EPCOS B88069X5731B201 Surge arrester 2-electrode arrester Datasheet

Surge arrester
2-electrode arrester
Series/Type:
Ordering code:
L1C-A800XP1
B88069X5731B201
Version/Date:
Version:
Issue 02 / 2007-07-03
02
Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the
table and then change the color to "white" (or invisible). This ensures that the table disappears for the customer
PDF. To update the data sheet, click on the symbol "Preview" and then "Close". Please do not alter the header or
footer when copying the content.
Identification/Classification 1:
(header 1 + top left header bar)
Surge arrester
Identification/Classification 2:
(header 2 + bottom left header bar)
2-electrode arrester
Ordering code:
(top right header bar)
B88069X5731B201
Series/Type:
(top right header bar)
L1C-A800XP1
Preliminary data (optional):
(if necessary)
Department:
KB AB E / KB AB PM
Date:
Issue 02 / 2007-07-03
© EPCOS AG 2006. Reproduction, publication and dissemination of this document, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
Surge arrester
2-electrode arrester
B88069X5731B201
L1C-A800XP1
Features
Applications
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
Very small size
Suitable for direct strikes
Very fast response time
Stable performance over life
High insulation resistance
RoHS compatible
AC power lines
Class 1 (class B) - requirements
Electrical specifications
DC spark-over voltage 1) 2)
> 600
V
Impulse spark-over voltage
at 1.2/50 µs, 6kV, for 99 % of measured values
< 1500
V
Response time
- typical values
< 100
< 20
ns
ns
Insulation resistance at 100 Vdc
>1
GΩ
255
50
50
Vrms
kA
kA
Arms
AC discharge current (TOV 3))
1 operation
50 Hz, 0.2 s
300
A
Weight
~ 100
g
Operation and storage temperature
-40 ... +90
°C
Climatic category (IEC 60068-1)
40/ 90/ 21
Class I according to EN 61643-11
Max. continuous operating voltage at 50/60 Hz
Nominal discharge current 8/20 µs
Impulse current 10/350 µs
Follow current at 50/60 Hz
Uc
In
Iimp
If
Marking, blue positive
800 YY O
800
YY
O
1)
2)
3)
- Nominal voltage
- Year of production
- Non radioactive
At delivery AQL 0.65 level II, DIN ISO 2859
In darkness w/o storage
TOV – Temporary Over Voltage
KB AB E / KB AB PM
Please read Cautions and warnings and
Important notes at the end of this document.
Issue 02 / 2007-07-03
Page 2 of 4
Surge arrester
2-electrode arrester
B88069X5731B201
L1C-A800XP1
Dimensional drawing
Not to scale
Dimensions in mm
Non controlled document
Cautions and warnings
ƒ
ƒ
ƒ
ƒ
Depending on the incorporation position, the surge arrester may have to be additionally secured
by mechanical means.
Surge arresters may become hot in the event of longer periods of current stress (danger of
burning).
Surge arresters may be used only within their specified values. In case of overload, the head
contacts may fail or the component may be destroyed.
Damaged surge arresters must not be re-used.
KB AB E / KB AB PM
Please read Cautions and warnings and
Important notes at the end of this document.
Issue 02 / 2007-07-03
Page 3 of 4
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As a
rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of the customer application or other action taken by the customer (e.g. installation
of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the
event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequently,
we cannot guarantee that all products named in this publication will always be available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of
the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSSP, MiniBlue, MLSC, MotorCap, PCC,
PhaseCap, PhaseMod, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SIMID, SineFormer,
SIOV, SIP5D, SIP5K, WindCap, are trademarks registered or pending in Europe and in other
countries. Further information will be found on the Internet at www.epcos.com/trademarks.
8.
Page 4 of 4
Similar pages