Maxim MAX16066ETL+ 12-channel/8-channel, flash-configurable system managers with nonvolatile fault register Datasheet

19-4717; Rev 0; 7/09
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
The MAX16065/MAX16066 flash-configurable system
managers monitor and sequence multiple system voltages. The MAX16065/MAX16066 can also accurately
monitor (±2.5%) one current channel using a dedicated
high-side current-sense amplifier. The MAX16065 manages up to twelve system voltages simultaneously, and
the MAX16066 manages up to eight supply voltages.
These devices integrate a selectable differential or single-ended analog-to-digital converter (ADC) and configurable outputs for sequencing power supplies. Device
configuration information, including overvoltage and
undervoltage limits, timing settings, and the sequencing order is stored in nonvolatile flash memory. During a
fault condition, fault flags and channel voltages can be
automatically stored in the nonvolatile flash memory for
later read-back.
The internal 1% accurate 10-bit ADC measures each
input and compares the result to one overvoltage, one
undervoltage, and one early warning limit that can be
configured as either undervoltage or overvoltage. A fault
signal asserts when a monitored voltage falls outside the
set limits. Up to three independent fault output signals
are configurable to assert under various fault conditions.
Because the MAX16065/MAX16066 support a powersupply voltage of up to 14V, they can be powered
directly from the 12V intermediate bus in many systems.
The integrated sequencer provides precise control over
the power-up and power-down order of up to twelve
(MAX16065) or up to eight (MAX16066) power supplies.
Eight outputs (EN_OUT1–EN_OUT8) are configurable
with charge-pump outputs to directly drive external
n-channel MOSFETs.
Features
S Operate from 2.8V to 14V
S ±2.5% Current-Monitoring Accuracy
S 1% Accurate 10-Bit ADC Monitors 12/8 Voltage
Inputs
S Single-Ended or Differential ADC for System
Voltage/Current Monitoring
S Integrated High-Side Current-Sense Amplifier
S 12/8 Monitored Inputs with Overvoltage/
Undervoltage/Early Warning Limit
S Nonvolatile Fault Event Logger
S Power-Up and Power-Down Sequencing
Capability
S Independent Secondary Sequence Block
S 12/8 Outputs for Sequencing/Power-Good
Indicators
S Two Programmable Fault Outputs and One Reset
Output
S Eight General-Purpose Inputs/Outputs
Configurable as:
Dedicated Fault Outputs
Watchdog Timer Function
Manual Reset
Margin Enable
S SMBus (with Timeout) or JTAG Interface
S Flash Configurable Time Delays and Thresholds
S -40NC to +85NC Operating Temperature Range
Applications
The MAX16065/MAX16066 include eight/six programmable general-purpose inputs/outputs (GPIO_s). GPIO_s
are flash configurable as dedicated fault outputs, as a
watchdog input or output, or as a manual reset.
Networking Equipment
The MAX16065/MAX16066 feature nonvolatile fault memory for recording information during system shutdown
events. The fault logger records a failure in the internal
flash and sets a lock bit protecting the stored fault data
from accidental erasure. An SMBus™ or a JTAG serial
interface configures the MAX16065/MAX16066. The
MAX16065 is available in a 48-pin, 7mm x 7mm, TQFN
package, and the MAX16066 is available in a 40-pin,
6mm x 6mm, TQFN package. Both devices are fully
specified from -40NC to +85NC.
Servers
SMBus is a trademark of Intel Corp.
Telecom Equipment (Base Stations, Access)
Storage/Raid Systems
Ordering Information
TEMP RANGE
PIN-PACKAGE
MAX16065ETM+
PART
-40NC to +85NC
48 TQFN-EP*
MAX16066ETL+
-40NC to +85NC
40 TQFN-EP*
+Denotes a lead(Pb)-free/RoHS-compliant package.
*EP = Exposed pad.
Pin Configuration and Typical Operating Circuits appear at
end of data sheet.
________________________________________________________________ Maxim Integrated Products 1
For pricing, delivery, and ordering information, please contact Maxim Direct at 1-888-629-4642,
or visit Maxim’s website at www.maxim-ic.com.
MAX16065/MAX16066
General Description
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
ABSOLUTE MAXIMUM RATINGS
VCC, CSP, CSM to GND.........................................-0.3V to +15V
CSP to CSM...........................................................-0.7V to +0.7V
MON_, GPIO_, SCL, SDA, A0, RESET, EN_OUT9–EN_OUT12 to
GND (programmed as open-drain outputs).........-0.3V to +6V
EN, TCK, TMS, TDI to GND.....................................-0.3V to +4V
DBP, ABP to GND....-0.3V to the lower of +3V and (VCC + 0.3V)
EN_OUT1–EN_OUT8 to GND (programmed as open-drain
outputs) .............................................................-0.3V to +15V
TDO, EN_OUT_, GPIO_, RESET (programmed as push-pull
outputs)............................................... -0.3V to (VDBP + 0.3V)
Input/Output Current ..........................................................20mA
Continuous Power Dissipation (TA = +70NC)
40-Pin TQFN (derate 26.3mW/NC above +70NC)........2105mW
48-Pin TQFN (derate 27.8mW/NC above +70NC)........2222mW
Operating Temperature Range........................... -40NC to +85NC
Junction Temperature .....................................................+150NC
Storage Temperature Range............................. -65NC to +150NC
Lead Temperature (soldering, 10s).................................+300NC
Stresses beyond those listed under “Absolute Maximum Ratings” may cause permanent damage to the device. These are stress ratings only, and functional operation of the device at these
or any other conditions beyond those indicated in the operational sections of the specifications is not implied. Exposure to absolute maximum rating conditions for extended periods may
affect device reliability.
ELECTRICAL CHARACTERISTICS
(VCC = 2.8V to 14V, TA = -40NC to +85NC, unless otherwise specified. Typical values are at ABP = DBP = VCC = 3.3V, TA = +25NC.)
(Note 1)
PARAMETER
Operating Voltage Range
Undervoltage Lockout (Rising)
Undervoltage Lockout Hysteresis
Minimum Flash Operating
Voltage
Supply Current
SYMBOL
VCC
VUVLO
CONDITIONS
MIN
Reset output asserted low
1.2
(Note 2)
2.8
ICC
MAX
14
Minimum voltage on VCC to ensure the
device is flash configurable
2.7
VUVLO_HYS
Vflash
TYP
UNITS
V
V
100
mV
Minimum voltage on VCC to ensure flash
erase and write operations
2.7
V
No load on output pins
4.5
7
During flash writing cycle
10
14
mA
ABP Regulator Voltage
VABP
CABP = 1μF, no load, VCC = 5V
2.85
3
3.15
DBP Regulator Voltage
VDBP
CABP = 1μF, no load, VCC = 5V
2.8
3
3.1
V
Boot Time
tBOOT
VCC > VUVLO
200
350
μs
8-byte word
122
Flash Writing Time
Internal Timing Accuracy
EN Input Voltage
EN Input Current
Input Voltage Range
(Note 3)
VTH_EN_R
EN voltage rising
VTH_EN_F
EN voltage falling
IEN
-8
ms
+8
1.41
1.365
1.39
V
1.415
%
V
-0.5
+0.5
μA
0
5.5
V
2 _______________________________________________________________________________________
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
(VCC = 2.8V to 14V, TA = -40NC to +85NC, unless otherwise specified. Typical values are at ABP = DBP = VCC = 3.3V, TA = +25NC.)
