C
0000 0001
+10°C
0000 1010
+25°C
0001 1001
+50°C
0011 0010
+75°C
0100 1011
+100°C
0110 0100
+125°C
0111 1101
+127°C
0111 1111
Layout Considerations
Digital boards can be electrically noisy environments and
care must be taken to protect the analog inputs from noise,
particularly when measuring the very small voltages from a
remote diode sensor. The following precautions should be
taken:
1. Place the ADM1031 as close as possible to the
remote sensing diode. Provided that the worst
noise sources such as clock generators,
data/address buses, and CRTs are avoided, this
distance can be 4 to 8 inches.
2. Route the D+ and D– tracks close together, in
parallel, with grounded guard tracks on each side.
Provide a ground plane under the tracks if possible.
3. Use wide tracks to minimize inductance and
reduce noise pickup. Ten mil track minimum
width and spacing is recommended.
Table 3. Remote Sensor Extended Temperature
Resolution
Extended Resolution
Remote Temperature Low Bits
0.000°C
000
0.125°C
001
0.250°C
010
0.375°C
011
0.500°C
100
0.625°C
101
0.750°C
110
0.875°C
Extended Resolution
GND
10MIL
10MIL
D+
10MIL
10MIL
D–
10MIL
10MIL
GND
111
10MIL
Figure 19. Arrangement of Signal Tracks
http://onsemi.com
10
ADM1031
4. Try to minimize the number of copper/solder
joints, which can cause thermocouple effects.
Where copper/solder joints are used, make sure
that they are in both the D+ and D– path and at the
same temperature.
Thermocouple effects should not be a major problem as
1°C corresponds to about 200 mV, and thermocouple
voltages are about 3 mV/°C of temperature difference.
Unless there are two thermocouples with a big temperature
differential between them, thermocouple voltages should be
much less than 200 mV.
5. Place a 0.1 mF bypass capacitor close to the
ADM1031.
6. If the distance to the remote sensor is more than
8 inches, the use of twisted pair cable is
recommended. This works up to about 6 to 12 feet.
7. For extra long distances (up to 100 feet), use a
shielded twisted pair cable, such as the Belden #8451
microphone cable. Connect the twisted pair to D+
and D– and the shield to GND close to the
ADM1031. Leave the remote end of the shield
unconnected to avoid ground loops.
Because the measurement technique uses switched
current sources, excessive cable and/or filter capacitance
can affect the measurement. When using long cables, the
filter capacitor C1 can be reduced or removed. In any case
the total shunt capacitance should not exceed 1000 pF.
Cable resistance can also introduce errors. One ohm series
resistance introduces about 0.5°C error.
register) is cleared to 0, then the fans do not run
full−speed. The THERM limit can be programmed
at a lower temperature than the high temperature
limit. This allows the system to run in silent mode,
where the CPU can be throttled while the cooling
fan is off. If the temperature continues to increase,
and exceeds the high temperature limit, an INT is
generated. Software can then decide whether the
fan should run to cool the CPU. This allows the
system to run in silent mode.
3. If the THERM−to−Fan Enable bit is set to 1, then
the fan runs full−speed whenever THERM is
asserted low. In this case, both throttling and active
cooling take place. If the high temperature limit is
programmed to a lower value than the THERM
limit, exceeding the high temperature limit asserts
INT low. Software could change the speed of the
fan depending on temperature readings. If the
temperature continues to increase and exceeds the
THERM limit, THERM asserts low to throttle the
CPU and the fan runs full−speed. This allows the
system to run in performance mode, where active
cooling takes place and the CPU is only throttled
at high temperature.
Using the high temperature limit and the THERM limit in
this way allows the user to gain maximum performance from
the system by only slowing it down, should it be at a critical
temperature.
Although the ADM1031 does not have a dedicated
interrupt mask register, clearing the appropriate enable bits
in Configuration Register 2 clears the appropriate interrupts
and masks out future interrupts on that channel. Disabling
interrupt bits prevents out−of−limit conditions from
generating an interrupt or setting a bit in the status registers.
Addressing the Device
ADD (Pin 13) is a three−state input. It is sampled, on
powerup to set the lowest two bits of the serial bus address.
Up to three addresses are available to the systems designer
via this address pin. This reduces the likelihood of conflicts
with other devices attached to the system management bus.
Using THERM as an Input
The THERM pin is an open−drain input/output pin. When
used as an output, it signals overtemperature conditions.
When asserted low as an output, the fan is driven full−speed
if the THERM−to−Fan Enable bit is set to 1 (Bit 7 of Register
0×3F). When THERM is pulled low as an input, the THERM
bit (Bit 7) of Status Register 2 is set to 1, and the fans are
driven full−speed. Note that the THERM−to−Fan Enable bit
has no effect whenever THERM is used as an input. If
THERM is pulled low as an input, and the THERM−to−Fan
Enable bit = 0, then the fans are still driven full−speed. The
THERM−to−Fan Enable bit only affects the behavior of
THERM when used as an output.
The Interrupt System
The ADM1031 has two interrupt outputs, INT and
THERM. These have different functions. INT responds to
violations of software programmed temperature limits and
is maskable.
THERM is intended as a “fail−safe” interrupt output that
cannot be masked. If the temperature is below the low
temperature limit, the INT pin is asserted low to indicate an
out−of−limit condition. If the temperature exceeds the high
temperature limit, the INT pin is also asserted low. A third
limit, THERM limit, can be programmed into the device to
set the temperature limit above which the overtemperature
THERM pin is asserted low. The behavior of the high limit
and THERM limit is as follows:
1. Whenever the temperature measured exceeds the
high temperature limit, the INT pin is asserted low.
2. If the temperature exceeds the THERM limit, the
THERM output asserts low. This can be used to
throttle the CPU clock. If the THERM−to−Fan
Enable bit (Bit 7 of THERM behavior/revision
Status Registers
All out−of−limit conditions are flagged by status bits in
Status Register 1 (0×02) and Status Register 2 (0×03). Bit 0
(Alarm Speed) and Bit 1 (Fan Fault) of Status Register 1,
once set, can be cleared by reading Status Register 1. Once
the alarm speed bit is cleared, this bit is not reasserted on the
next monitoring cycle even if the condition still persists.
This bit can be reasserted only if the fan is no longer at alarm
http://onsemi.com
11
ADM1031
Automatic Fan Speed Control
speed. Bit 1 (Fan Fault) is set whenever a fan tach failure is
detected. Once cleared, it reasserts on subsequent fan tach
failures.
Bit 2 and Bit 3 of Status Register 1 and Status Register 2
are the Remote 1 and Remote 2 Temperature High and Low
status bits. Exceeding the high or low temperature limits for
the external channel sets these status bits. Reading the status
register clears these bits. However, these bits are reasserted
if the out−of−limit condition still exists on the next
monitoring cycle. Bit 6 and Bit 7 are the Local Temperature
High and Low status bits. These behave exactly the same as
the Remote Temperature High and Low status bits. Bit 4 of
Status Register 1 indicates that the Remote Temperature
THERM limit has been exceeded. This bit gets cleared on a
read of Status Register 1 (see Figure 20). Bit 5 indicates a
remote diode error. This bit is a 1 if a short or open is detected
on the remote temperature channel on powerup. If this bit is
set to 1 on powerup, it cannot be cleared. Bit 6 of Status
Register 2 (0×03) indicates that the Local THERM limit has
been exceeded. This bit is cleared on a read of Status
Register 2. Bit 7 indicates that THERM has been pulled low
as an input. This bit can also be cleared on a read of Status
Register 2.
The ADM1031 has a local temperature channel and two
remote temperature channels, which can be connected to an
on−chip diode−connected transistor on a CPU. These three
temperature channels can be used as the basis for an
automatic fan speed control loop to drive fans using pulse
width modulation (PWM).
How Does the Control Loop Work?
The automatic fan speed control loop is shown in Figure 21.
MAX
SPIN−UP FOR SECONDS
FAN
SPEED
MIN
TMIN
TMAX = TMIN + TRANGE
TEMPERATURE
THERM LIMIT
Figure 21. Automatic Fan Speed Control Loop
TMIN is the temperature at which the fan should switch on
and run at minimum speed. The fan only turns on once the
temperature being measured rises above the TMIN value
programmed. The fan spins up for a predetermined time
(default = 2 seconds). See the Fan Spin−Up section for more
details.
TRANGE is the temperature range over which the
ADM1031 automatically adjusts the fan speed. As the
temperature increases beyond TMIN, the PWM_OUT duty
cycle increases accordingly. The TRANGE parameter
actually defines the fan speed vs. temperature slope of the
control loop.
TMAX is the temperature at which the fan is at its
maximum speed. At this temperature, the PWM duty cycle
driving the fan is 100%. TMAX is given by TMIN + TRANGE.
Since this parameter is the sum of the TMIN and TRANGE
parameters, it does not need to be programmed into a register
on−chip.
A hysteresis value of 5°C is included in the control loop
to prevent the fan continuously switching on and off if the
temperature is close to TMIN. The fan continues to run until
the temperature drops 5°C below TMIN.
