XP Power AHM85PS15C2 Energy efficiency level v, cec2008 and eisa 2007 Datasheet

ACDC
85250 Watts
AHM Series
xppower.com
•
IT & Medical Approvals
•
Energy Efficiency Level V, CEC2008 & EISA 2007
•
<0.5 W No Load Input Power
•
Class I and Class II Models (Except AHM250)
•
Very High Efficiency
•
IP22 Environmental Rating
•
3 Year Warranty
Specification
Input
General
• 80-264 VAC (see derating curve)
• 47-63 Hz
• 85 W: 0.8 A at 115 VAC, 0.4 A
100 W: 1.0 A at 115 VAC, 0.5 A
150 W: 1.5 A at 115 VAC, 0.75 A
180 W: 1.7 A at 115 VAC, 0.9 A
250 W: 2.3 A at 115 VAC, 0.9 A
at 230 VAC
Inrush Current
• 70 A typical, 120 A max at 230 VAC,
cold start at 25 °C
Power Factor
• >0.9 at 115 VAC, 60 Hz at 250 VAC
Earth Leakage Current • 85 W: 70 µA typical, 180 µA max
100 W: 70 µA typical, 180 µA max
150 W: 80 µA typical, 200 µA max
180 W: 80 µA typical, 200 µA max
250 W: 80 µA typical, 200 µA max
at 264 VAC/60 Hz
Input Protection
• 85 W: Internal T2.5 A/250 V
100 W: Internal T2.5 A/250 V
150 W: Internal T4.0 A/250 V
180 W: Internal T4.0 A/250 V
250 W: Internal T6.3 A/250 V
fuse in line and neutral
No Load Input Power • <0.5 W
Input Voltage
Input Frequency
Input Current
Switching Frequency
Power Density
MTBF
• 92% typical
• Level V
• 4000 VAC In to Out, 2 x MOPP
1500 VAC In to Earth, 1 x MOPP
500 VAC Out to Earth, 1 x MOPP
• 45-200 KHz variable
• 4.4-5.7 W/in3
• 153 kHrs typical to MIL-HDBK-217F
at 25 °C, GB
Environmental
Operating Temperature • 0 °C to +60 °C, derate linearly from 100%
power at +40 °C to 60% power at +60 °C
Cooling
• Convection-cooled
Operating Humidity
• 5-95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C
Operating Altitude
• 3000 m
Shock
• 3 x 30 g/11 ms shocks in both +ve & -ve
directions along the 3 orthogonal axis,
total 18 shocks.
Vibration
• Three axis 5-500 Hz at 2 g x 10 sweeps
EMC & Safety
Output
See tables
Not user-adjustable
No minimum load required
100-300 ms typical, model dependant(1)
20 ms typical
±1.5% maximum
±3.0% maximum
5% max. deviation, recovery to within
1% in 500 µs for a 25% load change
Ripple & Noise
• Typically less than 1%, 1.5% max pk-pk(2)
Overvoltage Protection • 125% typical, Recycle input to reset
Overtemperature
• Unit shuts down, auto recovery
Protection
Overload Protection
• 115-175%, auto recovery
Short Circuit Protection • Trip and restart (hiccup mode)
Temperature
• 0.05 %/°C
Coefficient
Output Voltage
Output Voltage Trim
Minimum Load
Start Up Delay
Hold Up Time
Line Regulation
Load Regulation
Transient Response
Efficiency
Energy Efficiency
Isolation
•
•
•
•
•
•
•
•
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Magnetic Field
Dips & Interruptions
Safety Approvals
Notes
• EN55011/22, class B conducted
EN55011/22, class B radiated
• EN61000-3-2, class A
• EN61000-3-3
• EN61000-4-2, level 3, Perf Criteria A
• EN61000-4-3, level 3, Perf Criteria A
• EN61000-4-4, level 3, Perf Criteria A
• EN61000-4-5, installation class 3,
Perf Criteria A
• EN61000-4-6, level 3, Perf Criteria A
• EN61000-4-8, level 3, Perf Criteria A
• EN61000-4-11, EN60601-1-2
• EN60601-1, ANSI/AAMI ES60601-1,
CSA22.2 No. 60601-1 per cUL, Including
Risk Management, EN60950, UL60950.
Denan (PSE) certification
1. See longform datasheet for further information.
2. Measured at the end of the output cable with 10 µF electrolytic and 0.1 µF
ceramic capacitor.
Output Power
Output Voltage
Output Current
85 W
12.0 VDC
7.08 A
Model Number(1)
AHM85PS12
85 W
15.0 VDC
5.67 A
AHM85PS15
85 W
19.0 VDC
4.47 A
AHM85PS19
85 W
24.0 VDC
3.54 A
AHM85PS24
85 W
12.0 VDC
7.08 A
AHM85PS12C2
85 W
15.0 VDC
5.67 A
AHM85PS15C2
85 W
19.0 VDC
4.47 A
AHM85PS19C2
85 W
24.0 VDC
3.54 A
AHM85PS24C2
Notes
1. Models with suffix ‘C2’ have a Class II equipment protection classification.
2. For IEC320-C8 input connector with Class II models, add suffix ‘-8’ to the
model number, e.g. AHM85PS24C2-8.
