Crydom H12D4825DE Panel mount Datasheet

DUAL Series
• Independently controlled dual output solid-state relay
• Ratings from 25A to 40A @ 24-530 VAC
• Industry standard package
• SCR output for heavy industrial loads
• DC Control
• Zero-crossing (resistive loads) or random-fire (inductive loads) output
PRODUCT SELECTION
Control Voltage
4-15 VDC
15-32 VDC
4-15 VDC
15-32 VDC
25A
40A
D2425D
D2425DE
H12D4825D
H12D4825DE
D2440D
D2440DE
H12D4840D
H12D4840DE
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2)
Maximum Load Current (3) [Arms]
Minimum Load Current [Arms]
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Maximum 1/2 Cycle I²t for Fusing (50/60 Hz) [A² sec]
Minimum Power Factor (with Maximum Load)
D2425xx
D2440xx
H12D4825xx
H12D4840xx
24-280
600
10
500
24-280
600
10
500
48-530
1200
10
500
48-530
1200
10
500
25
0.15
239/250
1.6
1.02
285/259
0.5
40
0.15
597/625
1.6
0.63
1779/1621
0.5
25
0.15
239/250
1.6
1.02
285/259
0.5
40
0.15
597/625
1.6
0.63
1779/1621
0.5
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Minimum Turn-On Voltage
Minimum Turn-Off Voltage
Typical Input Current @ 5 VDC (@ 24 VDC for E-Suffix)
Nominal Input Impedance
Maximum Turn-On Time [msec] (4)
Maximum Turn-Off Time [msec]
D24XXD
H12D48XXD
E-SUFFIX
4-15 VDC
4.0 VDC
1.0 VDC
13 mA
300 Ohm
1/2 cycle
1/2 cycle
4-15 VDC
4.0 VDC
1.0 VDC
13 mA
240 Ohm
1/2 cycle
1/2 cycle
15-32 VDC
15.0 VDC
1.0 VDC
15 mA
1500 Ohm
1/2 cycle
1/2 cycle
GENERAL SPECIFICATIONS
Description
Dielectric Strength, Input/Output/Base (50/60Hz)
Minimum Insulation Resistance (@ 500 V DC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Encapsulation
Terminals
GENERAL NOTES
1) All parameters at 25°C and per section unless otherwise specified.
3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
3) Heat sinking required, for derating curves see next page.
4) Turn-on time for random turn-on (-10) versions is 0.1 msec
MECHANICAL SPECIFICATIONS
Parameters
4000 Vrms
109 Ohm
10 pF
-40 to 80°C
-40 to 125 °C
3.0 oz (86.5g)
Thermally conductive Epoxy
.25" Fastons, .025" Square Pins
WIRING DIAGRAM
THERMAL DERATE INFORMATION
AGENCY APPROVALS
Designed in accordance with the requirements of IEC 62314
E116949 (except 15-32VDC control)
LR81689 (240 V, 4-15VDC control only)
5902 UG
Rev. 121211
ANNEX - ENVIROMENTAL INFORMATION