Figure 22 shows the different control slopes determined
by the TRANGE value chosen, and programmed into the
ADM1031. TMIN is set to 0°C to start all slopes from the
same point. The figure shows how changing the TRANGE
value affects the PWM duty cycle vs. temperature slope.
5°
TEMP
THERM
INT REARMED
INT
STATUS REG. READ
Figure 20. Operation of THERM and INT Signals
Figure 20 shows the interaction between INT and
THERM. Once a critical temperature THERM limit is
exceeded, both INT and THERM assert low. Reading the
status registers clears the interrupt and the INT pin goes
high. However, the THERM pin remains asserted until the
measured temperature falls 5°C below the exceeded
THERM limit. This feature can be used to CPU throttle or
drive a fan full speed for maximum cooling. Note that the
INT pin for that interrupt source is not rearmed until the
temperature has fallen below the THERM limit –5°C. This
prevents unnecessary interrupts from tying up valuable CPU
resources.
Fan Control Modes of Operation
The ADM1031 has four different modes of operation.
These modes determine the behavior of the system.
1. Automatic Fan Speed Control Mode.
2. Filtered Automatic Fan Speed Control Mode.
3. PWM Duty Cycle Select Mode (directly sets fan
speed under software control).
4. RPM Feedback Mode.
http://onsemi.com
12
ADM1031
Table 5. Fan Spin−Up Times
100
Bits 2:0
PWM DUTY CYCLE (%)
93
87
80
73
66
60
TRANGE = 5°C
TRANGE = 10°C
TRANGE = 20°C
TRANGE = 40°C
TRANGE = 80°C
53
47
40
33
0 5 10
TMIN
20
40
60
80
TMAX = TMIN + TRANGE
000
200 ms
001
400 ms
010
600 ms
011
800 ms
100
1 sec
101
2 sec (Default)
110
4 sec
111
8 sec
Once the automatic fan speed control loop parameters
have been chosen, the ADM1031 device can be
programmed. The ADM1031 is placed into automatic fan
speed control mode by setting Bit 7 of Configuration
Register 1 (Register 0×00). The device powers up in
automatic fan speed control mode by default. The control
mode offers further flexibility in that the user can decide
which temperature channel/channels control each fan.
TEMPERATURE (°C)
Figure 22. PWM Duty Cycle vs. Temperature Slope
(TRANGE)
Figure 23 shows how, for a given TRANGE, changing the
TMIN value affects the loop. Increasing the TMIN value
increases the TMAX (temperature at which the fan runs full
speed) value, since TMAX = TMIN + TRANGE. Note, however,
that the PWM duty cycle vs. temperature slope remains
exactly the same. Changing the TMIN value merely shifts the
control slope. The TMIN can be changed in increments of 4°C.
Table 6. Auto Mode Fan Behavior
Bits 6, 5
Control Operation (Configuration Register 1)
00
Remote Temperature 1 Controls Fan 1
Remote Temperature 2 Controls Fan 2
93
01
Remote Temperature 1 Controls Fan 1 and 2
87
10
Remote Temperature 2 Controls Fan 1 and 2
80
11
Maximum Speed Calculated by Local and Remote
Temperature Channels Controls Fans 1 and 2
100
PWM DUTY CYCLE (%)
Spin−Up Time
(Fan Characteristics Registers 1, 2)
73
66
When Bit 5 and Bit 6 of Configuration Register 1 are both
set to 1, increased flexibility is offered. The local and remote
temperature channels can have independently programmed
control loops with different control parameters. Whichever
control loop calculates the fastest fan speed based on the
temperature being measured, drives the fans.
Figure 24 and Figure 25 show how the fan’s PWM duty
cycle is determined by two independent control loops. This
is the type of auto mode fan behavior seen when Bit 5 and
Bit 6 of Configuration Register 1 are set to 11. Figure 24
shows the control loop for the local temperature channel. Its
TMIN value has been programmed to 20°C, and its TRANGE
value is 40°C. The local temperature’s TMAX is thus 60°C.
Figure 25 shows the control loop for the remote temperature
channel. Its TMIN value has been set to 0°C, while its
TRANGE = 80°C. Therefore, the remote temperature’s TMAX
value is 80°C.
Consider if both temperature channels measure 40°C.
Both control loops calculate a PWM duty cycle of 66%.
Therefore, the fan is driven at 66% duty cycle. If both
temperature channels measure 20°C, the local channel
calculates 33% PWM duty cycle, while the Remote 1
channel calculates 50% PWM duty cycle. Thus, the fans are
driven at 50% PWM duty cycle. Consider the local
60
53
47
40
33
0
TMIN
TRANGE = 40°C
20
40
TEMPERATURE (°C)
60
80
TMAX = TMIN + TRANGE
Figure 23. Effect of Increasing TMIN Value on
Control Loop
Fan Spin−Up
As mentioned in the How Does the Control Loop Work?
section, once the temperature being measured exceeds the
TMIN value programmed, the fan turns on at minimum speed
(default = 33% duty cycle). However, the problem with fans
being driven by PWM is that 33% duty cycle is not enough
to reliably start the fan spinning. The solution is to spin the
fan up for a predetermined time, and once the fan has spun
up, its running speed can be reduced in line with the
temperature being measured.
The ADM1031 allows fan spin−up times between 200 ms
and 8 seconds. Bits <2:0> of Fan Characteristics Register 1
(Register 0×20) and Fan Characteristic Register 2 (Register
0×21) program the fan spin−up times.
http://onsemi.com
13
ADM1031
Programming the Automatic Fan Speed Control Loop
temperature measuring 60°C while the Remote 1
temperature is measuring 70°C. The PWM duty cycle
calculated by the local temperature control loop is 100%
(because the temperature = TMAX). The PWM duty cycle
calculated by the Remote 1 temperature control loop at 70°C
is approximately 90%. Therefore, the fan runs full−speed
(100% duty cycle). Remember, that the fan speed is based on
the fastest speed calculated, and is not necessarily based on
the highest temperature measured. Depending on the control
loop parameters programmed, a lower temperature on one
channel, can actually calculate a faster speed than a higher
temperature on the other channel.
1. Program a value for TMIN.
2. Program a value for the slope TRANGE.
3. TMAX = TMIN + TRANGE.
4. Program a value for fan spin−up time.
5. Program the desired automatic fan speed control
mode behavior, that is, which temperature channel
controls the fan.
6. Select automatic fan speed control mode by setting
Bit 7 of Configuration Register 1.
Other Control Loop Parameters
It should be noted that changing the minimum PWM duty
cycle affects the control loop behavior.
Slope 1 of Figure 26 shows TMIN set to 0°C and the
TRANGE chosen is 40°C. In this case, the fan’s PWM duty
cycle varies over the range 33% to 100%. The fan runs
full−speed at 40°C. If the minimum PWM duty cycle at
which the fan runs at TMIN is changed, its effect can be seen
on Slope 2 and Slope 3. Take Case 2, where the minimum
PWM duty cycle is reprogrammed from 33% (default) to
53%.
100
PWM DUTY CYCLE (%)
93
87
80
73
66
60
53
47
40
0
20
TMIN
40
93
60
TMAX = TMIN + TRANGE
LOCAL TEMPERATURE ( °C)
PWM DUTY CYCLE (%)
33
100
TRANGE = 40°C
Figure 24. Maximum Speed Calculated by Local
Temperature Control Loop Drives Fan
100
PWM DUTY CYCLE (%)
93
3
73
66
2
60
1
53
40
80
TRANGE = 40°C
33
0
TMIN
73
66
16
28
40
60
TEMPERATURE (°C)
Figure 26. Effect of Changing Minimum Duty Cycle
on Control Loop with Fixed TMIN and TRANGE Values
60
53
The fan actually reaches full speed at a much lower
temperature, 28°C. Case 3 shows that when the minimum
PWM duty cycle is increased to 73%, the temperature at
which the fan runs full speed is 16°C. Therefore, the effect
of increasing the minimum PWM duty cycle, with a fixed
TMIN and fixed TRANGE, is that the fan actually reaches full
speed (TMAX) at a lower temperature than TMIN + TRANGE.
47
40
0
TMIN
80
47
87
33
87
TRANGE = 80°C
20
40
70
80
TMAX = TMIN + TRANGE
REMOTE TEMPERATURE ( °C)
Figure 25. Maximum Speed Calculated by Local
Temperature Control Loop Drives Fan
How can TMAX be calculated?
In automatic fan speed control mode, the register that
holds the minimum PWM duty cycle at TMIN, is the fan
speed configuration register (Register 0×22). Table 7 shows
the relationship between the decimal values written to the
fan speed configuration register and PWM duty cycle
obtained.
http://onsemi.com
14
ADM1031
TMAX = 0 + ((100% DC – 33% DC) × 40/10)
TMAX = 0 + ((15 – 5) × 4) = 40
TMAX = 40°C (as seen on Slope 1 of Figure 26)
Table 7. Programming PWM Duty Cycle
Decimal Value
PWM Duty Cycle
00
0%
01
7%
02
14%
03
20%
04
27%
05
33% (Default)
06
40%
07
47%
08
53%
09
60%
10 (0×0A)
67%
11 (0×0B)
73%
12 (0×0C)
80%
13 (0×0D)
87%
14 (0×0E)
93%
15 (0×0F)
100%
In this case, since the minimum duty cycle is the default
33%, the equation for TMAX reduces to:
TMAX = TMIN + ((Max DC – Min DC) × TRANGE/10)
TMAX = TMIN + ((15 – 5) × TRANGE/10)
TMAX = TMIN + (10 × TRANGE/10)
TMAX = TMIN + TRANGE
Relevant Registers for Automatic Fan Speed Control
Mode
Register 0y00 Configuration Register 1
<7> Logic 1 selects automatic fan speed control, Logic 0
selects software control (Default = 1).
