Gamewell-FCI ACC-AAM25 Zoned audio command center voice evacuation control panel Datasheet

Standard Features
GWACCZ
Zoned Audio Command Center
Voice Evacuation Control Panel
Description
g2504ph1.jpg
Gamewell’s Zoned Audio Command
Center (GWACCZ) is a state-of-the-art
Emergency Voice Evacuation Panel
(EVAC) capable of splitting 25 or 50
watts of audio power into up to eight
speaker circuits (i.e., zones). The
GWACCZ provides the ability to record
five field-programmable messages (up
to 60 seconds total message duration)
with an integral commercial-grade
emergency communications microphone or from an external audio source.
Significant technological enhancements
set the GWACCZ apart from other
EVAC panels — these include full supervision in both active alarm and
standby conditions, supervision of amplifier outputs, field wiring, message
generator, all tone generators, and the
microphone. The integral power supply
is capable of charging up to 18 AH batteries, which can be housed in the
GWACCZ cabinet.
The GWACCZ is suitable for use as an adjunct (slave or stand-alone) to most ULListed Fire Alarm Control Panels (FACPs). An optional 25 watt, 25 VRMS audio
amplifier is available for system expansion to 50 watts or as a secondary amplifier
in jurisdictions requiring such backup. A 70.7 VRMS converter is also available for
independently converting amplifiers to meet retrofit needs.
The Zone Splitter Module (ACC-ZSM) divides the output of the Audio Amplifier
Module(s) (ACC-AAM25) into up to eight speaker circuits (i.e., zones). The Zone
Page Module with Keypad (ACC-ZPMK) provides full manual control of the speaker
circuits, status indication of each of the speaker circuits, and automatic control by
the FACP via the ACS serial link connection.
A host of field-programming options, including the capability of five custom
messages (fire, tornado, evacuation, hazmat, non-fire, multi-language, etc.)
make the GWACCZ the most versatile voice evacuation system available.
Some suitable applications for the GWACCZ include schools, auditoriums,
dormitories, theatres, restaurants, places of worship, lodging, office buildings, and factories.
Controls and Indicators
1. Power On (green).
GWACCZ
CS-2505
09/01/06
Page 1 of 4
• 25 watts of audio power can be divided into eight
Style Y (Class B) or four Style Z (Class A) speaker
circuits (zones), utilizing the zone splitter module
(ACC-ZSM).
• Full manual control of all audio zones provided by
zone page module with keypad (ACC-ZPMK).
• Activation by the FACP using the ACS serial link
and/or the five Command (CMD) inputs.
• ACS serial link compatible with all Gamewell
FACPs, depending on function. FACP automatically directs the voice message to each or all audio
zones.
• Paging by zone or All-Call.
• Full status indication (normal, active, fault) of each
speaker circuit.
• Fault indication via ACS serial link and/or the two
Form-C trouble relays (System & AC Power Loss).
• Integral 25 watt, 25 VRMS audio amplifier with single
Style Z (Class A) or Style Y (Class B) speaker circuit
(expandable to 50 watts using the ACC-AAM25).
• Modular design for maximum system flexibility and
ease-of-service.
• Two command input circuits can be independently
field-programmed for activation by a Notification
Appliance Circuit (NAC) or contact closure.
• Three command input circuits activate on contact
closure.
• ACS link or Command Input (CMD) allow:
one 60-second message; two 30-second
messages; three 20-second messages; four 15second messages; or five 12-second messages.
• Microphone time-out feature.
• Nineteen different system and diagnostic LEDs.
• Two Form-C trouble relays (System/AC Power Loss).
• Optional equipment: second amplifier; local
playback speaker; remote microphone; and paging
equipment interface.
• Integral digital message generator with standard,
factory-prerecorded emergency evacuation message.
• Custom messages are field recordable, without the
addition of costly add-on modules, utilizing the
integral microphone or the audio input jack.
• Digital message may be field-selected for 3, 4, 6,
8, or infinite repeat.
• Built-in alert tone generators with steady, slow
whoop, high/low, or chime tone capability.
• Field-selectable lead-in/trailing tone selection.
• Alert tone selection may be field-programmed to
conform with ANSI S3.41 Audible Emergency
Evacuation Signal (Temporal Pattern), per NFPA.
• Speaker zone control via ACS serial link, CMD
inputs or keypad.
• Dual-optically-isolated, trigger input circuits are
independently field-programmable for activation by
polarity reversal (host FACP NAC) or dry-contact
closure.
• Integral diagnostic LEDs include: Power, System
Trouble, Microphone Trouble, Message Generator
Trouble, Tone Generator Trouble, Amplifier Fault,
and others.
• ACS serial link or independent Form-C trouble
relay allows FACP to monitor voice system while in
active (alarm) state.
• Integral piezo provides local audible indication for
troubles.
• Fully supervised in Standby and Active states,
including integral microphone, amplifier output,
message generator, speaker wiring, and tone
generators.
• Independent amplifier supervision: current limit,
audio level, short circuit protection.
• All outputs are power-limited.
• Auxiliary power output provides local power for
addressable control modules when used to
activate the GWACCZ.
• Compatible with all Gamewell FACPs, as well as
other manufacturers’ panels.