3. For optional input connector retention clip, add suffix ‘-A’ to the model number
e.g. AHM85PS24C2-A.
4. Alternate case colours available for OEM quantities, contact sales for information.
Mechanical Details
5.9 (150.0)
36.4 (900.0)
0.79 (Ø20)
2.52
(64.0)
5.12 (130.0)
1.4 (36.0)
IEC320-C14
1.45
(37.0)
3.02 (76.9)
1.57 (40.0)
1.55
(39.4)
5.11 (130.0)
Shell
Optional Input Connector Retention (-A)
Standard (Class I)
C2 Models (Class II)
C2-8 Models (Class II)
1.40 (35.7)
2
1
4
3
Output Connector equivalent
to KPPX-4P (Non Locking)
IEC 320-C14
IEC 320-C18
IEC 320-C8
Pin 1
Pin 2
Pin 3
Pin 4
Outer Shell
Output +
Output +
Return
Return
GND*
Outer Shell
C2 Models
Floating
* Functional earth.
Notes
1. Tolerance is 0.02 (0.5) maximum, except output cable length.
2. Weight 0.9 lbs (400 g).
3. Dimensions shown in inches (mm).
4. Alternate case colours available for OEM quantities, contact sales for information
ACDC
AHM85
Models and Ratings
ACDC
AHM100
Models and Ratings
Output Power
Output Voltage
Output Current
100 W
12.0 VDC
8.33 A
Model Number(1)
AHM100PS12
100 W
15.0 VDC
6.67 A
AHM100PS15
100 W
19.0 VDC
5.26 A
AHM100PS19
100 W
24.0 VDC
4.16 A
AHM100PS24
100 W
48.0 VDC
2.08 A
AHM100PS48
100 W
12.0 VDC
8.33 A
AHM100PS12C2
100 W
15.0 VDC
6.67 A
AHM100PS15C2
100 W
19.0 VDC
5.26 A
AHM100PS19C2
100 W
24.0 VDC
4.16 A
AHM100PS24C2
100 W
48.0 VDC
2.08 A
AHM100PS48C2
Notes
1. Models with suffix ‘C2’ have a class II equipment protection classification.
3. For optional input connector retention clip, add suffix ‘-A’ to the model number
2. For IEC320-C8 input connector with class II models, add suffix ‘-8’ to the model
e.g. AHM100PS24C2-A.
number, e.g. AHM100PS24C2-8.
4. Alternate case colours available for OEM quantities, contact sales for information.
Mechanical Details
6.29 (160.0)
36.4 (900.0)
0.2 (5.0)
0.79 (Ø20)
2.52
(64.0)
5.12 (130.0)
1.4 (36.0)
1.45
(37.0)
3.02 (76.9)
1.57 (40.0)
1.55
(39.4)
5.11 (130.0)
Shell
Optional Input Connector Retention (-A)
Standard (Class I)
C2 Models (Class II)
C2-8 Models (Class II)
1.40 (35.7)
2
1
4
3
Output Connector equivalent
to KPPX-4P (Non Locking)
IEC 320-C14
IEC 320-C18
IEC 320-C8
Pin 1
Pin 2
Pin 3
Pin 4
Outer Shell
Output +
Output +
Return
Return
GND*
Outer Shell
C2 Models
Floating
* Functional earth.
Notes
1. Tolerance is 0.02 (0.5) maximum, except output cable length.
2. Weight 1.1 lbs (500 g).
3. Dimensions shown in inches (mm).
Output Power
Output Voltage
Output Current
Model Number(1)
150 W
12.0 VDC
12.50 A
AHM150PS12
150 W
15.0 VDC
10.00 A
AHM150PS15
150 W
19.0 VDC
7.89 A
AHM150PS19
150 W
24.0 VDC
6.25 A
AHM150PS24
150 W
48.0 VDC
3.13 A
AHM150PS48
150 W
12.0 VDC
12.50 A
AHM150PS12C2
150 W
15.0 VDC
10.00 A
AHM150PS15C2
150 W
19.0 VDC
7.89 A
AHM150PS19C2
150 W
24.0 VDC
6.25 A
AHM150PS24C2
150 W
48.0 VDC
3.13 A
AHM150PS48C2
Notes
1. For optional input connector retention clip, add suffix ‘-A’ to the model number e.g. AHM150PS24-A. Models with suffix ‘C2’ have a class II equipment protection
classification. For IEC320-C8 input connector with class II models, add suffix ‘-8’ to the model number, e.g. AHM150PS24C2-8.
2. Alternate case colours available for OEM quantities, contact sales for information.
Mechanical Details
Dimensions shown in inches (mm).