<6:5> 00 = Remote Temp 1 controls Fan 1, Remote Temp 2
controls Fan 2.
01 = Remote Temp 1 controls Fan 1 and Fan 2
10 = Remote Temp 2 controls Fan 1 and Fan 2
11 = Fastest Calculated Speed controls Fan 1 and 2
The temperature at which the fan runs full−speed (100%
duty cycle) is given by:
TMAX = TMIN + ((Max DC – Min DC) × TRANGE/10)
where:
TMAX = Temperature at which fan runs full−speed.
TMIN = Temperature at which fan turns on.
Max DC = Maximum duty cycle (100%) = 15 decimal.
Min DC = Duty cycle at TMIN, programmed in to fan speed
configuration register (default = 33% = 5 decimal).
TRANGE = PWM duty cycle vs. temperature slope.
Register 0y20, 0y21 Fan Characteristics Registers 1, 2
<2:0> Fan X Spin−Up Time.
000 = 200 ms
001 = 400 ms
010 = 600 ms
011 = 800 ms
100 = 1 sec
101 = 2 sec (Default)
110 = 4 sec
111 = 8 sec
<5:3> PWM Frequency Driving the Fan.
000 = 11.7 Hz
001 = 15.6 Hz
010 = 23.4 Hz
011 = 31.25 Hz (Default)
100 = 37.5 Hz
101 = 46.9 Hz
110 = 62.5 Hz
111 = 93.5 Hz
<7:6> Speed Range N; defines the lowest fan speed that can
be measured by the device.
00 = 1: Lowest Speed = 2647 RPM
01 = 2: Lowest Speed = 1324 RPM
10 = 4: Lowest Speed = 662 RPM
11 = 8: Lowest Speed = 331 RPM
Example 1
TMIN = 0°C, TRANGE = 40°C
Min DC = 53% = 8 decimal (Table 7)
Calculate TMAX.
TMAX = TMIN + ((Max DC − Min DC) × TRANGE/10)
TMAX = 0 + ((100% DC − 53% DC) × 40/10)
TMAX = 0 + ((15 − 8) × 4) = 28
TMAX = 28°C (as seen on Slope 2 of Figure 26)
Example 2
TMIN = 0°C, TRANGE = 40°C
Min DC = 73% = 11 decimal (Table 7)
Calculate TMAX.
TMAX = TMIN + ((Max DC – Min DC) × TRANGE/10)
TMAX = 0 + ((100% DC – 73% DC) × 40/10)
TMAX = 0 + ((15 – 11) × 4) = 16
TMAX = 16°C (as seen on Slope 3 of Figure 26)
Register 0y22 Fan Speed Configuration Register
<3:0> Min Speed: This nibble contains the speed at which
the fan runs when the temperature is at TMIN. The default is
0×05, meaning that the fan runs at 33% duty cycle when the
temperature is at TMIN.
<7:4> Min Speed: Determines the minimum PWM cycle for
Fan 2 in automatic fan speed control mode.
Example 3
TMIN = 0°C, TRANGE = 40°C
Min DC = 33% = 5 decimal (Table 7)
Calculate TMAX.
TMAX = TMIN + ((Max DC – Min DC) × TRANGE/10)
http://onsemi.com
15
ADM1031
Register 0y24 Local Temperature TMIN/TRANGE
Filtered Control Mode
The automatic fan speed control loop reacts
instantaneously to changes in temperature, that is, the PWM
duty cycle responds immediately to temperature change. In
certain circumstances, we do not want the PWM output to
react instantaneously to temperature changes. If significant
variations in temperature are found in a system, the fan
speed changes, which could be obvious to someone in close
proximity. One way to improve the system’s acoustics
would be to slow down the loop so that the fan ramps slowly
to its newly calculated fan speed. This also ensures that
temperature transients are effectively ignored, and the fan’s
operation is smooth.
There are two means by which to apply filtering to the
automatic fan speed control loop. The first method is to ramp
the fan speed at a predetermined rate, to its newly calculated
value instead of jumping directly to the new fan speed. The
second approach involves changing the on−chip ADC
sample rate, to change the number of temperature readings
taken per second.
The filtered mode on the ADM1031 is invoked by setting
Bit 0 of the fan filter register (Register 0×23) for Fan 1 and
Bit 1 for Fan 2. Once the fan filter register has been written
to, and all other control loop parameters (such as TMIN,
TRANGE) have been programmed, the device can be placed
into automatic fan speed control mode by setting Bit 7 of
Configuration Register 1 (Register 0×00) to 1.
<7:3> Local Temperature TMIN. These bits set the
temperature at which the fan turns on when under auto fan
speed control. TMIN can be programmed in 4°C increments.
00000 = 0°C
00001 = 4°C
00010 = 8°C
00011 = 12°C
|
|
01000 = 32°C (Default)
|
|
11110 = 120°C
11111 = 124°C
<2:0> Local Temperature TRANGE. This nibble sets the
temperature range over which automatic fan speed control
takes place.
000 = 5°C
001 = 10°C
010 = 20°C
011 = 40°C
100 = 80°C
Register 0y25, 0y26 Remote 1, 2 Temperature
TMIN/TRANGE
<7:3> Remote Temperature TMIN. Sets the temperature at
which the fan switches on based on Remote X Temperature
Readings.
00000 = 0°C
00001 = 4°C
00010 = 8°C
00011 = 12°C
|
|
01100 = 48°C
|
|
11110 = 120°C
11111 = 124°C
<2:0> Remote Temperature TRANGE. This nibble sets the
temperature range over which the fan is controlled based on
remote temperature readings.
000 = 5°C
001 = 10°C
010 = 20°C
011 = 40°C
100 = 80°C
Effect of Ramp Rate on Filtered Mode
Bits <6:5> of the fan filter register determine the ramp rate
in filtered mode. The PWM_OUT signal driving the fan has
a period, T, given by the PWM_OUT drive frequency, f,
since T = 1/f. For a given PWM period, T, the PWM period
is subdivided in to 240 equal time slots. One time slot
corresponds to the smallest possible increment in PWM duty
cycle. A PWM signal of 33% duty cycle is thus high for 1/3
× 240 time slots and low for 2/3 × 240 time slots. Therefore,
33% PWM duty cycle corresponds to a signal that is high for
80 time slots and low for 160 time slots.
PWM_OUT
33% DUTY
CYCLE
80 TIME
SLOTS
160 TIME
SLOTS
PWM OUTPUT
(ONE PERIOD =
240 TIME SLOTS
Figure 27. 33% PWM Duty Cycle Presented
in Time Slots
The ramp rates in filtered mode are selectable between 1,
2, 4, and 8. The ramp rates are actually discrete time slots.
For example, if the ramp rate = 8, then eight time slots are
added to the PWM_OUT high duty cycle each time the
PWM_OUT duty cycle needs to be increased. Figure 28
shows how the filtered mode algorithm operates.
http://onsemi.com
16
ADM1031
140
120
120
100
RTEMP
100
80
60
60
PWM DUTY CYCLE
40
40
DECREMENT
PREVIOUS
PWM VALUE
BY RAMP
RATE
20
20
YES
0
INCREMENT
PREVIOUS PWM
VALUE BY RAMP
RATE
0
12
TIME (s)
0
Figure 29. Filtered Mode with Ramp Rate = 8
Figure 30 shows how changing the ramp rate from 8 to 4
affects the control loop. The overall response of the fan is
slower. Because the ramp rate is reduced, it takes longer for
the fan to achieve full running speed. In this case, it took
approximately 22 seconds for the fan to reach full speed.
Figure 28. Filtered Mode Algorithm
The filtered mode algorithm calculates a new PWM duty
cycle based on the temperature measured. If the new PWM
duty cycle value is greater than the previous PWM value, the
previous PWM duty cycle value is incremented by either 1,
2, 4, or 8 time slots (depending on the setting of bits <6:5>
of the fan filter register). If the new PWM duty cycle value
is less than the previous PWM value, the previous PWM
duty cycle is decremented by 1, 2, 4, or 8 time slots. Each
time the PWM duty cycle is incremented or decremented, it
is stored as the previous PWM duty cycle for the next
comparison.
100
RTEMP (°C)
80
60
0.416%
2
0.833%
4
1.66%
8
3.33%
PWM DUTY CYCLE
60
40
40
20
0
20
0
22
TIME (s)
0
Figure 30. Filtered Mode with Ramp Rate = 4
Figure 31 shows the PWM output response for a ramp rate
of 2. In this instance the fan took about 54 seconds to reach
full running speed.
Table 8. Effect of Ramp Rates on PWM_OUT
1
RTEMP
80
A ramp rate of 1 corresponds to one time slot, which is
1/240 of the PWM period. In filtered auto fan speed control
mode, incrementing or decrementing by 1 changes the PWM
output duty cycle by 0.416%.