(Note 1)
PARAMETER
SYMBOL
CONDITIONS
MIN
TYP
MAX
UNITS
Bits
LSB
ADC DC ACCURACY
Resolution
Gain Error
ADCGAIN
Offset Error
ADCOFF
10
0.35
0.70
1
Integral Nonlinearity
ADCINL
1
LSB
Differential Nonlinearity
ADCDNL
1
LSB
50
μs
ADC Total Monitoring Cycle Time
tCYCLE
ADC IN_ Ranges
TA = +25°C
TA = -40°C to +85°C
No MON_ fault detected
40
1 LSB = 5.43mV
5.56
1 LSB = 2.72mV
2.78
1 LSB = 1.36mV
1.39
%
V
CURRENT SENSE
CSP Input-Voltage Range
VCSP
3
ICSP
Input Bias Current
ICSM
CSP Total Unadjusted Error
Overcurrent Differential
Threshold
VSENSE Fault Threshold
Hysteresis
CSPERR
OVCTH
VCSP = VCSM
VSENSE Ranges
VCSP VCSM
46
51
56
Gain = 12
94
101
108
Gain = 6
190
202
210
0.5
CMRRSNS
PSRRSNS
μA
%FSR
mV
0
3
4
5
r73h[6:5] = ‘10’
12
16
20
r73h[6:5] = ‘11’
50
64
60
Gain = 6
232
Gain = 12
116
Gain = 24
58
ms
mV
29
-2.5
Q0.2
+2.5
-4
Q0.2
+4
VSENSE = 25mV, gain = 24
Q0.5
VSENSE = 10mV, gain = 48
Q1
VCSP > 4V
V
% OVCTH
r73h[6:5] = ‘01’
VSENSE = 20mV to 100mV, VCSP = 5V,
gain = 6
Power-Supply Rejection Ratio
30.5
Gain = 24
VSENSE = 50mV, gain = 12
Common-Mode Rejection Ratio
25
2
VSENSE = 150mV (gain = 6 only)
Gain Accuracy
5
21.5
Gain = 48
ADC Current Measurement
Accuracy
3
Gain = 48
OVCHYS
OVCDEL
25
(Note 4)
r73h[6:5] = ‘00’
Secondary Overcurrent Threshold
Timeout
14
14
-1.5
+1.5
%
%
80
dB
80
dB
_______________________________________________________________________________________ 3
MAX16065/MAX16066
ELECTRICAL CHARACTERISTICS (continued)
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
ELECTRICAL CHARACTERISTICS (continued)
(VCC = 2.8V to 14V, TA = -40NC to +85NC, unless otherwise specified. Typical values are at ABP = DBP = VCC = 3.3V, TA = +25NC.)
(Note 1)
PARAMETER
SYMBOL
CONDITIONS
MIN
TYP
MAX
UNITS
OUTPUTS (EN_OUT_, RESET, GPIO_)
ISINK = 2mA
0.4
ISINK = 10mA, GPIO_ only
0.7
VCC = 1.2V, ISINK = 100μA (RESET only)
0.3
Maximum Output Sink Current
Total current into EN_OUT_, RESET,
GPIO_, VCC = 3.3V
30
Output-Voltage High (Push-Pull)
ISOURCE = 100μA
Output-Voltage Low
VOL
EN_OUT1–EN_OUT8 = 13.2V
OUT_ Overdrive (Charge Pump)
(EN_OUT1–EN_OUT8 Only)
ICH_UP
mA
V
1
Output Leakage (Open Drain)
OUT_ Pullup Current (Charge
Pump)
2.4
V
5
IGATE_ = 1μA
10
11
During power up, VGATE = 1V
2.5
4
13
μA
V
μA
SMBus INTERFACE
Logic-Input Low Voltage
VIL
Input voltage falling
Logic-Input High Voltage
VIH
Input voltage rising
2.0
IN = GND or VCC
-1
Input Leakage Current
Output Sink Current
Input Capacitance
SMBus Timeout
VOL
V
+1
μA
0.4
V
35
ms
0.8
V
V
ISINK = 3mA
CIN
tTIMEOUT
0.8
5
SCL time low for reset
25
pF
INPUTS (A0, GPIO_)
Input Logic-Low
VIL
Input Logic-High
VIH
2.0
V
WDI Pulse Width
tWDI
100
ns
MR Pulse Width
tMR
1
μs
MR to RESET Delay
0.5
μs
MR Glitch Rejection
SMBus TIMING
100
ns
Serial Clock Frequency
fSCL
Bus Free Time Between STOP
and START Condition
tBUF
1.3
μs
START Condition Setup Time
tSU:STA
0.6
μs
START Condition Hold Time
tHD:STA
0.6
μs
STOP Condition Setup Time
tSU:STO
0.6
μs
Clock Low Period
tLOW
1.3
μs
Clock High Period
tHIGH
0.6
μs
tSU:DAT
100
ns
Data Setup Time
400
4 _______________________________________________________________________________________
kHz
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
(VCC = 2.8V to 14V, TA = -40NC to +85NC, unless otherwise specified. Typical values are at ABP = DBP = VCC = 3.3V, TA = +25NC.)
(Note 1)
PARAMETER
SYMBOL
Output Fall Time
tOF
Data Hold Time
tHD:DAT
Pulse Width of Spike Suppressed
CONDITIONS
MIN
TYP
CBUS = 10pF to 400pF
From 50% SCL falling to SDA change
0.3
tSP
MAX
UNITS
250
ns
0.9
μs
30
ns
JTAG INTERFACE
TDI, TMS, TCK Logic-Low Input
Voltage
VIL
Input voltage falling
TDI, TMS, TCK Logic-High Input
Voltage
VIH
Input voltage rising
TDO Logic-Output Low Voltage
VOL
ISINK = 3mA
TDO Logic-Output High Voltage
VOH
ISOURCE = 200μA
2.4
TDI, TMS Pullup Resistors
RPU
Pullup to DBP
40
I/O Capacitance
CI/O
TCK Clock Period
0.8
2
V
0.4
V
60
kω
V
50
5
t1
TCK High/Low Time
V
pF
1000
500
ns
t2, t3
50
TCK to TMS, TDI Setup Time
t4
15
ns
TCK to TMS, TDI Hold Time
t5
10
TCK to TDO Delay
t6
500
ns
TCK to TDO High-Z Delay
t7
500
ns
ns
ns
Note 1: Specifications are guaranteed for the stated global conditions, unless otherwise noted. 100% production tested at TA =
+25NC and TA = +85NC. Specifications at TA = -40NC are guaranteed by design.
Note 2: For VCC of 3.6V or lower, connect VCC, DBP, and ABP together. For higher supply applications, connect only VCC to the
supply rail.
Note 3: Applies to RESET, fault, autoretry, sequence delays, and watchdog timeout.
Note 4: Total unadjusted error is a combination of gain, offset, and quantization error.
