FAB0307015 FEATURES 160 x 80 x 39 mm INPUT : 18 - 36 Vdc OUTPUT : 12V 50W Efficiency : 84 % typ. Convection cooled Cover and output low noise filtering as options APPLICATIONS This range of power supplies is specially designed for DIN Rail mounting applications. INPUT Voltage range : 18 - 36Vdc Undervoltage lockout : 16Vdc Nominal : 24 Vdc Input protection : fuse 5A transient and surges protected reverse polarity protected OUTPUT Voltage : 12V +/- 1% Current : 4,16A nominal Trim range : 90 % to 110 % of 12Vdc (factory adjustable) Overvoltage protection : 115-140 % Vnominal OUTPUT Conditions Typ. Max. Line regulation 0,05 % 0,5 % Load regulation 0,2 % 1% No load to full load Ripple and noise 1,5 % 3% Peak to peak, nom. Input ; full load Current limit 110 to 140 % of I nominal Low line to high line ; full load Vout = 95% of nominal ; Automatic restart 1/3 FAB0307015 OPTIONS Plastic cover Output common mode filtering reducing output ripple ENVIRONMENTAL Storage temperature : -20°C to +100°C Operating temperature in natural convection : -20°C to +60°C ambiant, vertical mounting, nominal Power ISOLATION Input to heatsink : 1500 Vdc Input to Output : 1500 Vdc Output to heatsink : 1500 Vdc GENERAL Safety : built to meet EN60950 EMI : built to meet EN55022A, conducted. 2/3 FAB0307015 MECHANICALS INPUT : J1 - Screw connector 3pts 1 2 3 PIN 1 DESCRIPTION 2 + IN 3 Ground - IN OUTPUT : J2 - Screw connector 2 pts PIN 1 DESCRIPTION 2 + output + output 1 2 1 2 OUPUT : J3 - Screw connector 2 pts 3/3 PIN 1 DESCRIPTION 2 - output - output