PWM Duty Cycle Change
120
110
What does an increase of 1, 2, 4, or 8 time slots
actually mean in terms of PWM duty cycle?
Ramp Rate
140
120
PWM DUTY CYCLE (%)
NO
80
120
140
120
100
RTEMP
100
RTEMP (°C)
So programming a ramp rate of 1, 2, 4, or 8 simply
increases or decreases the PWM duty cycle by the amounts
shown in Table 8, depending on whether the temperature is
increasing or decreasing.
Figure 29 shows remote temperature plotted against
PWM duty cycle for filtered mode. The ADC sample rate is
the highest sample rate; 11.25 kHz. The ramp rate is set to
8, which would correspond to the fastest ramp rate. With
these settings, it took approximately 12 seconds to go from
0% duty cycle to 100% duty cycle (full−speed). The TMIN
value = 32°C and the TRANGE = 80°C. Even though the
temperature increased very rapidly, the fan gradually ramps
up to full speed.
80
80
60
60
PWM DUTY CYCLE
40
40
20
20
0
0
TIME (s)
54
0
Figure 31. Filtered Mode with Ramp Rate = 2
http://onsemi.com
17
PWM DUTY CYCLE (%)
IS NEW
PWM VALUE >
PREVIOUS
VALUE?
RTEMP (°C)
CALCULATE
NEW PWM
DUTY CYCLE
PWM DUTY CYCLE (%)
READ
TEMPERATURE
ADM1031
Finally, Figure 32 shows how the control loop reacts to
temperature with the slowest ramp rate. The ramp rate is set
to 1, while all other control parameters remain the same.
With the slowest ramp rate selected, it took 112 seconds for
the fan to reach full speed.
140
120
120
RTEMP
100
80
80
60
60
PWM DUTY CYCLE
40
RTEMP (°C)
PWM DUTY CYCLE (%)
110
Table 9. Temperature Updates per Second
40
20
0
the ADC sample rate, the more temperature samples are
obtained per second. One way to apply filtering to the
control loop is to slow down the ADC sampling rate. This
means that the number of iterations of the filtered mode
algorithm per second is effectively reduced. If the number
of temperature measurements per second is reduced, how
often the PWM_OUT signal controlling the fan is updated
is also reduced.
Bits <4:2> of the fan filter register (Register 0×23) set the
ADC sample rate. The default ADC sample rate is 1.4 kHz.
The ADC sample rate is selectable from 87.5 Hz to 11.2 kHz.
Table 9 shows how many temperature samples are obtained
per second, for each of the ADC sample rates.
ADC Sample Rate
Temperature Updates/Sec
87.5 Hz
0.0625
175 Hz
0.125
20
0
TIME (s)
112
0
Figure 32. Filtered Mode with Ramp Rate = 1
As can be seen from Figure 29 through Figure 32, the rate
at which the fan reacts to temperature change is dependent
on the ramp rate selected in the fan filter register. The higher
the ramp rate, the faster the fan reaches the newly calculated
fan speed.
Figure 33 shows the behavior of the PWM output as
temperature varies. As the temperature rises, the fan speed
ramps up. Small drops in temperature do not affect the
ramp−up function because the newly calculated fan speed is
still higher than the previous PWM value. The filtered mode
allows the PWM output to be made less sensitive to
temperature variations. This is dependent on the ramp rate
selected and the ADC sample rate programmed into the fan
filter register.
50
RTEMP
70
50
40
40
30
30
20
20
10
10
0
0
1 (Default)
2.8 kHz
2
5.6 kHz
4
11.2 kHz
8
<7> Spin−up Disable: When this bit is set to 1, fan spin−up
is disabled. (Default = 0)
<6:5> Ramp Rate: These bits set the ramp rate for filtered
mode.
00 = 1 (0.416% Duty Cycle Change)
01 = 2 (0.833% Duty Cycle Change)
10 = 4 (1.66% Duty Cycle Change)
11 = 8 (3.33% Duty Cycle Change)
<4:2> ADC Sample Rate.
000 = 87.5 Hz
001 = 175 Hz
010 = 350 Hz
011 = 700 Hz
100 = 1.4 kHz (Default)
101 = 2.8 kHz
110 = 5.6 kHz
111 = 11.2 kHz
<1> Fan 2 Filter Enable: When this bit is set to 1, it enables
filtering on Fan 2. Default = 0.
<0> Fan 1 Filter Enable: When this bit is set to 1, it enables
filtering on Fan 1. Default = 0.
60
60
1.4 kHz
Register 0y23 Fan Filter Register
RTEMP (°C)
PWM DUTY CYCLE (%)
70
PWM DUTY CYCLE
0.5
In addition to the registers used to program the normal
automatic fan speed control mode, the following register
needs to be programmed.
80
80
0.25
Relevant Registers for Filtered Automatic Fan Speed
Control Mode
90
90
350 Hz
700 kHz
TIME (s)
Figure 33. How Fan Reacts to Temperature Variation
in Filtered Mode
Effect of ADC Sample Rate on Filtered Mode
The second way to change the filtered mode
characteristics is to adjust the ADC sample rate. The faster
http://onsemi.com
18
ADM1031
Programming the Filtered Automatic Fan Speed
Control Loop
RPM Feedback Mode
The second method of fan speed control under software is
RPM feedback mode. This involves programming the
desired fan RPM value to the device to set fan speed. The
advantages include a very tightly maintained fan RPM over
the fan’s life, and virtually no acoustic pollution due to fan
speed variation.
Fans typically have manufacturing tolerances of ±20%,
meaning a wide variation in speed for a typical batch of
identical fan models. If it is required that all fans run at
exactly 5000 RPM, it can be necessary to specify fans with
a nominal fan speed of 6250 RPM. However, many of these
fans run too fast and make excess noise. A fan with nominal
speed of 6250 RPM could run as fast as 7000 RPM at 100%
PWM duty cycle. RPM mode allows all of these fans to be
programmed to run at the desired RPM value.
Clearing Bit 7 of Configuration Register 1 (Register
0×00) to 0 places the ADM1031 under software control.
Once under software control, the device can be placed into
RPM feedback mode by writing to Bit 5 and Bit 6 of
Configuration Register 1. Writing a 1 to Bit 5 and Bit 6
selects RPM feedback mode for each fan.
Once RPM feedback mode has been selected, the required
fan RPM can be written to the fan tach high limit registers
(0×10, 0×11). The RPM feedback mode function allows a fan
RPM value to be programmed into the device, and the
ADM1031 maintains the selected RPM value by monitoring
the fan tach and speeding up the fan as necessary, should the
fan start to slow down. Conversely, should the fan start to
speed up due to aging, the RPM feedback slows the fan down
to maintain the correct RPM speed. The value to be
programmed into each fan tach high limit register is given by:
Count = (f × 60)/R × N
where:
f = 11.25 kHz
R = desired RPM value
N = speed range; must be set to 2
The speed range, N, really determines what the slowest
fan speed measured can be before generating an interrupt.
The slowest fan speed is measured when the count value
reaches 255.
Since N = 2
Count = (f × 60)/R × N
R = (f × 60)/Count × N
R = (11250 × 60)/255 × 2
R = (675000)/510
R = 1324 RPM, fan fail detect speed
1. Program a value for TMIN.
2. Program a value for the slope TRANGE.
3. TMAX = TMIN + TRANGE.
4. Program a value for fan spin−up time.
5. Program the desired automatic fan speed control
mode behavior, that is, which temperature channel
controls the fan.
6. Program a ramp rate for the filtered mode.
7. Program the ADC sample rate in the fan filter
register.
8. Set Bit 0 to enable fan filtered mode for Fan 1.
9. Set Bit 1 to enable the fan filtered mode for Fan 2.
10. Select automatic fan speed control mode by setting
Bit 7 of Configuration Register 1.
PWM Duty Cycle Select Mode
The ADM1031 can operate under software control by
clearing Bit 7 of Configuration Register 1 (Register 0×00).
This allows the user to directly control PWM duty cycle for
each fan.
Clearing Bit 5 and Bit 6 of Configuration Register 1
allows fan control by varying PWM duty cycle. Values of
duty cycle between 0% and 100% can be written to the fan
speed configuration register (0×22) to control the speed of
each fan. Table 10 shows the relationship between hex
values written to the fan speed configuration register and
PWM duty cycle obtained.
Table 10. PWM Duty Cycle Select Mode
Hex Value
PWM Duty Cycle
00
0%
01
7%
02
14%
03
20%
04
27%
05
33%
06
40%
07
47%
08
53%
09
60%
0A
67%
0B
73%
0C
80%
0D
87%
0E
93%
Programming RPM Values in RPM Feedback Mode
0F
100%
Rather than writing a value such as 5000 to a 16−bit
register, an 8−bit count value is programmed instead. The
count to be programmed is given by:
Count = (f × 60)/R × N
where:
f = 11.25 kHz
R = desired RPM value
N = speed range 2
Bits <3:0> set the PWM duty cycle for Fan 1; Bits <7:4>
set the PWM duty cycle for Fan 2.
http://onsemi.com
19
ADM1031
Example 1:
To find the lowest RPM value allowed for a given fan, do
the following:
1. Run the fan at 53% PWM duty cycle in software
mode. Clear Bit 5 and Bit 7 of Configuration
Register 1 (Register 0×00) to enter PWM duty
cycle mode. Write 0×08 to the fan speed
configuration register (Register 0×22) to set the
PWM output to 53% duty cycle.