_______________________________________________________________________________________ 5
MAX16065/MAX16066
ELECTRICAL CHARACTERISTICS
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
SDA
tSU:DAT
tHD:DAT
tLOW
tBUF
tSU:STA
tHD:STA
tSU:STO
SCL
tHIGH
tHD:STA
tR
tF
START
CONDITION
STOP
CONDITION
REPEATED START
CONDITION
Figure 1. SMBus Timing Diagram
t1
t2
t3
TCK
t4
t5
TDI, TMS
t6
t7
TDO
Figure 2. JTAG Timing Diagram
6 _______________________________________________________________________________________
START
CONDITION
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
VCC SUPPLY CURRENT
vs. VCC SUPPLY VOLTAGE
TA = -40NC
ABP AND DBP
REGULATORS ACTIVE
2
FOR LOW-VOLTAGE APPLICATIONS
VCC < 3.6V CONNECT ABP AND
DBP TO VCC
1
0
2
4
6
8
10
0.6
0.4
0.2
MAX16065 toc03
1.002
1.000
0.998
0.996
0.994
0.992
-40
14
-20
0
20
40
60
80
-40
-20
0
20
40
60
VCC (V)
TEMPERATURE (NC)
TEMPERATURE (NC)
TRANSIENT DURATION
vs. THRESHOLD OVERDRIVE (EN)
NORMALIZED TIMING ACCURACY
vs. TEMPERATURE
MON_ DEGLITCH
vs. TRANSIENT DURATION
120
100
80
60
40
0.984
0.982
0.980
0.978
0.976
120
100
0
10
1
100
80
60
40
20
0.974
20
80
MAX16065 toc06
0.986
TRANSIENT DURATION (µs)
MAX16065 toc04
140
0
0.972
-40
-20
0
20
40
60
2
80
4
8
16
EN OVERDRIVE (mV)
TEMPERATURE (NC)
DEGLITCH VALUE
MR TO RESET PROPAGATION DELAY
vs. TEMPERATURE
OUTPUT VOLTAGE vs. SINK CURRENT
(OUT = LOW)
OUTPUT-VOLTAGE HIGH vs. SOURCE
CURRENT (CHARGE-PUMP OUTPUT)
EN_OUT_
0.35
1.4
12
10
0.30
1.0
MIN
0.8
8
0.25
VOUT (V)
VOUT (V)
1.2
GPIO_
RESET
0.20
0.15
0.6
0.4
0.10
0.2
0.05
-40
-20
0
20
40
TEMPERATURE (NC)
60
80
6
4
2
0
0
MAX16065 toc09
MAX
0.40
MAX16065 toc08
1.8
1.6
0.45
MAX16065 toc07
2.0
DELAY (µs)
5.6V RANGE,
HALF SCALE,
PUV THRESHOLD
1.004
0
12
160
TRANSIENT DURATION (µs)
0.8
MAX16065 toc05
0
1.0
1.006
NORMALIZED EN THRESHOLD
TA = +25NC
3
NORMALIZED SLOT DELAY
ICC (mA)
4
1.2
MAX16065 toc02
5
TA = +85NC
NORMALIZED MON_ THRESHOLD
ABP AND DBP CONNECTED TO VCC
MAX16065 toc01
6
NORMALIZED EN THRESHOLD
vs. TEMPERATURE
NORMALIZED MON_ THRESHOLD
vs. TEMPERATURE
0
5
10
IOUT (mA)
15
20
0
0
1
2
3
4
IOUT (µA)
_______________________________________________________________________________________ 7
MAX16065/MAX16066
Typical Operating Characteristics
(Typical values are at VCC = 3.3V, TA = +25°C, unless otherwise noted.)
Typical Operating Characteristics (continued)
(Typical values are at VCC = 3.3V, TA = +25°C, unless otherwise noted.)
0.8
0.6
0.8
0.6
0.4
3.0
0.2
0.2
GPIO_
EN_OUT_
2.7
2.6
2.5
RESET
2.4
500
0
1000
-0.2
-0.4
-0.4
-0.6
-0.6
-0.8
-0.8
-1.0
-1.0
0
1500
128 256 384 512 640 768 896 1024
IOUT (µA)
0
CURRENT-SENSE TRANSIENT DURATION
vs. CSP-CSM OVERDRIVE
MAX16065 toc14
1.0
MAX16065 toc13
1.03
200mV
CODE (LSB)
CURRENT-SENSE ACCURACY
vs. CSP-CSM VOLTAGE
1.05
0.8
0.6
0.4
ERROR (mV)
25mV
1.01
0.99
100mV
0.2
0
-0.2
-0.4
0.97
0.95
1.8
1.6
0
20
40
60
80
1.4
1.2
1.0
0.8
0.6
-0.6
0.4
-0.8
0.2
-1.0
-20
128 256 384 512 640 768 896 1024
CODE (LSB)
NORMALIZED CURRENT-SENSE
ACCURACY vs. TEMPERATURE
-40
0
-0.2
MAX16065 toc15
2.8
0
TRANSIENT DURATION (Fs)
2.9
DNL (LSB)
0.4
INL (LSB)
3.1
0
0
5
10
15
20
25
30
0
20
40
60
CSP-CSM VOLTAGE (mV)
CSP-CSM OVERDRIVE (mV)
FET TURN-ON WITH CHARGE PUMP
SEQUENCING MODE
RESET OUTPUT CURRENT
vs. SUPPLY VOLTAGE
MAX16065 toc17
MAX16065 toc16
18
ABP AND DBP
CONNECTED TO VCC
16
OUTPUT CURRENT (mA)
EN_OUT
ILOAD
100
80
TEMPERATURE (NC)
MAX16065 toc18
3.2
DIFFERENTIAL NONLINEARITY vs. CODE
1.0
MAX16065 toc11
3.3
VOUT (V)
INTEGRAL NONLINEARITY vs. CODE
1.0
MAX16065 toc10
3.4
MAX16065 toc12
OUTPUT-VOLTAGE HIGH vs. SOURCE
CURRENT (PUSH-PULL OUTPUT)
NORMALIZED CURRENT-SENSE OUTPUT
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
14
12
ABP AND DBP
REGULATORS ACTIVE
10
8
6
4
VLOAD
2
VRESET = 0.3V
0
20ms/div
20ms/div
0
2
4
6
8
10
SUPPLY VOLTAGE (V)
8 _______________________________________________________________________________________
12
14
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
PIN
NAME
FUNCTION
MAX16065
MAX16066
1–6, 43–46
1–5, 36–40
MON1–
MON10
Monitor Voltage Inputs. Set monitor voltage range through configuration
registers. Measured value written to ADC register can be read back through the
SMBus or JTAG interface.
47, 48
—
MON11,
MON12
Monitor Voltage Inputs. Set monitor voltage range through configuration
registers. Measured value written to ADC register can be read back through the
SMBus or JTAG interface.
7
6
CSP
Current-Sense Amplifier Positive Input. Connect CSP to the source side of the
external sense resistor.
8
7
CSM
Current-Sense Amplifier Negative Input. Connect CSM to the load side of the
external sense resistor.
9
8
RESET
10
9
TMS
Configurable Reset Output
JTAG Test Mode Select
11
10
TDI
JTAG Test Data Input
12
11
TCK
JTAG Test Clock
13
12
TDO
JTAG Test Data Output
14
13
SDA
SMBus Serial-Data Open-Drain Input/Output
15
14
A0
16
15
SCL
SMBus Serial-Clock Input
17, 42
16, 35
GND
Ground
20–25
17–22
GPIO1–
GPIO6
General-Purpose Input/Outputs. GPIO_s can be configured to act as a TTL input,
a push-pull, open-drain, or high-impedance output or a pulldown circuit during a
fault event.
18, 19
—
GPIO7,
GPIO8
General-Purpose Input/Outputs. GPIO_s can be configured to act as a TTL input,
a push-pull, open-drain, or high-impedance output or a pulldown circuit during a
fault event or reverse sequencing.
26–29
—
EN_OUT12–
EN_OUT9
Outputs. Set EN_OUT_ with active-high/active-low logic and with push-pull or
open-drain configuration. EN_OUT_ can be asserted by a combination of IN_
voltages configurable through the flash.
Outputs. Set EN_OUT_ with active-high/active-low logic and with push-pull or
open-drain configuration. EN_OUT_ can be asserted by a combination of IN_
voltages configurable through the flash. EN_OUT1–EN_OUT8 can be configured
with a charge-pump output (+10V above GND) that can drive an external
n-channel MOSFET.
Four-State SMBus Address. Address sampled upon POR.
30–37
23–30
EN_OUT1–
EN_OUT8
38
31
EN
39
32
DBP
Digital Bypass. All push-pull outputs are referenced to DBP. Bypass DBP with a
1FF capacitor to GND.
40
33
VCC
Device Power Supply. Connect VCC to a voltage from 2.8V to 14V. Bypass VCC
with a 10FF capacitor to GND.
41
34
ABP
Analog Bypass. Bypass ABP with a 1FF ceramic capacitor to GND.
—
—
EP
Analog Enable Input. All outputs deassert when VEN is below the enable
threshold.
Exposed Pad. Internally connected to GND. Connect to ground, but do not use
as the main ground connection.
