Littelfuse EL731-20-X0 The el731 is a microprocessor-based Datasheet

Protection Relays and Controls
Earth-Leakage Protection–Grounded AC or DC Systems
EL731 SERIES
AC/DC Sensitive Earth-Leakage Relay
Description
The EL731 is a microprocessor-based AC/DC Sensitive
Earth-Leakage Relay that offers complete coverage for all
frequencies from 0 to 6,000 Hz. Two CTs are required for the
entire frequency range, or one CT can be used for only low- or
high-frequency detection. An RTD/PTC sensor input allows
over-temperature protection for a motor or drive. The EL731
offers metering, password-protected alarm and trip settings
and optional network communications. It is primarily used to
add low-level ground-fault protection to variable-speed drives,
and to dc circuits.
Simplified Circuit Diagram
CT1 A
CT2
A
A
GROUNDED
AC SUPPLY
CT1
B
GROUNDED
C
DC SUPPLY
–
EL731 SERIES
L1
A
+
EL731 SERIES
(AC/DC Sensitive
Earth-Leakage Relay)
L1
L2
(AC/DC Sensitive
Earth-Leakage Relay)
L2
AC Mode
DC Mode
For detailed wiring diagram, see adjacent page.
Accessories
Ordering Information
ORDERING NUMBER
CONTROL
POWER
COMMUNICATIONS
EL731-00-X0
120/240 Vac/Vdc
None
EL731-01-X0
120/240 Vac/Vdc
DeviceNet™
EL731-02-X0
120/240 Vac/Vdc
Profibus®
EL731-03-X0
120/240 Vac/Vdc
EtherNet/IP™
EL731-04-X0
120/240 Vac/Vdc
Modbus® TCP
EL731-10-X0
48 Vdc & 24 Vac
None
EL731-11-X0
48 Vdc & 24 Vac
DeviceNet™
EL731-12-X0
48 Vdc & 24 Vac
Profibus®
EL731-13-X0
48 Vdc & 24 Vac
EtherNet/IP™
EL731-14-X0
48 Vdc & 24 Vac
Modbus® TCP
EL731-20-X0
24 Vdc
None
EL731-21-X0
24 Vdc
DeviceNet™
EL731-22-X0
24 Vdc
Profibus®
EL731-23-X0
24 Vdc
EtherNet/IP
EL731-24-X0
24 Vdc
Modbus® TCP
A
EFCT Series Earth-Fault Current
Transformer
Required zero-sequence current transformer
specifically designed for low level detection.
AC700-CUA Series
Communication Adapter
Optional network-interface and firmwareupgrade communications adapters field-install
in EL731.
AC700-SMK DIN-rail & Surface-mount Adapter
EL731 plugs into adapter for back-plane
mounting.
™
ACCESSORIES
REQUIREMENT
EFCT Series CT
One Required
AC700-CUA Series Com. Unit
AC700-SMK Surface-Mount Kit
Optional
Optional
AC700-CVR-00 Watertight Cover (IP66) for
Panel-Mount Applications
Optional
PGA-0520 Analog Meter
Optional
Note: When building a part number, replace the “X” with “1” for AS/NZS 2081:2011 Compliant product, “0” otherwise.
© 2016 Littelfuse Protection Relays & Controls
Littelfuse.com/el731
Rev: 4-F-040716
Based on Manual Rev 6-F-031116
Protection Relays and Controls
Earth-Leakage Protection–Grounded AC or DC Systems
EL731 SERIES
AC/DC Sensitive Earth-Leakage Relay
Features & Benefits
FEATURES
BENEFITS
Adjustable pickup (30-5,000 mA)
Adjustable trip setting provides a wide range of low-level protection and system coordination
Frequency range (0-90 Hz, 20-6,000 Hz)
Operate in either AC or DC mode or both. Use single or combined ranges. Separate metering
32-char OLED display
Earth-leakage metering, setup and programming
Local LED indication
Visual Trip, Alarm, CT connection indication
CT-Loop monitoring
Alarms when CT is not connected
Analog output (4-20 mA)
Connect to DCS. Allows connection to an optional meter (PGA-0520) or control system
Adjustable time delay
Adjustable trip delay for quick protection and system coordination
Alarm and trip settings
Detect a deteriorating condition before damage occurs
Temperature-sensor input
Drive or motor temperature protection
Output contacts
3 programmable: Operate 2 alarm and 1 trip circuit
Network communication
Optional connection to plant network
Harmonic filtering
Eliminates nuisance tripping due to harmonic noise
Microprocessor based
No required calibration saves maintenance cost
Universal power supply
Provides flexibility for numerous applications
Wiring Diagram
LINE 1
Specifications
OPTIONAL
NETWORK
COMM
14 L1
AC/DC SENSITIVE
EARTH-LEAKAGE RELAY
EL731
L2/N 15
GND
K1
FAULT
18
K2
21
22
23
K3
24
25
EFCT-X
16
20
19
11 S21
26
20-6000 HZ CT
NC 17
10 S22
TC 5
TC
RTD/PTC TB 4
TB
TA 3
TA
9 SH2
EFCT-X
8 S11
7 S12
DC-90 HZ CT
13 RST
PTC
TC
ANALOG
OUT
TB
TA
12 GND
+–
AB 2
4-20mA
AA 1
RTD
t˚
+t˚
SUPPLY
6 SH1
REMOTE
RESET
IEEE Device Numbers
LINE 2/N
PGA-0520
AC ground fault (50G/N, 51G/N),
DC ground fault (79G),
PTC overtemperature (49),
RTD temperature (38, 49)
Supply Voltage
120/240 Vac/Vdc, 24 Vdc,
48 Vdc/24 Vac
Trip Level Settings
30-5,000 mA AC and DC
Alarm Level Settings
30-5,000 mA AC and DC
Trip Delay
0.05-2 s
Output Contacts
3 Form C (programmable)
Contact Operating Mode Fail-safe & non-fail-safe
Reset
Front panel and remote
Freq. Response, CT1
0-90 Hz
Freq. Response, CT2
20-6,000, 190-6,000, 20-90, 20-3,000 Hz;
selectable
Current Transformer
EFCT-x series
CT Detection
Open & short detection
Terminals
Plug-in, wire clamping,
24 to 12 AWG (0.2-2.5 mm2)
Communications
EtherNet/IP™, DeviceNet™, Profibus®,
Modbus® TCP (optional)
Analog Output
4-20 mA (selectable 0-5 A or
0-100% trip-level setting)
Conformal Coating
Standard feature
Dimensions
H 48 mm (1.9”); W 96 mm (3.8”);
D 129 mm (5.0”)
Approvals
UL Listed (E340889), CSA,
RCM (Australia), CE
Warranty
5 years
Mounting
Panel; Surface and DIN (with optional
AC700-SMK)
Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information.
© 2016 Littelfuse Protection Relays & Controls
Littelfuse.com/el731
Rev: 4-F-040716