2. Measure the fan RPM. This represents the fan
RPM below which the RPM mode fails to operate.
Do not program a lower RPM than this value when
using RPM feedback mode.
3. Ensure that speed range N = 2 when using RPM
feedback mode.
If the desired value for RPM feedback mode is 5000 RPM,
the count to be programmed is:
Count = (f × 60)/R × N
Since the desired RPM value, R, is 5000 RPM, the value
for count is:
N = 2:
Count = (11250 × 60)/5000 × 2
Count = 675000/10000
Count = 67 (assumes 2 tach pulses/rev)
Example 2:
If the desired value for RPM feedback mode is 3650 RPM,
the count to be programmed is:
Count = (f × 60)/R × N
Since the desired RPM value, R, is 3650 RPM, the value
for count is:
N = 2:
Count = (11250 × 60)/3650 × 2
Count = 675000/7300
Count = 92 (assumes 2 tach pulses/rev)
Once the count value has been calculated, it should be
written to the fan tach high limit register. It should be noted
that in RPM feedback mode, there is no high limit register
for underspeed detection that can be programmed as there
are in the other fan speed control modes. The only time each
fan indicates a fan failure condition is whenever the count
reaches 255. Since the speed range N = 2, the fan fails if its
speed drops below 1324 RPM.
Fan Drive and Speed Measurement
Fans come in a variety of different options. One
distinguishing feature of fans is the number of poles that a
fan has internally. The most common fans available have
four, six, or eight poles. The number of poles the fan has
generally affects the number of pulses per revolution the fan
outputs.
If the ADM1031 is used to drive fans other than 4−pole
fans that output 2 tach pulses/revolution, then the fan speed
measurement equation needs to be adjusted to calculate and
display the correct fan speed, and also to program the correct
count value in RPM feedback mode.
Fan Speed Measurement Equations
For a 4−pole fan (2 tach pulses/rev):
Fan RPM = (f × 60)/Count × N
For a 6−pole fan (3 tach pulses/rev):
Fan RPM = (f × 60)/(Count × N × 1.5)
For an 8−pole fan (4 tach pulses/rev):
Fan RPM = (f × 60)/(Count × N × 2)
If in doubt as to the number of poles the fans used have,
or the number of tach output pulses/rev, consult the fan
manufacturer’s data sheet, or contact the fan vendor for
more information.
Programming RPM Values
1. Choose the RPM value to be programmed.
2. Set speed range value N = 2.
3. Calculate count value based on RPM and speed
range values chosen. Use the count equation to
calculate the count value.
4. Clear Bit 7 of Configuration Register 1 (Register
0×00) to place the ADM1031 under software
control.
5. Write a 1 to Bit 5 of Configuration Register 1 to
place the device in RPM feedback mode.
6. Write the calculated count value to the fan tach
high limit register (Register 0×10). The fan speed
now goes to the desired RPM value and maintains
that fan speed.
Fan Drive Using PWM Control
The external circuitry required to drive a fan using PWM
control is extremely simple. A single NMOS FET is the only
drive transistor required. The specifications of the MOSFET
depend on the maximum current required by the fan being
driven. Typical notebook fans draw a nominal 170 mA, and
so SOT devices can be used where board space is a
constraint. If driving several fans in parallel from a single
PWM output, or driving larger server fans, the MOSFET
needs to handle the higher current requirements. The only
other stipulation is that the MOSFET should have a gate
voltage drive, VGS <3.3 V, for direct interfacing to the
PWM_OUT pin. The MOSFET should also have a low
on−resistance to ensure that there is not significant voltage
drop across the FET. This would reduce the maximum
operating speed of the fan.
RPM Feedback Mode Limitations
RPM feedback mode only controls fan RPM over a limited
fan speed range of about 75% to 100%. However, this should
be enough range to overcome fan−manufacturing tolerance.
In practice, however, the program must not function at too
low an RPM value for the fan to run at, or the RPM mode does
not operate.
http://onsemi.com
20
ADM1031
Figure 34 shows how a 3−wire fan can be driven using
PWM control.
3.3 V
+V
10kW
TYPICAL
TACH/AIN
TACH
5.0 V OR 12 V
FAN
3.3 V
ADM1031
10kΩ
TYPICAL
Q1
NDT3055L
PWM_OUT
Figure 34. Interfacing the ADM1031 to a 3−Wire Fan
The NDT3055L n−type MOSFET was chosen since it has
3.3 V gate drive, low on−resistance, and can handle 3.5 A of
current. Other MOSFETs can be substituted based on the
system’s fan drive requirements.
Figure 35 shows how a 2−wire fan can be connected to the
ADM1031. This circuit allows the speed of the 2−wire fan
to be measured even though the fan has no dedicated Tach
signal. A series RSENSE resistor in the fan circuit converts
the fan commutation pulses into a voltage. This is accoupled
into the ADM1031 through the 0.01 mF capacitor. On−chip
signal conditioning allows accurate monitoring of fan speed.
For typical notebook fans drawing approximately 170 mA,
a 2 W RSENSE value is suitable. For fans such as desktop or
server fans that draw more current, RSENSE can be reduced.
The smaller RSENSE is, the better, since more voltage is
developed across the fan, and the fan then spins faster.
Figure 36. Fan Speed Sensing Waveform at
TACH/AIN Pin
Fan Speed Measurement
The fan counter does not count the fan tach output pulses
directly, because the fan speed can be less than 1000 RPM
and it would take several seconds to accumulate a
reasonably large and accurate count. Instead, the period of
the fan revolution is measured by gating an on−chip
11.25 kHz oscillator into the input of an 8−bit counter. The
fan speed measuring circuit is initialized on the rising edge
of a PWM high output if fan speed measurement is enabled
(Bit 2 and Bit 3 of Configuration Register 2 = 1). It then starts
counting on the rising edge of the second tach pulse and
counts for two fan tach periods, until the rising edge of the
fourth tach pulse, or until the counter overranges if the fan
tach period is too long. The measurement cycle repeats until
monitoring is disabled. The fan speed measurement is stored
in the fan speed reading register at address 0×08, 0×09. The
fan speed count is given by:
Count = (f × 60)/R × N
where:
f = 11.25 kHz
R = fan speed in RPM.
N = speed range (either 1, 2, 4, or 8)
The frequency of the oscillator can be adjusted to suit the
expected running speed of the fan by varying N, the speed
range. The oscillator frequency is set by Bit 7 and Bit 6 of
Fan Characteristics Register 1 (0×20) and Fan
Characteristics Register 2 (0×21) as shown in Table 11.
Figure 37 shows how the fan measurements relate to the
PWM_OUT pulse trains.
+V
5.0 V OR 12 V
FAN
3.3 V
10kW
TYPICAL
PWM_OUT
TACH
Q1
NDT3055L
ADM1031
TACH/AIN
0.01μF
RSENSE
(2W TYPICAL)
Figure 35. Interfacing the ADM1031 to a 2−Wire Fan
Figure 36 shows a typical plot of the sensing waveform at
the TACH/AIN pin. The most important thing is that the
negative−going spikes are more than 250 mV in amplitude.
This is the case for most fans when RSENSE = 2 W. The value
of RSENSE can be reduced as long as the voltage spikes at the
TACH/AIN pin are greater than 250 mV. This allows fan
speed to be reliably determined.
Table 11. Oscillator Frequencies
Bit 7
Bit 6
N
Oscillator Frequency (kHz)
0
0
1
11.25
0
1
2
5.625
1
0
4
2.812
1
1
8
1.406
http://onsemi.com
21
ADM1031
Figure 38 shows the relationship between INT,
FAN_FAULT, and the PWM drive channel. The
PWM_OUT channel is driving a fan at some PWM duty
cycle, 50% for example, and the fan’s tach signal (or fan
current for a 2−wire fan) is being monitored at the
TACH/AIN pin. Tach pulses are being generated by the fan,
during the high time of the PWM duty cycle train. The tach
is pulled high during the off time of the PWM train because
the fan is connected high−side to the n−MOS device.
Suppose the fan has twice previously failed its fan speed
measurement. Looking at Figure 38, PWM_OUT is brought
high for two seconds, to restart the fan if it has stalled.
Sometime later a third tach failure occurs. This is evident by
the tach signal being low during the high time of the PWM
pulse, causing the fan speed reading register to reach its
maximum count of 255. Since the tach limit has been
exceeded, an interrupt is generated on the INT pin. The fan
fault bit (Bit 1) of Interrupt Status Register 1 (Register 0×02)
is also asserted. Once the processor has acknowledged the
INT by reading the status register, the INT is cleared.
PWM_OUT is then brought high for another two seconds to
restart the fan. Subsequent fan failures cause INT to be
reasserted and the PWM_OUT signal is brought high for
two seconds (fan spin−up default) each time to restart the
fan. Once the fifth tach failure occurs, the failure is deemed
to be catastrophic and the FAN_FAULT pin is asserted low.