_______________________________________________________________________________________ 9
MAX16065/MAX16066
Pin Description
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Functional Diagram
ABP
VCC
DBP
OVERC
RESET
MAX16065
RESET
ANYFAULT
FAULT1
DECODE
LOGIC
FAULT2
MR
C
O
N
T
R
O
L
MARGIN
WATCHDOG
TIMER
EN
WDI
WDO
GPIO1–GPIO8
PRIMARY
SEQUENCE
BLOCK
1.4V
AV
REF
MON1–
MON12
VOLTAGE
SCALING
AND
MUX
10-BIT ADC
(SAR)
ADC
REGISTERS
DIGITAL
COMPARATORS
RAM
REGISTERS
SMBus INTERFACE
AO
SCL
SDA
FLASH
MEMORY
GND
JTAG
INTERFACE
TDO
TDI
GPIO2
GPIO3
GPIO4
GPIO5
GPIO6
GPIO7
EN_OUT1–
EN_OUT12
SECONDARY
SEQUENCE
BLOCK
VCSTH
GPIO1
GPIO8
CSP
CSM
G
P
I
O
TCK
TMS
10 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
The MAX16065 manages up to twelve system power
supplies and the MAX16066 can manage up to eight
system power supplies. After boot-up, if EN is high and
the software enable bit is set to ‘1,’ a power-up sequence
begins based on the configuration stored in flash and
the EN_OUT_s are controlled accordingly. When the
power-up sequence is successfully completed, the
monitoring phase begins. An internal multiplexer cycles
through each MON_ input. At each multiplexer stop, the
10-bit ADC converts the monitored analog voltage to a
digital result and stores the result in a register. Each time
a conversion cycle (50Fs, max) completes, internal logic
circuitry compares the conversion results to the overvoltage and undervoltage thresholds stored in memory.
When a result violates a programmed threshold, the
conversion can be configured to generate a fault. GPIO_
can be programmed to assert on combinations of faults.
Additionally, faults can be configured to shut off the system and trigger the nonvolatile fault logger, which writes
all fault information automatically to the flash and writeprotects the data to prevent accidental erasure.
The MAX16065/MAX16066 contain both SMBus and
JTAG serial interfaces for accessing registers and flash.
Use only one interface at any given time. For more information on how to access the internal memory through
these interfaces, see the SMBus-Compatible Interface
and JTAG Serial Interface sections. The memory map
is divided into three pages with access controlled by
special SMBus and JTAG commands.
The factory-default values at POR (power-on reset) for all
RAM registers are ‘0’s. POR occurs when VCC reaches
the undervoltage-lockout threshold (UVLO) of 2.8V (max).
At POR, the device begins a boot-up sequence. During
the boot-up sequence, all monitored inputs are masked
from initiating faults and flash contents are copied to
the respective register locations. During boot-up, the
MAX16065/MAX16066 are not accessible through the
serial interface. The boot-up sequence takes up to
150Fs, after which the device is ready for normal operation. RESET is asserted low up to the boot-up phase and
remains asserted for its programmed timeout period once
sequencing is completed and all monitored channels
are within their respective thresholds. Up to the boot-up
phase, the GPIO_s and EN_OUT_s are high impedance.
Power
Apply 2.8V to 14V to VCC to power the MAX16065/
MAX16066. Bypass VCC to ground with a 10FF capacitor. Two internal voltage regulators, ABP and DBP,
supply power to the analog and digital circuitry within
the device. For operation at 3.6V or lower, disable the
regulators by connecting ABP and DBP to VCC.
ABP is a 3.0V (typ) voltage regulator that powers the internal analog circuitry. Bypass ABP to GND with a 1FF ceramic capacitor installed as close to the device as possible.
DBP is an internal 3.0V (typ) voltage regulator. DBP
powers flash and digital circuitry. All push-pull outputs
refer to DBP. DBP supplies the input voltage to the internal charge pump when the programmable outputs are
configured as charge-pump outputs. Bypass the DBP
output to GND with a 1FF ceramic capacitor installed as
close as possible to the device.
Do not power external circuitry from ABP or DBP.
Sequencing
To sequence a system of power supplies safely, the
output voltage of a power supply must be good before
the next power supply may turn on. Connect EN_OUT_
outputs to the enable input of an external power supply
and connect MON_ inputs to the output of the power
supply for voltage monitoring. More than one MON_ can
be used if the power supply has multiple outputs.
Sequence Order
The MAX16065/MAX16066 provide a system of ordered
slots to sequence multiple power supplies. To determine
the sequence order, assign each EN_OUT_ to a slot
ranging from Slot 1 to Slot 12. EN_OUT_(s) assigned to
Slot 1 are turned on first, followed by outputs assigned
to Slot 2, and so on through Slot 12. Multiple EN_OUT_s
assigned to the same slot turn on at the same time.
Each slot includes a built-in configurable sequence delay
(registers r77h to r7Dh) ranging from 20Fs to 1.6s. During
a reverse sequence, slots are turned off in reverse order
starting from Slot 12. The MAX16065/MAX16066 can be
configured to power-down in simultaneous mode or in
reverse sequence mode as set in r75h[0]. See Tables 5
and 6 for the EN_OUT_ slot assignment bits, and Tables
3 and 4 for the sequence delays.
During power-up or power-down sequencing, the current sequencer state can be found in r21h[4:0].
______________________________________________________________________________________ 11
MAX16065/MAX16066
Detailed Description
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 1. Current Sequencer Slot
REGISTER
ADDRESS
21h
BIT RANGE
DESCRIPTION
[4:0]
Current Sequencer State:
00000 = Slot 0
00001 = Slot 1
00010 = Slot 2
00011 = Slot 3
00100 = Slot 4
00101 = Slot 5
00110 = Slot 6
00111 = Slot 7
01000 = Slot 8
01001 = Slot 9
01010 = Slot 10
01011 = Slot 11
01100 = Slot 12
01101 = Secondary sequence monitoring mode
01110 = Primary sequence fault
01111 = Primary sequence monitoring mode
10000 = Secondary sequence fault
10001 to 11111 = Reserved
[7:5]
Reserved
Multiple Sequencing Groups
The MAX16065/MAX16066 sequencing slots can be
split into two groups: the primary sequence and the secondary sequence. The last slot of the primary sequence
is selected using register bits r7Dh[7:4]. The secondary sequence begins at the slot after the one specified in register bits 7Dh[7:4]. The primary sequence
is controlled by the EN input and the software enable
bit in r73h[0]. Outputs assigned to slots in the primary
sequence turn on, and monitoring begins for inputs
assigned to these slots. RESET deasserts after the primary sequence and timeout period completes.
To initiate secondary sequencing and monitoring, set
the software enable 73h[1] bit to 1. Additionally, if GPIO_
is configured as EN2 then both the software enable 2
and EN2 must be high. Outputs assigned to slots in the
secondary sequence turn on, and monitoring begins for
inputs assigned to these slots. If a GPIO_ is configured
as the RESET2 output, it deasserts after the secondary
sequence and timeout period completes.
If a critical fault occurs in the primary sequence group,
both sequence groups automatically shut down. If a
critical fault occurs in the secondary sequence group,
then just the outputs assigned to slots in the secondary sequence turn off. The failing slot in secondary
sequence is stored in r1Dh.
Multiple sequencing groups can be used to conserve
power by powering down secondary systems when not
in use.
Enable and Enable2
To initiate sequencing/tracking and enable monitoring,
the voltage at EN must be above 1.4V and the software
enable bit in r73h[0] must be set to ‘1.’ To power down
and disable monitoring, either pull EN below 1.35V or
set the Software Enable bit to ‘0.’ See Table 2 for the
software enable bit configurations. Connect EN to ABP
if not used.
If a fault condition occurs during the power-up cycle,
the EN_OUT_ outputs are powered down immediately,
regardless of the state of EN. In the monitoring state,
if EN falls below the threshold, the sequencing state
machine begins the power-down sequence. If EN rises
above the threshold during the power-down sequence,
the sequence state machine continues the power-down
sequence until all the channels are powered off and then
the device immediately begins the power-up sequence.
