Specifications:
• CCPB Ampacity rejection breaks: 15A, 20A, 30A, 40A,
50A and 60A
• 1-, 2- and 3-Pole versions
• For systems 600Vac (or less)
• Box lug loadside terminal:
• 18-6AWG single & dual rated, solid or stranded –
75°C, Cu only
• 4AWG single – 75°C, Cu only
• Box lug loadside terminal torque: 18-10AWG 20 Lb-In
(2.2 N•m), 8-4AWG 35 Lb-In (3.9 N•m)
The revolutionary Cooper Bussmann® CCPB with
CUBEFuse® is designed as a fused branch circuit
disconnect with fuse holder for the Cooper Bussmann®
Quik-Spec™ Coordination Panelboard. The CCPB with
CUBEFuse simplifies selective coordination and allows for
isolation of individual branch circuit loads for safe work
practices.
• Spade terminal load connection:
Max. 30A suitable for use with #8-32UNC screw
Product Features and Benefits
• Bolt-mounted design into Quik-Spec Coordination
Panelboard bus
Low-Peak®
CUBEFuse®
• Uses IP20 finger-safe
with
current-limiting, time-delay Class J performance
• Bolt-on style bus connector, #10-32-UNC Hex flange
Phillips screw, torque to 25 Lb-In (2.8N•m)
• Lockout/tagout: 4mm shank lock or standard pin-out
devices (Brady pin-out wide device P/N 90850 or Ideal
P/N 44-784
• High Short-Circuit Current Ratings at 200kA
• Local indication: illumination requires closed circuit and
minimum 90Vac operating voltage
• Disconnect rated to provide means for load isolation
• RoHS compliant
• Full voltage rated at 600Vac
• UL 98 Listed and suitable for branch circuit disconnect
and branch circuit protection
• 1-, 2- and 3-pole versions are horsepower rated
Agency Information:
UL 98 Listed, File E302370, Guide WHTY
• Patented rejection feature helps prevent overfusing
cULus to CSA Standard 22.2 No. 4, File E302370,
Guide WHTY7
• Complies with UL and cULus
CE Compliant
• Open fuse indication light per pole
• Additional open fuse indication can be provided by using
the indicating CUBEFuse version
Shipping Weight: 2.03 lbs per carton
• Built-in switch/fuse interlock prohibits removing the fuse
while energized
Carton quantity: 6 poles
Environmental Data
• Permanent lockout/tagout provisions
Storage and operating temperature: -20ºC to 75ºC*
• Lock-On provision
1008
BU-SB08561
*For fuse performance under or above 25ºC, consult fuse performance
derating charts.
Form No.CCPB
Page 1 of 3
Data Sheet 1161
Bolt-on style bus connector
Symbols for ON and OFF
Lockout/tagout provision
Local, neon open fuse indication light
Disconnect handle
CUBEFuse base
Box lug loadside terminal
Spade terminal connection
Technical Ratings
CUBEFuse Type
(Class J performance)
CCPB Part
Numbers
CCPB-1-15CF
CCPB-2-15CF
Poles
Fuse Amp
Range
Voltage
Rating
1
2
CCPB-3-15CF
3
CCPB-1-20CF
CCPB-2-20CF
1
2
CCPB-3-20CF
3
CCPB-1-30CF
CCPB-2-30CF
1
2
CCPB-3-30CF
3
CCPB-1-40CF
CCPB-2-40CF
1
2
CCPB-3-40CF
3
CCPB-1-50CF
CCPB-2-50CF
1
2
CCPB-3-50CF
3
CCPB-1-60CF
CCPB-2-60CF
1
2
CCPB-3-60CF
3
Non-Indicating
Max. Fuse
Ampacity
Indicating*
1-15
600Vac
TCF1RN, TCF3RN, TCF6RN,
TCF10RN, TCF15RN
TCF3, TCF6,
TCF10, TCF15
15A
200kA
171⁄2-20
600Vac
TCF17-1/2RN, TCF20RN
TCF17-1/2, TCF20
20A
200kA
25-30
600Vac
TCF25RN, TCF30RN
TCF25, TCF30
30A
200kA
35-40
600Vac
TCF35RN, TCF40RN
TCF35, TCF40
40A
200kA
45-50
600Vac
TCF45RN, TCF50RN
TCF45, TCF50
50A
200kA
60
600Vac
TCF60RN
TCF60
60A
200kA
*1A indicating CUBEFuse not available. Correct fit with CCPB disconnect requires indicating CUBEFuse with date code R38 or later.