7.8 (200.0)
36.4 (900.0)
0.19 (4.9)
0.79 (Ø20)
3.15
(80.0)
1.4 (36.0)
5.12 (130.0)
IEC320-C14
1.45
(37.0)
3.94 (100.3)
2.02
(51.5)
1.58
(40.30)
6.8 (173.0)
Shell
Optional Input Connector Retention (-A)
Standard (Class I)
C2 Models (Class II)
C2-8 Models (Class II)
2
1
4
3
1.40 (35.7)
Output Connector equivalent
to KPPX-4P (Non Locking)
IEC 320-C14
IEC 320-C18
IEC 320-C8
Pin 1
Pin 2
Pin 3
Pin 4
Outer Shell
Output +
Output +
Return
Return
GND*
Outer Shell
C2 Models
Floating
* Functional earth.
Notes
1. Tolerance is 0.02 (0.5) maximum, except output cable length.
2. Weight 1.3 lbs (600 g).
ACDC
AHM150
Models and Ratings
ACDC
AHM180
Models and Ratings
Output Power
Output Voltage
Output Current
165 W
12.0 VDC
13.50 A
Model Number
AHM180PS12
180 W
15.0 VDC
12.00 A
AHM180PS15
180 W
19.0 VDC
9.47 A
AHM180PS19
180 W
24.0 VDC
7.50 A
AHM180PS24
180 W
48.0 VDC
3.75 A
AHM180PS48
165 W
12.0 VDC
13.50 A
AHM180PS12C2
180 W
15.0 VDC
12.00 A
AHM180PS15C2
180 W
19.0 VDC
9.47 A
AHM180PS19C2
180 W
24.0 VDC
7.50 A
AHM180PS24C2
180 W
48.0 VDC
3.75 A
AHM180PS48C2
Notes
1. For optional input connector retention clip, add suffix ‘-A’ to the model number e.g. AHM180PS24-A. Models with suffix ‘C2’ have a class II equipment protection
classification. For IEC320-C8 input connector with class II models, add suffix ‘-8’ to the model number, e.g. AHM180PS24C2-8.
2. Alternate case colours available for OEM quantities, contact sales for information.
Mechanical Details
Dimensions shown in inches (mm).
7.87 (200.0)
0.193
(4.9)
35.43 (900.0)
0.79 (Ø20.0)
3.15
(80.0)
1.41 (36.0)
5.12 (130.0)
1.61
(41.0)
3.94 (100.3)
2.02
(51.5) 1.58
(40.3)
6.81 (173.0)
Shell
Optional Input Connector Retention (-A)
Standard (Class I)
IEC 320-C14
C2 Models (Class II)
IEC 320-C18
C2-8 Models (Class II)
2
4
1.40 (35.7)
Output Connector equivalent
to KPPX-4P (Non Locking)
IEC 320-C8
Pin 1
Pin 2
Pin 3
Pin 4
Outer Shell
Output +
Output +
Return
Return
GND*
Outer Shell
C2 Models
Floating
* Functional earth.
Notes
1. Dimensions shown in inches (mm). Tolerance is 0.02 (0.5) maximum,
except output cable length.
1
3
2. Weight 1.4 lbs (620 g)
Output Power
Output Voltage
Output Current
Model Number(2)
210 W
12.0 VDC
17.50 A
AHM250PS12T
220 W
15.0 VDC
14.66 A
AHM250PS15T
240 W
19.0 VDC
12.63 A
AHM250PS19T
250 W
24.0 VDC
10.41 A
AHM250PS24T
250 W
48.0 VDC
5.21 A
AHM250PS48T
Notes
1. For optional input connector retention clip, add suffix ‘-A’ to the model number e.g. AHM250PS24T-A.
2. For 6 pin DIN connector, remove ‘T’ from the end of the model number e.g. AHM250PS24 (DIN connector for medical applications only).
Mechanical Details
Dimensions shown in inches (mm).
Standard Molex 6 pin Connector
8.8 (223.0)
8.58 (218.0)
0.2 (5.0)
35.43 (900.0)
0.79 (Ø 20.0)
3.484
(88.50)
1.417 (36.0)
Optional 6 pin DIN connector shown
(for medical applications only)
IEC 320-C14
0.79 (Ø 20.0)
1.457 (37.0)
4.134 (105.0)
1.417 (36.0)
0.063 (1.60)
7.41 (188.40)
2.37 (60.20)
1.97 (50.20)
OUTPUT CONNECTOR
5.12 (130.20)
5
4
Optional Input Connector Retention (-A)
6
1.40 (35.7)
3
1
2
Pin No.
Molex Part
No.: 50-36-1672
DIN Part
No.: DIN45322
Pin 1
Return
Output +
Pin 2
Return
Return
Pin 3
Return
Return
Pin 4
Output +
Return
Pin 5
Output +
Output +
Pin 6
Ouput +
Ouput +
Outer Shell
Shell
GND*
* Functional earth.
IEC 320-C14
1
2
3
6
Notes
5
1. Dimensions shown in inches (mm). Tolerance is 0.02
(0.5) maximum, except output cable length.
2. Weight 2.2 lbs (1000 g).
4
Derating Curve
100
Output Power (%)
90
80
70
AHM85,100,150 & 180 Models
60
AHM250 Models
50
40
80
85
90
100
110
240
250
264
28-Oct-13
ACDC
AHM250