When in the monitoring state, a register bit, ENRESET,
is set to a ‘1’ when EN falls below the undervoltage
threshold. This register bit latches and must be cleared
through software. This bit indicates if RESET asserted
low due to EN going under the threshold. The POR state
of ENRESET is ‘0’. The bit is only set on a falling edge
12 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
To initiate secondary sequencing and monitoring set the
software enable r73h[1] bit to 1. Additionally, if GPIO_ is
configured as EN2 then both the software enable 2 bit and
EN2 must be high. To power-down and disable monitoring, either drive EN2 low or set the Software Enable2 bit to
‘0.’ See Table 2 for the software enable bit configurations.
When a fault condition occurs during the power-up cycle,
the EN_OUT_ outputs are powered down immediately,
independent of the state of EN2. Drive EN2 low to begin
the secondary power-down sequence. When EN2 is driv-
en high during the power-down sequence, the sequence
state machine continues the power-down sequence until
the secondary channels are powered off and then the
device immediately begins the power-up sequence.
Monitoring Inputs While Sequencing
An enabled MON_ input can be assigned to a slot
ranging from Slot 1 to Slot 12. EN_OUT_s are always
asserted at the beginning of a slot. The supply voltages connected to the MON_ inputs must exceed the
undervoltage threshold before the programmed timeout
period expires otherwise a fault condition will occur. The
undervoltage threshold checking cannot be disabled
during power-up and power-down. See Tables 5 and
6 for the MON_ slot assignment bits. The programmed
Table 2. Software Enable Configurations
REGISTER
ADDRESS
73h
FLASH
ADDRESS
BIT RANGE
273h
DESCRIPTION
[0]
Software enable 1 (primary sequence)
[1]
Software enable 2 (secondary sequence)
[2]
1 = Margin mode enabled
[3]
Early warning threshold select
0 = Early warning is undervoltage
1 = Early warning is overvoltage
[4]
Independent watchdog mode enable
1 = Watchdog timer is independent of sequencer
0 = Watchdog timer boots after sequence completes
Table 3. Slot Delay Register
REGISTER
ADDRESS
FLASH
ADDRESS
77h
277h
78h
79h
7Ah
7Bh
7Ch
7Dh
278h
279h
27Ah
27Bh
27Ch
27Dh
BIT RANGE
DESCRIPTION
[3:0]
Sequence Slot 0 Delay
[7:4]
Sequence Slot 1 Delay
[3:0]
Sequence Slot 2 Delay
[7:4]
Sequence Slot 3 Delay
[3:0]
Sequence Slot 4 Delay
[7:4]
Sequence Slot 5 Delay
[3:0]
Sequence Slot 6 Delay
[7:4]
Sequence Slot 7 Delay
[3:0]
Sequence Slot 8 Delay
[7:4]
Sequence Slot 9 Delay
[3:0]
Sequence Slot 10 Delay
[7:4]
Sequence Slot 11 Delay
[3:0]
Sequence Slot 12 Delay
[7:4]
Grouped Sequence Split Location, Final Slot of Primary Sequence
______________________________________________________________________________________ 13
MAX16065/MAX16066
of the EN comparator output or the software enable bit.
If operating in latch-on fault mode, toggle EN or toggle
the Software Enable bit to clear the latch condition and
restart the device once the fault condition has been
removed.
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 4. Power-Up/Power-Down Slot Delays
CODE
VALUE
0000
0001
0010
0011
0100
0101
0110
0111
1000
1001
25Fs
500Fs
1ms
2ms
3ms
4ms
6ms
8ms
10ms
12ms
1010
1011
25ms
100ms
1100
1101
200ms
400ms
1110
1111
800ms
1.6s
sequence delay is then counted before moving to the
next slot.
Slot 0 does not monitor any MON_ input and does not
control any EN_OUT_. Slot 0 waits for the Software
Enable bit r73h[0] to be a logic-high and for the voltage
on EN to rise above 1.4V before initiating the power-up
sequence and counting its own sequence delay.
Any MON_ input that suffers a fault that occurs during
power-up sequencing causes all the EN_OUT_s to turn
off and the sequencer to shut down regardless of the
state of the critical fault enables (see the Faults section
for more information). If a MON_ input is less critical to
system operation, it can be configured as “monitoring
only” (see Table 6) for either the primary or secondary
sequence. Monitoring for MON_ inputs assigned as
“monitoring only” begins after sequencing is complete
for that group, and can trigger a critical fault only if
specifically configured to do so using the critical fault
enables.
Power-Up
On power-up, when EN is high and the Software Enable
bit is 1, the MAX16065/MAX16066 begin sequencing
with Slot 0. After the sequencing delay for Slot 0 expires,
the sequencer advances to Slot 1, and all EN_OUT_s
assigned to the slot assert. All MON_ inputs assigned to
Slot 1 are monitored and when the voltage rises above the
UV fault threshold, the sequence delay counter is started.
When the tFAULT counter expires before all MON_ inputs
assigned to the slot are above the fault UV threshold,
a fault asserts. EN_OUT_ outputs are disabled and the
MAX16065/MAX16066 return to the power-off state.
When the sequence delay expires, the MAX16065/
MAX16066 proceed to the next slot.
After the voltages on all MON_ inputs assigned to the
last slot exceed the UV fault threshold and the slot delay
expires, the MAX16065/MAX16066 start the reset timeout counter. After the reset timeout, RESET deasserts.
r75h[4:1] sets the tFAULT delay. See Table 7 for details.
Power-Down
Power-down starts when EN is pulled low or the Software
Enable bit is set to ‘0.’ Power down EN_OUT_s simultaneously or in reverse-sequence mode by setting the
Reverse Sequence bit (r75h[0]) appropriately.
Reverse-Sequence Mode
When the MAX16065/MAX16066 are fully powered up
(including secondary sequence group, if enabled) and
EN or the Software Enable bit is set to ‘0’, the EN_OUT_s
assigned to Slot 12 deassert, the MAX16065/MAX16066
wait for the Slot 12 sequence delay and then proceed to
the previous slot (Slot 11), and so on until the EN_OUT_s
assigned to Slot 1 turn off. When simultaneous powerdown is selected (r75h[0] set to ‘0’), all EN_OUT_s turn
off at the same time.
14 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
SLOT 1
SLOT 2
(PRIMARY
SEQUENCE)
tFAULT
SLOT1-SLOT2
DELAY
EN_OUT1
FINAL SLOT
SLOT1-SLOT2
DELAY
OV
BOTH ARE
ASSIGNED
TO SLOT 1
MON4
UV
EN_OUT2
UV/OV
MONITORING BEGINS
WHEN MON4
REACHES UV
THRESHOLD
MON4 MUST
REACH UV
THRESHOLD BY THIS
TIME
BOTH ARE
ASSIGNED
TO SLOT 2
RESET
TIMEOUT
MON3
MON5
RESET
EN
Figure 3. Delay and Reset Timing
Table 5. MON_ and EN_OUT_ Assignment Registers
REGISTER
ADDRESS
FLASH
ADDRESS
7Eh
27Eh
7Fh
27Fh
80h
280h
81h
281h
82h
282h
83h
283h
BIT RANGE
DESCRIPTION
[3:0]
MON1
[7:4]
MON2
[3:0]
MON3
[7:4]
MON4
[3:0]
MON5
[7:4]
MON6
[3:0]
MON7
[7:4]
MON8
[3:0]
MON9
[7:4]
MON10
[3:0]
MON11
[7:4]
MON12
______________________________________________________________________________________ 15
MAX16065/MAX16066
SLOT 0
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 5. MON_ and EN_OUT_ Assignment Registers (continued)
REGISTER
ADDRESS
FLASH
ADDRESS
84h
284h
85h
86h
87h
88h
89h
285h
286h
287h
288h
289h
BIT RANGE
DESCRIPTION
[3:0]
EN_OUT1
[7:4]
EN_OUT2
[3:0]
EN_OUT3
[7:4]
EN_OUT4
[3:0]
EN_OUT5
[7:4]
EN_OUT6
[3:0]
EN_OUT7
[7:4]
EN_OUT8
[3:0]
EN_OUT9
[7:4]
EN_OUT10
[3:0]
EN_OUT11
[7:4]
EN_OUT12
Table 6. MON_ and EN_OUT_ Slot Assignment Codes
SLOT ASSIGNMENT
CODE
MON_ DESCRIPTION
OUT_ DESCRIPTION
0000
0001
Not assigned
Slot 1
Not assigned
Slot 1
0010
0011
Slot 2
Slot 3
Slot 2
Slot 3
0100
0101
Slot 4
Slot 5
Slot 4
Slot 5
0110
0111
Slot 6
Slot 7
1000
1001
1010
1011
1100
1101
1110
1111
Slot 8
Slot 9
Slot 10
Slot 11
Slot 12
Monitoring only, primary sequence
Monitoring only, secondary sequence
Not assigned
Slot 6
Slot 7
Slot 8
Slot 9
Slot 10
Slot 11
Slot 12
General-purpose input (EN_OUT9–EN_OUT12 only)
General-purpose output (EN_OUT9–EN_OUT12 only)
Not assigned
16 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
CODE
DELAY
0000
0001
0010
0011
0100
0101
0110
0111
1000
120Fs
150Fs
1001
6ms
1010
1011
1100
1101
1110
1111
10ms
15ms
25ms
40ms
60ms
100ms
When the secondary sequence group is already powered down and EN or the Software Enable bit is set
to ‘0’, the reverse power-down sequence is similar to
above, but starts from the last slot assigned to the primary sequence r7Dh[7:4]. After the last assigned slot is
powered down the previous slot will power down and so
on until Slot 0 is powered down.