PWM_OUT is brought high to attempt to restart the fan. The
INT pin continues to generate interrupts after the assertion
of FAN_FAULT since tach measurement continues even
after fan failure. Should the fan recover from its failure
condition, the FAN_FAULT signal is negated, and the fan
returns to its normal operating speed.
Figure 39 shows a typical application circuit for the
ADM1031. Temperature monitoring can be based around a
CPU diode or discrete transistor measuring thermal
hotspots. Either 2− or 3−wire fans can be monitored by the
ADM1031, as shown.
CLOCK
CONFIG 2
REG. BIT 2
FAN
INPUT
START OF
MONITORING
CYCLE
FAN
MEASUREMENT
PERIOD
Figure 37. Fan Speed Measurement
In situations where different output drive circuits are used
for fan drive, it can be desirable to invert the PWM drive
signal. Setting Bit 3 of Configuration Register 1 (0×00) to 1,
inverts the PWM_OUT signal. This makes the PWM_OUT
pin high for 100% duty cycle. Bit 3 of Configuration
Register 1 should generally be set to 1 when using an
n−MOS device to drive the fan.
If using a p−MOS device, Bit 3 of Configuration Register
1 should be cleared to 0.
FAN_FAULTs
The FAN_FAULT output (Pin 8) is an active−low,
open−drain output used to signal fan failure to the system
processor. Writing a Logic 1 to Bit 4 of Configuration
Register 1 (0×00) enables the FAN_FAULT output pin. The
FAN_FAULT output is enabled by default. The
FAN_FAULT output asserts low only when five consecutive
interrupts are generated by the ADM1031 device due to the
fan running underspeed, or if the fan is completely stalled.
Note that the Fan Tach High Limit must be exceeded by at
least one before a FAN_FAULT can be generated. For
example, if we are only interested in getting a FAN_FAULT
if the fan stalls, then the fan speed value is 0×FF for a failed
fan. Therefore, we should make the Fan Tach High
Limit = 0×FE to allow FAN_FAULT to be asserted after five
consecutive fan tach failures.
PWM_OUT
2 SECS
2 SECS
2 SECS
FULL SPEED
TACH/AIN
3RD TACH
FAILURE
4TH TACH
FAILURE
5TH TACH
FAILURE
INT
STATUS REG READ TO
CLEAR INTERRUPT
FAN_FAULT
Figure 38. Operation of FAN_FAULT and Interrupt Pins
http://onsemi.com
22
CONTINUING
TACH FAILURE
ADM1031
5.0 V MAX
(DO NOT CONNECT
TO 12 V)
5.0 V
5.0 V
10 kV
TYP
FAN2
2−WIRE
FAN
FAN1 1
3−WIRE
FAN
TACH
3.3 V 3.3 V
2.2 kV
2.2 kV
SCL
3.3 V
NDT3055L
(N−MOS)
10 kV
TYP PWM_OUT1
NDT3055L
(NMOS)
TACH1/AIN1
3.3 V
10 kV
TYP
RSENSE
PWM_OUT2
TACH2/AIN2
GND
0.01mF
THERM
SIGNAL TO
THROTTLE
CPU CLOCK
FAN_FAULT
TO SIGNAL
FAN FAILURE
CONDITION
3.3 V
3.3 V
10 kV
TYP
VCC
THERM
FAN_FAULT
3.3 V
SDA
1
16
2
15
3
14
4
5
ADM1031
13
12
6
11
7
10
8
9
SCL
3.3 V
SDA
INT (SMBALERT)
10 kV
TYP
CPU INTERRUPT
ADD
D2+
2N3904 OR PENTIUM III
CPU THERMAL DIODE
D2–
D1+
D1–/NTI
2N3904 OR PENTIUM III
CPU THERMAL DIODE
10 kV
TYP
1IN ACTUAL APPLICATION,
BOTH FANS MUST BE 2−WIRE OR 3−WIRE TYPE. A SINGLE BIT
CONTROLS WHETHER TACH1/AIN1 AND TACH2/AIN2 ARE ANALOG OR DIGITAL INPUTS.
Figure 39. Typical Application Circuit
Table 12. Registers
Register Name
Value Registers
Address
A7−A0 in Hex
0x08–0x1E
Comments
See Table 13.
Device ID Register
0x3D
This location contains the device identification number. Since this device
is the ADM1031, this register contains 0x31. This register is read only.
Company ID THERM
0x3E
This location contains the company identification number (0x41). This
register is read only.
Behavior/Revision
0x3F
Configuration Register 1
0x00
See Table 14. (Power−On Value = 1001 0000)
Configuration Register 2
0x01
See Table 15. (Power−On Value = 0111 1111)
Status Register 1
0x02
See Table 16. (Power−On Value = 0000 0000)
Status Register 2
0x03
See Table 17. (Power−On Value = 0000 0000)
Manufacturer’s Test Register
0x07
This register is used by the manufacturer for test purposes only. This
register should not be read from or written to in normal operation.
Fan Characteristics Register 1
0x20
See Table 19. (Power−On Value = 0101 1101)
Fan Characteristics Register 2
0x21
See Table 20 . (Power−On Value = 0101 1101)
Fan Speed Configuration Register
0x22
See Table 21. (Power−On Value = 0101 0101)
Fan Filter Register
0x23
See Table 22. (Power−On Value = 0101 0000)
Local Temperature TMIN/TRANGE
0x24
See Table 23. (Power−On Value = 0100 0001)
Remote 1 Temperature TMIN/TRANGE
0x25
See Table 24. (Power−On Value = 0110 0001)
Remote 2 Temperature TMIN/TRANGE
0x26
See Table 25. (Power−On Value = 0110 0001)
This location contains the revision number of the device. The lower four bits
reflect device revisions [3:0]. Bit 7 of this register is the THERM−to−fan
enable bit. See Table 17.
http://onsemi.com
23
ADM1031
Table 13. Value Registers
Address
R/W
0x06
R
Description
0x08
R/W
Fan 1 Speed. This register contains the value of the Fan 1 tach measurement.
0x09
R/W
Fan 2 Speed. This register contains the value of the Fan 2 tach measurement.
0x0A
R
Local Temperature Value. This register contains the 8 MSBs of the local temperature measurement.
Extended Temperature Resolution (see Table 18).
0x0B
R
Remote 1 Temperature Value. This register contains the 8 MSBs of the Remote 1 temperature reading.
0x0C
R
Remote 2 Temperature Value. This register contains the 8 MSBs of the Remote 2 temperature reading.
0x0D
R/W
Local Temperature Offset. See Table 27. (Power−On Default = 00h)
0x0E
R/W
Remote 1 Temperature Offset. See Table 28. (Power−On Default = 00h)
0x0F
R/W
Remote 2 Temperature Offset. See Table 29. (Power−On Default = 00h)
0x10
R/W
Fan 1 Tach High Limit. This register contains the limit for the Fan 1 tach measurement. Because the tach
circuit counts between pulses, a slow fan results in a large measure value, so exceeding the limit is the
way to detect a slow or stalled fan. (Power−On Default = FFh)
0x11
R/W
Fan 2 Tach High Limit. This register contains the limit for the Fan 2 tach measurement. Because the tach
circuit counts between pulses, a slow fan results in a large measured value, so exceeding the limit is the
way to detect a slow or stalled fan. (Power−On Default = FFh)
0x14
R/W
Local Temperature High Limit (Power−On Default 60°C)
0x15
R/W
Local Temperature Low Limit (Power−On Default 0°C)
0x16
R/W
Local Temperature THERM Limit (Power−On Default 70°C)
0x18
R/W
Remote 1 Temperature High Limit (Power−On Default 80°C)
0x19
R/W
Remote 1 Temperature Low Limit (Power−On Default 0°C)
0x1A
R/W
Remote 1 Temperature THERM Limit (Power−On Default 100°C)
0x1C
R/W
Remote 2 Temperature High Limit (Power−On Default 80°C)
0x1D
R/W
Remote 2 Temperature Low Limit (Power−On Default 0°C)
0x1E
R/W
Remote 2 Temperature THERM Limit (Power−On Default 100°C)
Table 14. Register 0y00 Configuration Register 1 Power−On Default = 90H
Bit
Name
R/W
Description
0
MONITOR
R/W
Setting this bit to a “1” enables monitoring of temperature and enables measurement
of the fan tach signals. (Powerup Default=0)
1
INT Enable
R/W
Setting this bit to a “1” enables the INT output. 1= Enabled 0= Disabled
(Powerup Default=0)
2
TACH/AIN
R/W
Clearing this bit to “0” selects digital fan speed measurement via the TACH pins.
Setting this bit to “1” configures the TACH pins as analog inputs that can measure the
speed of 2−wire fans via a sense resistor. (Powerup Default=0)
3
PWM Invert
R/W
Setting this bit to “1” inverts the PWM signal on the output pins. (Powerup Default=0)
4
FAN_FAULT Enable
R/W
Logic 1 enables FAN_FAULT pin; Logic 0 disables FAN_FAULT output.
(Powerup Default=1)
6−5
PWM Mode
R/W
These two bits control the behavior of the fans in auto fan speed control mode.