1008
SCCR
BU-SB08561
Form No.CCPB
Page 2 of 3
Data Sheet 1161
Hp Ratings
0.5Hp@120V
1.5Hp@240V
3Hp@240V
5Hp@480V
7.5Hp@600V
0.75Hp@120V
2Hp@240V
3Hp@240V
7.5Hp@480V
10Hp@600V
1.5Hp@120V
3Hp@240V
5Hp@240V
15Hp@480V
10Hp@600V
2.0Hp@120V
3Hp@240V
7.5Hp@240V
20Hp@480V
10Hp@600V
3.0Hp@120V
5Hp@240V
7.5Hp@240V
20Hp@480V
10Hp@600V
3.0Hp@120V
7.5Hp@240V
7.5Hp@240V
20Hp@480V
10Hp@600V
CUBEFuse® Motor Sizing Table
Voltage
115Vac,
1-Phase
230Vac,
1-Phase
200Vac,
3-Phase
208Vac,
3-Phase
Motor
Size (Hp)
0.167
0.25
0.333
0.5
0.75
1
1.5
2
3 **
0.167
0.25
0.333
0.5
0.75
1
1.5
2
3
5
7.5**
0.5
0.75
1
1.5
2
3
5
7.5**
0.5
0.75
1
1.5
2
3
5
7.5 **
Motor*
FLA (Amps)
4.4
5.8
7.2
9.8
13.8
16
20
24
34
2.2
2.9
3.6
4.9
6.9
8
10
12
17
28
40
2.5
3.7
4.8
6.9
7.8
11
17.5
25.3
2.4
3.5
4.6
6.6
7.5
10.6
16.7
24.2
Low-Peak® CUBEFuse® (Amp Rating)
Optimal
Code
Heavy
Protection
Max
Start
10
10
10
10
15
15
15
15
15
15
20
20
25
25
30
25
30
35
30
35
45
40
45
50
50
60
N/A
6
6
6
6
6
6
6
10
10
10
10
10
15
15
15
15
15
17.5
15
20
20
20
25
25
25
30
35
45
50
60
60
N/A
N/A
6
6
6
6
10
10
10
10
10
15
15
15
15
15
17.5
17.5
20
20
30
35
35
40
45
50
6
6
6
6
10
10
10
10
10
10
15
15
15
15
15
17.5
20
20
25
30
35
40
45
50
Voltage
230Vac,
3-Phase
460Vac,
3-Phase
575Vac,
3-Phase
Motor
Size (Hp)
0.5
0.75
1
1.5
2
3
5
7.5**
0.5
0.75
1
1.5
2
3
5
7.5
10
15
20**
0.5
0.75
1
1.5
2
3
5
7.5
10 **
Motor1
FLA (Amps)
2.2
3.2
4.2
6
6.8
9.6
15.2
22
1.1
1.6
2.1
3
3.4
4.8
7.6
11
14
21
27
0.9
1.3
1.7
2.4
2.7
3.9
6.1
9
11
Low-Peak® CUBEFuse® (Amp Rating)
Optimal
Code
Heavy
Protection
Max
Start
6
6
6
6
6
6
10
10
10
10
15
15
15
15
15
15
20
20
25
30
30
35
40
45
3
3
3
3
3
3
6
6
6
6
6
6
6
6
6
10
10
10
15
15
15
17.5
20
20
25
25
30
35
40
45
40
50
60
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
10
10
10
15
15
15
20
20
17.5
20
20
Note: Use Code Max column for low to moderate reverse/jog/plug
applications. Heavy Start permitted only if Code Max does not allow motor
start-up.
*Based on motor FLA from NEC® tables 430.248 and 430.250.
**Max. Hp rating for the CCPB 60 Amp device at specified voltage.
Dimensional Data — in (mm)
3.9
(99.4)
1.0
(25.4)
2.0
(50.7)
2.7
(69.1)
2.9
(73.5)
3.0
(75.8)
Ø.5
(12.9)
Ø.2
(5.8)
39
For details on the CCPB and its use in the Quik-Spec™ Coordination Panelboard, see data sheet 1160.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are
by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with
design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of
any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has
been selected, it should be tested by the user in all possible applications.
© 2008 Cooper Bussmann
St. Louis, MO 63178
636-394-2877
w w w. c o o p e r b u s s m a n n . c o m
1008
BU-SB08561
Form No.CCPB
Page 3 of 3
Data Sheet 1161
Similar pages