To power down the secondary sequence group, drive
EN2 low or set r75h[1] to ‘0’. The secondary reverse
power-down sequence will start at Slot 12 and end at
the primary sequence monitoring mode state at which
point only the slots assigned to the primary sequence
are active.
Voltage/Current Monitoring
The MAX16065/MAX16066 feature an internal 10-bit
ADC that monitors the MON_ voltage inputs. An internal
multiplexer cycles through each of the enabled inputs,
taking less than 40Fs for a complete monitoring cycle.
Each acquisition takes approximately 3.2Fs. At each
multiplexer stop, the 10-bit ADC converts the analog
input to a digital result and stores the result in a register. ADC conversion results are stored in registers r00h
to r1Ah (see Table 10). Use the SMBus or JTAG serial
interface to read ADC conversion results.
The MAX16065 provides twelve inputs, MON1–MON12,
for voltage monitoring. The MAX16066 provides eight
inputs, MON1–MON8, for voltage monitoring. Each input
250Fs
380Fs
600Fs
1ms
1.5ms
2.5ms
4ms
voltage range is programmable in registers r43h to r45h
(see Table 9). When MON_ configuration registers are
set to ’11,’ MON_ voltages are not monitored, and the
multiplexer does not stop at these inputs, decreasing
the total cycle time. These inputs cannot be configured
to trigger fault conditions.
The three programmable thresholds for each monitored
voltage include an overvoltage, an undervoltage, and a
secondary warning threshold that can be set in r73h[3]
to be either an undervoltage or overvoltage threshold.
See the Faults section for more information on setting
overvoltage and undervoltage thresholds. All voltage
thresholds are 8 bits wide. The 8 MSBs of the 10-bit ADC
conversion result are compared to these overvoltage
and undervoltage thresholds.
For any undervoltage or overvoltage condition to be
monitored and any faults detected, the MON_ input must
be assigned to a sequence order or set to monitoring
mode as described in the Sequencing section.
Inputs that are not enabled are not converted by the
ADC; they contain the last value acquired before that
channel was disabled.
The ADC conversion result registers are reset to 00h at
boot-up. These registers are not reset when a reboot
command is executed.
Configure the MAX16065/MAX16066 for differential
mode in r46h (Table 9). The possible differential pairs
______________________________________________________________________________________ 17
MAX16065/MAX16066
Table 7. tFAULT Delay Settings
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
are MON1/MON2, MON3/MON4, MON5/MON6, MON7/
MON8, MON9/MON10, MON11/MON12 with the first
input always being at a higher voltage than the second.
Use differential voltage sensing to eliminate voltage offsets or measure supply current. See Figure 4. In differential mode, the odd-numbered MON_ input measures
the absolute voltage with respect to GND while the result
of the even input is the difference between the odd and
even inputs. See Figure 4 for the typical differential measurement circuit.
In addition, there are two programmable current-sense
trip thresholds: primary overcurrent and secondary overcurrent. For fast fault detection, the primary overcurrent
threshold is implemented with an analog comparator
connected to the internal OVERC signal. The OVERC
signal can be output on one of the GPIO_s. See the
General-Purpose Inputs/Outputs section for configuring the GPIO_ to output the OVERC signal. The primary
threshold is set by:
Internal Current-Sense Amplifier
where ITH is the current threshold to be set, VCSTH is the
threshold set by r47h[3:2], and RSENSE is the value of
the sense resistor. See Table 8 for a description of r47h.
OVERC depends only on the primary overcurrent threshold. The secondary overcurrent threshold is implemented through ADC conversions and digital comparison set
by r6Ch. The secondary overcurrent threshold includes
programmable time delay options located in r73h[6:5].
Primary and secondary current-sense faults are enabled/
disabled through r47h[0].
The current-sense inputs, CSP/CSM, and a currentsense amplifier facilitate power monitoring (see Figure
5). The voltage on CSP relative to GND is also monitored
by the ADC when the current-sense amplifier is enabled
with r47h[0]. The conversion results are located in registers r19h and r1Ah (see Table 10). There are two selectable voltage ranges for CSP set by r47h[1], see Table
8. Although the voltage can be monitored over SMBus
or JTAG, this voltage has no threshold comparators and
cannot trigger any faults. Regarding the current-sense
amplifier, there are four selectable ranges and the ADC
output for a current-sense conversion is:
XADC = (VSENSE x AV)/1.4V x (28 - 1)
where XADC is the 8-bit decimal ADC result in register
r18h, VSENSE is VCSP - VCSM, and AV is the currentsense voltage gain set by r47h[3:2].
RS
POWER
SUPPLY
ITH = VCSTH/RSENSE
General-Purpose Inputs/Outputs
GPIO1–GPIO8 are programmable general-purpose
inputs/outputs. GPIO1–GPIO8 are configurable as a
manual reset input, a watchdog timer input and output,
logic inputs/outputs, fault-dependent outputs. When programmed as outputs, GPIO_s are open drain or pushpull. See Tables 12 and 13 for more detailed information
on configuring GPIO1–GPIO8.