00 = Remote Temp 1 controls Fan 1; Remote Temp 2 controls Fan 2.
01 = Remote Temp 1 controls Fan 1 and Fan 2.
10 = Remote Temp 2 controls Fan 1 and Fan 2.
11 = Max of Local Temp and Remote Temp 1 and 2 drives Fans 1 and 2.
These two bits have the following effect in software control mode.
00 = Program PWM duty cycles for Fans 1 and 2.
11 = Program RPM Speeds for Fans 1 and 2.
7
Auto/SW Ctrl
R/W
Logic 1 selects automatic fan speed control; Logic 0 selects SW control. (Powerup
Default = 1). When under software control, PWM duty cycle or RPM values can be
programmed for each fan.
http://onsemi.com
24
ADM1031
Table 15. Register 0y01 Configuration 2 Power−On Default = 7FH
Bit
Name
R/W
Description
0
PWM 1 En
R/W
Enables Fan 1 PWM output when this bit is a “1.”
1
PWM 2 En
R/W
Enables Fan 2 PWM output when this bit is a “1.”
2
TACH 1 En
R/W
Enables Tach 1 input when set to “1.”
3
TACH 2 En
R/W
Enables Tach 2 input when set to “1.”
4
Loc Temp En
R/W
Enables Interrupts on local temperature channel when set to “1.”
5
Remote 1 Temp En
R/W
Interrupts on Remote 1 Channel when set to “1.” Default is normally enabled, except
when a diode fault is detected on powerup.
6
Remote 2 Temp En
R/W
Enables Interrupts on Remote 2 Channel when set to “1.” Default is normally enabled,
except when a diode fault is detected on powerup.
7
SW Reset
R/W
When set to “1,” resets the device. Self−clears. Powerup Default = 0.
Table 16. Register 0y02 Status Register 1 Power−On Default = 00H
Bit
Name
R/W
Description
0
Alarm 1 Speed
R
This bit is set to “1” when fan is running at alarm speed. Once read, this bit is not
reasserted on next monitoring cycle, even if the fan is still running at alarm speed.
1
Fan 1 Fault
R
This bit is set to “1” if Fan 1 becomes stuck or is running under speed.
2
Remote 1 High
R
“1” indicates Remote 1 high temperature limit has been exceeded. If the temperature
is still outside the Remote 1 Temp High Limit, this bit reasserts on next monitoring
cycle.
3
Remote 1 Low
R
“1” indicates Remote 1 low temperature limit exceeded (below). If the temperature is
still outside the Remote 1 Temp Low Limit, this bit reasserts on next monitoring cycle.
4
Remote 1 THERM
R
“1” indicates Remote 1 temperature THERM limit has been exceeded. This bit is
cleared on a read of Status Register 1.
5
Remote Diode 1 Error
R
This bit is set to “1” if a short or open is detected on the Remote 1 temperature
channel. This test is only done on powerup, and if set to 1 cannot be cleared by
reading the Status Register 1.
6
Local Temp High
R
This bit is set to “1” if a short or open is detected on the Remote 1 temperature
channel. This test is only done on powerup, and if set to 1 cannot be cleared by
reading the Status Register 1.
7
Local Temp Low
R
“1” indicates Local Temp Low Limit has been exceeded (below). If the temperature is
still outside the Local Temp Low Limit, this bit reasserts on next monitoring cycle.
Table 17. Register 0y03 Status Register 2 Powerup Default = 00H
Bit
Name
R/W
0
Alarm 2 Speed
R
This bit is set to “1” when Fan 2 is running at alarm speed. Once read, this bit is not
reasserted on next monitoring cycle, even if the fan is still running at alarm speed.
Description
1
Fan 2 Fault
R
This bit is set to “1” if Fan 2 becomes stuck or is running under speed.
2
Remote 2 High
R
“1” indicates Remote 2 high temperature limit has been exceeded. If the temperature
is still outside the Remote 2 Temp High Limit, this bit reasserts on the next monitoring
cycle.
3
Remote 2 Low
R
“1” indicates Remote 2 low temperature limit exceeded (below). If the temperature is
still outside the Remote 2 Temp Low Limit, this bit reasserts on the next monitoring
cycle.
4
Remote 2 THERM
R
“1” indicates Remote 2 temperature THERM limit has been exceeded. This bit is
cleared on reading Status Register 2.
5
Remote Diode 2 Error
R
This bit is set to “1” if a short or open is detected on the Remote 2 temperature
channel. This test is only done on powerup, and if set to 1 cannot be cleared by
reading Status Register 2.
6
Local THERM
R
“1” indicates local temperature THERM limit has been exceeded. This bit clears on a
read of Status Register 2.
7
THERM
R
Set to “1” when THERM is pulled low as an input. This bit clears on a read of Status
Register 2.
http://onsemi.com
25
ADM1031
Table 18. Register 0y06 Extended Temperature Resolution Power−On Default = 00H
Bit
Name
R/W
<2:0>
Remote Temp 1
R
Holds extended temperature resolution bits for Remote 1 channel.
Description
<5:3>
Remote Temp 2
R
Holds extended temperature resolution bits for Remote 2 channel.
<7:6>
Local Temp
R
Holds extended temperature resolution bits for local temperature channel.
Table 19. Register 0y20 Fan Characteristics Register 1 Power−On Default = 5DH
Bit
Name
R/W
Description
<2:0>
Fan 1 Spin−Up
R/W
These bits contain the fan spin−up time to allow Fan 1 to overcome its own inertia.
000 = 200 ms
001 = 400 ms
010 = 600 ms
011 = 800 ms
100 = 1 sec
101 = 2 sec (Default)
110 = 4 sec
111 = 8 sec
<5:3>
PWM 1 Frequency
R/W
These bits allow programmability of the nominal PWM 1 output frequency driving Fan 1.
(Default = 31 Hz.)
000 = 11.7 Hz
001 = 15.6 Hz
010 = 23.4 Hz
011 = 31.25 Hz (Default)
100 = 37.5 Hz
101 = 46.9 Hz
110 = 62.5 Hz
111 = 93.5 Hz
<7:6>
Speed Range, N
R/W
Speed range
00 = 1
01 = 2
10 = 4
11 = 8
Table 20. Register 0y21 Fan Characteristics Register 2 Power−On Default = 5H
Bit
Name
R/W
Description
<2:0>
Fan 2 Spin−Up
R/W
These bits contain the fan spin−up time to allow Fan 2 to overcome its own inertia.
000 = 200 ms
001 = 400 ms
010 = 600 ms
011 = 800 ms
100 = 1 sec
101 = 2 sec (Default)
110 = 4 sec
111 = 8 sec
<5:3>
PWM 2 Frequency
R/W
These bits allow programmability of the nominal PWM 2 output frequency driving Fan 1.
(Default = 31 Hz.)
000 = 11.7 Hz
001 = 15.6 Hz
010 = 23.4 Hz
011 = 31.25 Hz (Default)
100 = 37.5 Hz
101 = 46.9 Hz
110 = 62.5 Hz
111 = 93.5 Hz
<7:6>
Speed Range, N
R/W
Speed range
00 = 1
01 = 2
10 = 4
11 = 8
http://onsemi.com
26
ADM1031
Table 21. Register 0y22 Fan Speed Configuration Register Power−On Default = 55H
Bit
Name
R/W
Description
<3:0>
Normal/Min Spd 1
R/W
This nibble contains the normal speed value for Fan 1. When in automatic fan speed
control mode, this nibble contains the minimum speed at which Fan 1 runs. Default is
0x05 for 33% PWM duty cycle.
<7:4>
Normal/Min Spd 2
R/W
This nibble contains the normal speed value for Fan 2. When in automatic fan speed
control mode, this nibble contains the minimum speed at which Fan 2 runs. Default is
0x05 for 33% PWM duty cycle.
Table 22. Register 0y23 Fan Filter Register Power−On Default = 50H
Bit
Name
R/W
Description
<7>
Spin−Up Disable
R/W
When set to 1, disables fan spin−up.
<6:5>
Ramp Rate
R/W
These bits set the ramp rate. (Default = 31 Hz)
00 = 1
01 = 2
10 = 4 (Default)
11 = 8
<4:2>
ADC Sample Rate
R/W
These bits set the sampling rate for the ADC.
000 = 87.5 Hz
001 = 175 Hz
010 = 350 Hz
011 = 700 Hz
100 = 1.4 kHz (Default)
101 = 2.8 kHz
110 = 5.6 kHz
111 = 11.2 kHz
<1>
Fan 2 Filter En
R/W
This bit enables fan filtering for Fan 2.
<0>
Fan 1 Filter En
R/W
This bit enables fan filtering for Fan 1.
Table 23. Register 0y24 Local Temp TMIN/TRANGE Power−On Default = 41H
Bit
Name
R/W
Description
<7:3>
> Local Temp TMIN
R/W
Contains the minimum temperature value for automatic fan speed control based on
local temperature readings. TMIN can be programmed to positive values only in 4°C
increments. Default is 32°C.
00000 = 0°C
00001 = 4°C
00010 = 8°C
00011 = 12°C
|
|
01000 = 32°C (Default)
|
|
|
11110 = 120°C
11111 = 124°C
<2:0>
Local Temp TRANGE
R/W
This nibble contains the temperature range value for automatic fan speed control
based on the local temperature readings.
