TRUMPower OMNI1000ISO Omnismart 1000va tower line-interactive 120v Datasheet

OmniSmart 1000VA Tower Line-Interactive 120V
UPS with built-in Isolation Transformer and USB
port
Highlights
1000VA / 1kVA tower 120V line
interactive UPS with isolation
transformer
Corrects brownouts and
MODEL NUMBER: OMNI1000ISO
overvoltages from 81V to 143V
USB port, Normal & common
mode EMI/RFI line noise immunity
NEMA 5-15P input plug and 6
5-15R outlets
Package Includes
OMNI1000ISO UPS System
USB cable
Instruction manual
Description
Tripp Lite's OMNI1000ISO offers complete UPS protection with built-in line-interactive voltage regulation, intelligent monitoring and unattended shutdown
capability. Built-in isolation transformer with Faraday shield offers full isolation and complete common mode noise rejection. 1000VA power-handling capacity
supports point-of-sale applications, computers, internetworking equipment and home theater systems during commercial power failures. Line-interactive
voltage regulation corrects brownouts as low as 81V and overvoltages as high as 143V back to normal 120V levels, reserving battery power for use during
complete power failures. Built-in USB communications port works with PowerAlert Software and cabling to provide automatic unattended shutdown of
connected network and PC applications.
Features
1000VA line-interactive UPS with Faraday-shielded, low-impedance isolation transformer delivers full isolation from potential damage and performance
problems
Provides immunity from EMI/RFI line noise in both normal and common modes. Delivers clean signal-reference ground, reducing data errors and
audio/video distortion
Automatic voltage regulation (AVR) automatically corrects incoming voltage to keep equipment working through low voltage (brownouts) as low as 81V
and overvoltages as high as 143V without consuming battery power
Supports loads up to 1000VA/700W
Half-load runtime of 24 min. (500VA/350W); full load runtime of 8 min. (1000VA/700W)
5 diagnostic LEDs indicate AC present, on battery, voltage correction status, overload and battery low/replace
Electrostatic discharge (ESD) resistance reduces potential static damage to connected electronics
Built-in USB port and PowerAlert Software (free via web download) provide safe, unattended system shutdown during extended blackouts
Built-in surge suppression (backed by $200,000 Ultimate Lifetime Insurance U.S., Canada, and Puerto Rico only) safeguards connected equipment
against damage
SURGE VOLTAGE WITHSTAND CAPABILITY: ANSI/IEEE C62.41 Catagories A & B 6KV/200/500 amp 100Khz Ringwave and category B BiWave
SURGE VOLTAGE ATTENUATION: N-G 2000:1, L-G 240:1, L-N 100:1
INSERTION LOSS: 65 db N-G from 10Khz to 100Khz, 45 to 60 db L-G from 10Khz to 100Khz, 18 to 54 db L-N from 50Khz to 500 Khz
1/5
6 UPS-supported AC outlets; 6-ft. cord
Optional PDUB15 bypass PDU enables hot-swappable UPS replacement with no disruption to connected equipment
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
1000
Output kVA Capacity (kVA)
1
Output Watt Capacity (Watts)
700
Power Factor
0.7
Nominal Output Voltage(s)
Supported
115V; 120V
Frequency Compatibility
60 Hz
Output Voltage Regulation (Line
Mode)
-18%, +8%
Output Voltage Regulation (Battery
Mode)
115V (+/- 5%)
UPS Output Receptacles
6 5-15R outlet(s)
Hot-Swap PDU options
PDUB15 (2U / 8 5-15R outlets)
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode)
PWM sine wave
INPUT
Rated input current (Maximum Load)
7.6A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-15P
UPS Input Cord Length (ft.)
6
UPS Input Cord Length (m)
1.8
Recommended Electrical Service
15A 120V
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
8 min. (700w)
Half Load Runtime (min.)
24 min. (350w)
DC System Voltage (VDC)
36
Battery Recharge Rate (Included
Batteries)
Less than 4.5 hours from 10% to 90%
2/5
Internal UPS Replacement Battery
Cartridge
RBC53
Battery Access
Battery access door
Battery Replacement Description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 85 to 143
Overvoltage Correction
Input voltages between 128 and 143V are reduced by 9%
Undervoltage Correction
Input voltages between 96 and 107V are boosted by 10%
Severe Undervoltage Correction
Input voltages between 85 and 95V are boosted by 20%
LEDS ALARMS & SWITCHES
LED Indicators
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible Alarm
Audible alarm indicates power-failure and low-battery conditions
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
510
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes
ISOLATION
Output Isolation Transformer
Professional grade load isolation transformer
Surge Voltage Withstand Capability
ANSI/IEEE C62.41 Categories A & B 6KV/200/500 amp 100Khz Ringwave and category B BiWave
Surge Voltage Attenuation
N-G 2000:1, L-G 240:1, L-N 100:1
Insertion Loss
65 db N-G from 10Khz to 100Khz, 45 to 60 db L-G from 10Khz to 100Khz, 18 to 54 db L-N from 50Khz to 500 Khz
PHYSICAL
Installation Form Factors Supported
with Included Accessories
Tower
Installation Form Factors Supported
with Optional Accessories
Wallmount (UPSWM - tower mounting kit)
Primary Form Factor
Tower
UPS Power Module Dimensions
(hwd, in.)
12.8 x 7.5 x 9.2
UPS Power Module Dimensions
(hwd, cm)
32.4 x 19 x 23.5
3/5
UPS Power Module Weight (lbs.)
36.4
UPS Power Module Weight (kg)
16.5
UPS Shipping Dimensions (hwd / in.)
18.2 x 13.8 x 12
UPS Shipping Dimensions (hwd /
cm)
46.4 x 34.9 x 30.5
Shipping Weight (lbs.)
40
Shipping Weight (kg)
18.2
Cooling Method
Fan
UPS Housing Material
PVC
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
235.4
Battery Mode BTU / Hr. (Full Load)
324.5
AC Mode Efficiency Rating (100%
Load)
91%
COMMUNICATIONS
Communications Interface
USB
PowerAlert Software
Free download from www.tripplite.com
Communications Cable
USB cable included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time
2-4 milliseconds
Low Voltage Transfer to Battery
Power (Setpoint)
81
High Voltage Transfer to Battery
Power (Setpoint)
143
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Hot swappable batteries
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
4/5
WARRANTY
Product Warranty Period (Worldwide)
2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$200,000 Ultimate Lifetime Insurance
© 2014 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement.
Specifications are subject to change without notice. Photos may differ slightly from final products.
5/5
Similar pages