ILOAD
VMON
CS+
MONEVEN
MONODD
RSENSE
-
CS-
TO ADC MUX
*AV
+
MAX16065
MAX16066
MAX16065
LOAD
MONODD
MONEVEN
OVERC
+
+
-
POWER
SUPPLY
*VCSTH
LOAD
*ADJUSTABLE BY r47h[1:0]
Figure 4. Differential Measurement Connections
Figure 5. Current-Sense Amplifier
18 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER
ADDRESS
47h
FLASH
ADDRESS
BIT
RANGE
[0]
1 = Current sense is enabled
0 = Current sense is disabled
[1]
1 = CSP full-scale range is 14V
0 = CSP full-scale range is 7V
247h
73h
273h
DESCRIPTION
[3:2]
Overcurrent Primary Threshold and Current-Sense Gain Setting:
00 = 200mV threshold, AV = 6V/V
01 = 100mV threshold, AV = 12V/V
10 = 50mV threshold, AV = 24V/V
11 = 25mV threshold, AV = 48V/V
[6:5]
Overcurrent Secondary Threshold Deglitch:
00 = No delay
01 = 4ms
10 = 15ms
11 = 60ms
Table 9. ADC Configuration Registers
REGISTER ADDRESS
43h
FLASH
ADDRESS
BIT RANGE
DESCRIPTION
[1:0]
ADC1 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[3:2]
ADC2 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[5:4]
ADC3 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[7:6]
ADC4 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
243h
______________________________________________________________________________________ 19
MAX16065/MAX16066
Table 8. Overcurrent Primary Threshold and Current-Sense Control
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 9. ADC Configuration Registers (continued)
REGISTER ADDRESS
44h
45h
FLASH
ADDRESS
BIT RANGE
DESCRIPTION
[1:0]
ADC5 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[3:2]
ADC6 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[5:4]
ADC7 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[7:6]
ADC8 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[1:0]
ADC9 Full-Scale Range
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[3:2]
ADC10 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[5:4]
ADC11 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
[7:6]
ADC12 Full-Scale Range:
00 = 5.6V
01 = 2.8V
10 = 1.4V
11 = Channel not converted
244h
245h
20 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER ADDRESS
46h
FLASH
ADDRESS
BIT RANGE
DESCRIPTION
[0]
Differential Conversion ADC1–ADC2:
0 = Disabled
1 = Enabled
[1]
Differential Conversion ADC3–ADC4:
0 = Disabled
1 = Enabled
[2]
Differential Conversion ADC5–ADC6:
0 = Disabled
1 = Enabled
[3]
Differential Conversion ADC7–ADC8:
0 = Disabled
1 = Enabled
[4]
Differential Conversion ADC9–ADC10:
0 = Disabled
1 = Enabled
[5]
Differential Conversion ADC11–ADC12:
0 = Disabled
1 = Enabled
246h
Table 10. ADC Conversion Results (Read Only)
REGISTER ADDRESS
00h
01h
02h
03h
04h
05h
06h
07h
08h
09h
0Ah
0Bh
0Ch
0Dh
0Eh
0Fh
10h
11h
12h
13h
14h
15h
16h
17h
18h
19h
1Ah
BIT RANGE
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:6]
[7:0]
[7:0]
[7:6]
DESCRIPTION
ADC1 result (MSB) bits 9–2
ADC1 result (LSB) bits 1–0
ADC2 result (MSB) bits 9–2
ADC2 result (LSB) bits 1–0
ADC3 result (MSB) bits 9–2
ADC3 result (LSB) bits 1–0
ADC4 result (MSB) bits 9–2
ADC4 result (LSB) bits 1–0
ADC5 result (MSB) bits 9–2
ADC5 result (LSB) bits 1–0
ADC6 result (MSB) bits 9–2
ADC6 result (LSB) bits 1–0
ADC7 result (MSB) bits 9–2
ADC7 result (LSB) bits 1–0
ADC8 result (MSB) bits 9–2
ADC8 result (LSB) bits 1–0
ADC9 result (MSB) bits 9–2
ADC9 result (LSB) bits 1–0
ADC10 result (MSB) bits 9–2
ADC10 result (LSB) bits 1–0
ADC11 result (MSB) bits 9–2
ADC11 result (LSB) bits 1–0
ADC12 result (MSB) bits 9–2
ADC12 result (LSB) bits 1–0
Current-sense ADC result
CSP ADC output (MSB) bits 9–2
CSP ADC output (LSB) bits 1–0
______________________________________________________________________________________ 21
MAX16065/MAX16066
Table 9. ADC Configuration Registers (continued)
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
When GPIO1–GPIO8 are configured as general-purpose inputs/outputs, read values from the GPIO_ ports
through r1Eh and write values to GPIO_s through r3Eh.
Note that r3Eh has a corresponding flash register, which
programs the default state of a general-purpose output.
See Table 11 for more information on reading and writing
to the GPIO_.
Fault1 and Fault2
GPIO1–GPIO8 are configurable as dedicated fault outputs, Fault1 or Fault2. Fault outputs can assert on one or
more overvoltage, undervoltage, or early warning conditions for selected inputs, as well as the secondary overcurrent comparator. Fault1 and Fault2 dependencies are
set using registers r36h to r3Ah. See Table 14. When
a fault output depends on more than one MON_, the
fault output asserts when one or more MON_ exceeds a
programmed threshold voltage. These fault outputs act
independently of the critical fault system, described in
the Critical Faults section.
Table 11. GPIO_ State Registers
REGISTER
ADDRESS
1Eh
3Eh
FLASH
ADDRESS
—
23Eh
BIT RANGE
DESCRIPTION
[0]
GPIO1 input state
[1]
GPIO2 input state
[2]
GPIO3 input state
[3]
GPIO4 input state
[4]
GPIO5 input state
[5]
GPIO6 input state
[6]
GPIO7 input state
[7]
GPIO8 input state
[0]
GPIO1 output state
[1]
GPIO2 output state
[2]
GPIO3 output state
[3]
GPIO4 output state
[4]
GPIO5 output state
[5]
GPIO6 output state
[6]
GPIO7 output state
[7]
GPIO8 output state
Table 12. GPIO_ Configuration Registers
REGISTER
ADDRESS
3Fh
40h
FLASH
ADDRESS
23Fh
240h
BIT RANGE
DESCRIPTION
[2:0]
GPIO1 configuration
[5:3]
GPIO2 configuration
[7:6]
GPIO3 configuration (LSB)
[0]
GPIO3 configuration (MSB)
[3:1]
GPIO4 configuration
[6:4]
GPIO5 configuration
[7]
GPIO6 configuration (LSB)
22 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER
ADDRESS
FLASH
ADDRESS
41h
241h
BIT RANGE
GPIO6 configuration (MSB)
[4:2]
GPIO7 configuration
[7:5]
GPIO8 configuration
[1]
[2]
[3]
42h
DESCRIPTION
[1:0]
[0]
242h
[4]
[5]
[6]
[7]
MAX16065/MAX16066
Table 12. GPIO_ Configuration Registers (continued)
Output Configuration
0 = Push-pull
1 = Open drain
Output Configuration
0 = Push-pull
1 = Open drain
Output Configuration
0 = Push-pull
1 = Open drain
Output Configuration
0 = Push-pull
1 = Open drain
Output Configuration
0 = Push-pull
1 = Open drain
Output Configuration
0 = Push-pull
1 = Open drain
Output Configuration
0 = Push-pull
1 = Open drain
Output Configuration
0 = Push-pull
1 = Open drain
for GPIO1:
for GPIO2:
for GPIO3:
for GPIO4:
for GPIO5:
for GPIO6:
for GPIO7:
for GPIO8:
Table 13. GPIO_ Function Configuration Bits
GPIO1
GPIO2
000
Logic input
Logic
input
GPIO3
Logic input
001
Logic output
Logic
output
010
Fault2 output
011
GPIO4
GPIO5
GPIO6
GPIO7
GPIO8
Logic input
Logic input
Logic
input
Logic input
Logic input
Logic output
Logic output
Logic output
Logic
output
Logic output
Logic
output
Fault2
output
Fault2 output
Fault2 output
Fault2 output
Fault2
output
Fault2 output
Fault2
output
Fault1 output
Fault1
output
FAULTPU
output
Fault1 output
Fault1 output
Fault1
output
Fault1 output
FAULTP
output
100
ANY_FAULT
output
RESET2
output
ANY_FAULT
output
ANY_FAULT
output
ANY_FAULT
output
RESET2
output
ANY_FAULT
output
RESET2
output
101
OVERC
output
OVERC
output
OVERC
output
OVERC
output
OVERC
output
OVERC
output
OVERC
output
OVERC
output
110
MR input
WDO
output
MR input
WDO output
MR input
WDO
output
MR input
WDO output
111
WDI input
—
—
EXTFAULT
input/output
EN2 input
MARGIN
input
EN2 input
EXTFAULT
input/output
______________________________________________________________________________________ 23
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
ANY_FAULT
GPIO1, GPIO3, GPIO4, GPIO5, and GPIO7 are configurable to assert low during any fault condition. This
includes power-up, power-down fault conditions as well
as conditions where Fault1 or Fault2 assert.