000 = 5°C
001 = 10°C (Default)
010 = 20°C
011 = 40°C
100 = 80°C
http://onsemi.com
27
ADM1031
Table 24. Register 0y25 Remote 1 Temp TMIN/TRANGE Power−On Default = 61H
Bit
Name
R/W
<7:3>
Remote 1 Temp TMIN
R/W
Contains the minimum temperature value for automatic fan speed control based on
local temperature readings. TMIN can be programmed to positive values only in 4°C
increments. Default is 32°C.
00000 = 0°C
00001 = 4°C
00010 = 8°C
00011 = 12°C
|
|
01100 = 48°C
|
|
|
11110 = 120°C
11111 = 124°C
Description
<2:0>
Remote 1 Temp
TRANGE
R/W
This nibble contains the temperature range value for automatic fan speed control
based on the Remote 1 Temp Readings.
000 = 5°C
001 = 10°C (Default)
010 = 20°C
011 = 40°C
100 = 80°C
Table 25. Register 0y26 Remote 2 Temp TMIN/TRANGE Power−On Default = 61H
Bit
Name
R/W
Description
<7:3>
Remote 2 Temp TMIN
R/W
Contains the minimum temperature value for automatic fan speed control based on
Remote 2 Temperature Readings. TMIN can be programmed to positive values only in
4°C increments. Default is 32°C.
00000 = 0°C
00001 = 4°C
00010 = 8°C
00011 = 12°C
|
|
01100 = 48°C (Default)
|
|
11110 = 120°C
11111 = 124°C
<2:0>
Remote 2 Temp
TRANGE
R/W
This nibble contains the temperature range value for automatic fan speed control
based on the Remote 2 Temp Readings.
000 = 5°C
001 = 10°C (Default)
010 = 20°C
011 = 40°C
100 = 80°C
Table 26. Register 0y3F THERM Behavior/Revision Power−On Default = 80H
Bit
Name
R/W
<7>
THERM−to−Fan En
R/W
<3:0>
Revision
R
Description
Setting this bit to 1, enables the fan to run full−speed when THERM is asserted low.
This allows the system to be run in performance mode. Clearing this bit to 0 disables
the fan from running full−speed whenever THERM is asserted low. This allows the
system to run in silent mode. (Power−On Default = 1).
This nibble contains the revision number for the ADM1031.
http://onsemi.com
28
ADM1031
Table 27. Register 0y0D Local Temperature Offset Power−On Default = 00H
Bit
Name
R/W
<7>
Sign
R/W
When this bit is 0, the local offset is added to the Local Temperature Reading. When
this bit is set to 1, the local offset is subtracted from the Local Temperature Reading.
Description
<3:0>
Local Offset
R
These four bits are used to add an offset to the Local Temperature Reading. These
bits allow an offset value of up to ±15°C to be added to or subtracted from the
temperature reading.
Table 28. Register 0y0E Remote 1 Temperature Offset Power−On Default = 00H
Bit
Name
R/W
Description
<7>
Sign
R/W
When this bit is 0, the remote offset is added to the Remote 1 Temperature Reading.
When this bit is set to 1, the remote offset is subtracted from the Remote 1
Temperature Reading.
<6.4>
Unused
R/W
Unused. Read back 0.
<3:0>
Remote 1 Offset
R/W
These four bits are used to add an offset to the Remote 1 Temperature Reading.
These bits allow an offset value of up to ±15°C to be added to or subtracted from the
temperature reading, depending on the sign bit.
Table 29. Register 0y0F Remote 2 Temperature Offset Power−On Default = 00H
Bit
Name
R/W
<7>
Sign
R/W
When this bit is 0, the remote offset is added to the Remote 2 Temperature Reading.
When this bit is set to 1, the remote offset is subtracted from the Remote 2
Temperature Reading.
Description
<6.4>
Unused
R/W
Unused. Read back 0.
<3:0>
Remote 2 Offset
R/W
These four bits are used to add an offset to the Remote 2 Temperature Reading.
These bits allow an offset value of up to ±15°C to be added to or subtracted from the
temperature reading, depending on the sign bit.
ORDERING INFORMATION
Device Order Number*
Package Type
Package Option
ADM1031ARQZ
ADM1031ARQZ−REEL
Shipping†
98 Tube
16−Lead QSOP
RQ−16
ADM1031ARQZ−R7
2500 Tape & Reel
1000 Tape & Reel
†For information on tape and reel specifications, including part orientation and tape sizes, please refer to our Tape and Reel Packaging
Specifications Brochure, BRD8011/D.
*These are Pb−Free packages.
http://onsemi.com
29
ADM1031
PACKAGE DIMENSIONS
QSOP−16
CASE 492−01
ISSUE O
−A−
Q
R
H x 45_
U
RAD.
0.013 X 0.005
DP. MAX
−B−
MOLD PIN
MARK
RAD.
0.005−0.010
TYP
G
L
0.25 (0.010)
M
P
T
DETAIL E
V
K
C
INCHES
DIM
MIN
MAX
A
0.189
0.196
B
0.150
0.157
C
0.061
0.068
D
0.008
0.012
F
0.016
0.035
G
0.025 BSC
H
0.008
0.018
J 0.0098 0.0075
K
0.004
0.010
L
0.230
0.244
M
0_
8_
N
0_
7_
P
0.007
0.011
Q
0.020 DIA
R
0.025
0.035
U
0.025
0.035
8_
V
0_
MILLIMETERS
MIN
MAX
4.80
4.98
3.81
3.99
1.55
1.73
0.20
0.31
0.41
0.89
0.64 BSC
0.20
0.46
0.249
0.191
0.10
0.25
5.84
6.20
0_
8_
0_
7_
0.18
0.28
0.51 DIA
0.64
0.89
0.64
0.89
0_
8_
−T−
D 16 PL
0.25 (0.010)
N 8 PL
NOTES:
1. DIMENSIONING AND TOLERANCING PER ANSI
Y14.5M, 1982.
2. CONTROLLING DIMENSION: INCH.
3. THE BOTTOM PACKAGE SHALL BE BIGGER THAN
THE TOP PACKAGE BY 4 MILS (NOTE: LEAD SIDE
ONLY). BOTTOM PACKAGE DIMENSION SHALL
FOLLOW THE DIMENSION STATED IN THIS
DRAWING.
4. PLASTIC DIMENSIONS DOES NOT INCLUDE MOLD
FLASH OR PROTRUSIONS. MOLD FLASH OR
PROTRUSIONS SHALL NOT EXCEED 6 MILS PER
SIDE.
5. BOTTOM EJECTOR PIN WILL INCLUDE THE
COUNTRY OF ORIGIN (COO) AND MOLD CAVITY I.D.
SEATING
PLANE
M
T B
S
A
S
M
J
F
DETAIL E
Pentium is a registered trademark of Intel Corporation.
ON Semiconductor and
are registered trademarks of Semiconductor Components Industries, LLC (SCILLC). SCILLC reserves the right to make changes without further notice
to any products herein. SCILLC makes no warranty, representation or guarantee regarding the suitability of its products for any particular purpose, nor does SCILLC assume any liability
arising out of the application or use of any product or circuit, and specifically disclaims any and all liability, including without limitation special, consequential or incidental damages.
“Typical” parameters which may be provided in SCILLC data sheets and/or specifications can and do vary in different applications and actual performance may vary over time. All
operating parameters, including “Typicals” must be validated for each customer application by customer’s technical experts. SCILLC does not convey any license under its patent rights
nor the rights of others. SCILLC products are not designed, intended, or authorized for use as components in systems intended for surgical implant into the body, or other applications
intended to support or sustain life, or for any other application in which the failure of the SCILLC product could create a situation where personal injury or death may occur. Should
Buyer purchase or use SCILLC products for any such unintended or unauthorized application, Buyer shall indemnify and hold SCILLC and its officers, employees, subsidiaries, affiliates,
and distributors harmless against all claims, costs, damages, and expenses, and reasonable attorney fees arising out of, directly or indirectly, any claim of personal injury or death
associated with such unintended or unauthorized use, even if such claim alleges that SCILLC was negligent regarding the design or manufacture of the part. SCILLC is an Equal
Opportunity/Affirmative Action Employer. This literature is subject to all applicable copyright laws and is not for resale in any manner.
PUBLICATION ORDERING INFORMATION
LITERATURE FULFILLMENT:
Literature Distribution Center for ON Semiconductor
P.O. Box 5163, Denver, Colorado 80217 USA
Phone: 303−675−2175 or 800−344−3860 Toll Free USA/Canada
Fax: 303−675−2176 or 800−344−3867 Toll Free USA/Canada
Email: [email protected]
N. American Technical Support: 800−282−9855 Toll Free
USA/Canada
Europe, Middle East and Africa Technical Support:
Phone: 421 33 790 2910
Japan Customer Focus Center
Phone: 81−3−5773−3850
http://onsemi.com
30
ON Semiconductor Website: www.onsemi.com
Order Literature: http://www.onsemi.com/orderlit
For additional information, please contact your local
Sales Representative
ADM1031/D
Similar pages