Module Features
ACC-AAM25
2. System Trouble (yellow).
3. Message Generator Trouble (yellow).
4. Tone Generator Trouble (yellow).
5. Microphone Trouble (yellow).
6. Record/Playback (green).
7. All-Call (green = Active).
8. Audio ON/OFF (green = Active, yellow = Manual Deactivation).
9. Status of each speaker zone (green = Active, yellow = Manual Deactivation or Fault).
Other System LEDs: Battery Trouble, Charger Trouble, Ground Fault,
Speaker Circuit Trouble, and Amplifier Supervisory.
Ordering Information
GWACCZ
ACC-AAM25
25 watt, 25 VRMS, emergency Voice Evacuation Control
Panel (VECP) with integral commercial microphone, digital
message generator, zone-splitter module (ACC-ZSM), zone
page module with keypad (ACC-ZPMK).
Optional 25 watt, 25 VRMS Audio Amplifier Module with single
Class A or Class B speaker circuit.
ACC-EPM
Optional External Page Module.
FC-XRM70
Optional 70.7 VRMS Converter Module (one required per
amplifier, consult factory for availability).
FC-RM
Optional Remote Microphone, includes backbox (only one
FC-RM per system).
FC-LPS
Optional Local Playback Speaker.
BAT-1270
Battery, 12 volt, 7.0 AH (two required).
BAT-12120
Battery, 12 volt, 12.0 AH (two required).
BAT-12180
Battery, 12 volt, 18.0 AH (two required).
• 25 watt, 25 VRMS audio amplifier module.
• Field-programmable for system expansion to 50
watts (providing dual 25-watt speaker circuits)
or as a backup to the primary 25-watt amplifier
where required.
• Provides single Class A or Class B speaker
circuit.
• Utilizes plug-in-style terminal blocks for ease of
service and maintenance.
• Fully supervised and power-limited.
• Diagnostic LEDs include: yellow “trouble” LED
(cable fault, 70 V RMS fault, amp fault) and green
“amp functional” LED.
ACC-EPM
• Provides interface to non-fire paging equipment
for non-emergency paging applications.
• Provides plug-in-style terminal blocks for ease
of service and maintenance.
• Transformer-isolated, 600-ohm audio
connection to paging equipment.
FC-XRM70
• Converts 25 V RMS audio outputs to 70.7 VRMS
for retrofit applications.
• Plugs directly on ACC-AAM25 module(s),
allowing independent conversion to 70.7VRMS.
FC-LPS
• Provides local digital message playback for user
review of field-recorded custom messages.
Specifications
Electrical specifications
Command input circuits(CMD1andCMD2):
Trigger input voltage 10.5 — 29 VDC. NOTE:
When programmed for reverse-polarity
activation.
Trouble contact rating: 2.0 A at 30 VDC
(resistive), 0.6 A @ 125 VAC (resistive).
Auxiliary power output: Specific application
power 24 V, 35 mA.
Primary (AC) power: 1.6 A maximum
@ 120 VAC, 50/60 Hz.
Secondary power (battery) charging circuit:
• Supports lead-acid batteries only.
• Float-charge voltage: 27.6 V.
• Maximum charge current: 800 mA.
• Maximum battery charging capacity:18 AH.
Cabinet dimensions
Door: 26.174" (66.482 cm) high x 15.780" (40.081
cm) wide x 1.125" (2.858 cm) deep. Backbox:
26.0" (66.040 cm) high x 15.5" (39.370 cm) wide x
4.75" (12.065 cm) deep, depth includes door.
Standards and Codes
The GWACC complies with the following
standards: NFPA 72 National Fire Alarm Code;
NFPA 101 Life Safety Code; UL 864 Standard
for Control Units for Fire Alarm Systems; and
UL 1711 Standard for Amplifiers for Fire Alarm
Systems.
Listings
Listings and approvals below apply to the basic
GWACCZ voice evacuation control panel. In
some cases, certain modules may not be listed
by certain approval agencies, or listing may be
in process. Consult factory for latest listing
status.
• UL Listed: file S521.
Page 2 of 4
GWACCZ
CS-2505 09/01/06
Application Example: 50-watt zone splitting, eight speaker circuits
50 watts total power with automatic control via ACS link from the FACP — see diagram below.
This application of the GWACCZ configures the zone splitter module (ACC-ZSM) to divide 50 watts of audio from two audio
amplifiers (ACC-AAM25) into four speaker circuits each. The FACP uses the ACS link connected to the zone page module
with keypad (ACC-ZPMK) for automatic activation of the speaker zones and for alarm activation.
Configuration switches are set as follows:
• ACC-ZSM SW1 set to “AAM1 & AAM2” and SW2 to “Class B” to place speaker circuits 1 – 4 on AAM1
and speaker circuits 5 – 8 on AAM2, configured for Style Y (Class B) wiring.
• ACC-ZPMK DIP switch S1 set for communication with software version 2.x (1 = ON, 2 = OFF, 3 = OFF).
• GWACCZ main circuit board DIP switch S3 set for single zone mode, All-Call and two messages
(1 = ON, 2 = OFF, 3 = OFF).
g2505ap1.wmf
The FACP can automatically activate the Fire Evacuation Message and any combination of the eight speaker zones. For
speaker circuit manual deactivation, press the activated zone pushbutton on the ACC-ZPMK keypad. For manual activation, press either of the Message push-buttons, then select the Zone pushbutton on the ACC-ZPMK keypad. For All-Call
Paging, press the All-Call pushbutton on the main panel keypad, then key the microphone to make an announcement.
GWACCZ
CS-2505 09/01/06
Page 3 of 4
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.