Second Enable (EN2)
GPIO5 and GPIO7 are configurable as the enable
input for the secondary sequence. See the Multiple
Sequencing Groups section for more details.
Table 14. Fault1 and Fault2 Dependencies
REGISTER
ADDRESS
36h
37h
38h
FLASH
ADDRESS
236h
BIT
RANGE
0
1 = Fault1 depends on MON1
1
1 = Fault1 depends on MON2
2
1 = Fault1 depends on MON3
3
1 = Fault1 depends on MON4
4
1 = Fault1 depends on MON5
5
1 = Fault1 depends on MON6
6
1 = Fault1 depends on MON7
7
1 = Fault1 depends on MON8
0
1 = Fault1 depends on MON9
1
1 = Fault1 depends on MON10
2
1 = Fault1 depends on MON11
3
1 = Fault1 depends on MON12
4
1 = Fault1 depends on the overvoltage thresholds of the inputs selected by
r36h and r37h[3:0]
5
1 = Fault1 depends on the undervoltage thresholds of the inputs selected
by r36h and r37h[3:0]
6
1 = Fault1 depends on the early warning thresholds of the inputs selected
by r36h and r37h[3:0]
7
0 = Fault1 is an active-low digital output
1 = Fault1 is an active-high digital output
237h
238h
DESCRIPTION
[0]
1 = Fault2 depends on MON1
[1]
1 = Fault2 depends on MON2
[2]
1 = Fault2 depends on MON3
[3]
1 = Fault2 depends on MON4
[4]
1 = Fault2 depends on MON5
[5]
1 = Fault2 depends on MON6
[6]
1 = Fault2 depends on MON7
[7]
1 = Fault2 depends on MON8
24 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER
ADDRESS
39h
3Ah
FLASH
ADDRESS
BIT
RANGE
[0]
1 = Fault2 depends on MON9
[1]
1 = Fault2 depends on MON10
[2]
1 = Fault2 depends on MON11
[3]
1 = Fault2 depends on MON12
[4]
1 = Fault2 depends on the overvoltage thresholds of the inputs selected by
r38h and r39h[3:0]
[5]
1 = Fault2 depends on the undervoltage thresholds of the inputs selected
by r38h and r39h[3:0]
[6]
1 = Fault2 depends on the early warning thresholds of the inputs selected
by r38h and r39h[3:0]
[7]
0 = Fault2 is an active-low digital output
1 = Fault2 is an active-high digital output
[0]
1 = Fault1 depends on secondary overcurrent comparator
[1]
1 = Fault2 depends on secondary overcurrent comparator
239h
23Ah
DESCRIPTION
[7:2]
Reserved
Overcurrent Comparator (OVERC)
GPIO1 to GPIO8 are configurable to assert low when
the voltage across CSP and CSM exceed the primary
overcurrent threshold. See the Internal Current-Sense
Amplifier section for more details.
no MON_ inputs are assigned to Slot 12, the power-up
sequence is complete after the slot sequence delay
expires. RESET2 shares configuration bits with RESET
with the exception of polarity (active-high or active-low)
and output type (push-pull or open drain), see Table 23.
Fault-On Power-Up (FAULTPU)
GPIO3 and GPIO8 are configurable to indicate a fault
during power-up or power-down on the secondary
sequence. This output asserts low when a MON_ input
exceeds the overvoltage or undervoltage threshold. The
sequencer will still enter the fault state and turn off all the
EN_OUT_ outputs assigned to the secondary sequence.
During normal monitoring, RESET2 can be configured
to assert when any combination of MON_ inputs violates
configurable combinations of thresholds: undervoltage,
overvoltage, or early warning. Select the combination of
thresholds using r3Bh[1:0], and select the combination
of MON_ inputs using 3Ch[7:1] and 3Dh[4:0]. Note that
MON_ inputs in the secondary sequence configured as
critical faults will always cause RESET2 to assert regardless of these configuration bits.
Manual Reset (MR)
GPIO1, GPIO3, GPIO5, and GPIO7 are configurable to
act as an active-low manual reset input, MR. Drive MR
low to assert RESET. RESET remains asserted for the
selected reset timeout period after MR transitions from
low to high. See the RESET2 Output section for more
information on selecting a reset timeout period.
RESET2 Output
GPIO2, GPIO6, and GPIO8 are configurable to act as
a reset indicator related to the secondary sequence.
RESET2 asserts during power-up/power-down and deasserts following the reset timeout period once the powerup of the secondary sequence is complete. The secondary power-up sequence is completed when any MON_
inputs assigned to Slot 12 exceed the undervoltage
thresholds and Slot 12 sequence delay expires. When
RESET2 can be configured as push-pull or open drain
using the appropriate GPIO_ configuration bit in r42h
(see Table 12), and is always active-low. Select the
reset timeout for RESET and RESET2 by loading a value
from Table 5 into r3Bh[7:4]. RESET and RESET2 can be
forced to assert by writing a ‘1’ into r3Ch[0]. RESET2
remains asserted for the reset timeout period after a ‘0’
is written into r3Ch[0].
Watchdog Input (WDI) and Output (WDO)
GPIO2, GPIO4, GPIO6, and GPIO8 are configurable as
the watchdog timer output, WDO. GPIO1 is configurable
as WDI. See Table 24 for configuration details. WDO is an
active-low output. See the Watchdog Timer section for more
information about the operation of the watchdog timer.
______________________________________________________________________________________ 25
MAX16065/MAX16066
Table 14. Fault1 and Fault2 Dependencies (continued)
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
External Fault (EXTFAULT)
GPIO4 and GPIO8 are configurable as the external fault
input/output. When configured as push-pull, EXTFAULT
signals that a critical fault has occurred on one or more
monitored voltages or current. When configured as
open-drain, EXTFAULT can be asserted low by an external circuit to trigger a critical fault. This signal can be
used to cascade multiple MAX16065/MAX16066s.
Two configuration bits determine the behavior of the
MAX16065/MAX16066 when EXTFAULT is pulled low
by some other device. Register bit r72h[5], if set to a
‘1’, causes the sequencer state machine to enter the
fault state, deasserting all the outputs, when EXTFAULT
is pulled low. When this happens, the flag bit r1Ch[5]
gets set to indicate the cause of the fault. If register bit
r6Dh[2] is set in addition to r72h[5], EXTFAULT going low
triggers a nonvolatile fault log operation.
Faults
tiplexer. Only the upper 8 bits of a conversion result are
compared with the programmed fault thresholds.
The general-purpose inputs/outputs (GPIO1 to GPIO8)
can be configured as ANY_FAULT outputs or dedicated
Fault1 and Fault2 outputs to indicate fault conditions.
These fault outputs are not masked by the critical fault
enable bits shown in Table 18. See the General-Purpose
Inputs/Outputs section for more information on configuring GPIO_s as fault outputs.
Deglitch
Fault conditions are detected at the end of each conversion. When the voltage on an input falls outside a monitored threshold for one acquisition, the input multiplexer
remains on that channel and performs several successive conversions. To trigger a fault, the input must stay
outside the threshold for a certain number of acquisitions
as determined by the deglitch setting in r73h[6:5] and
r74h[6:5] (see Table 16).
The MAX16065/MAX16066 monitor the input (MON_)
channels and compare the results with an overvoltage
threshold, an undervoltage threshold, and a selectable
overvoltage or undervoltage early warning threshold.
Based on these conditions, the MAX16065/MAX16066
assert various fault outputs and save specific information about the channel conditions and voltages into the
nonvolatile flash. Once a critical fault event occurs, the
failing channel condition, ADC conversions at the time of
the fault, or both can be saved by configuring the event
logger. The event logger records a single failure in the
internal flash and sets a lock bit that protects the stored
fault data from accidental erasure on a subsequent
power-up.
Fault Flags
Fault flags indicate the fault status of a particular input.
The fault flag of any monitored input in the device can be
read at any time from registers r1Bh and r1Ch, as shown
in Table 17. Clear a fault flag by writing a ‘1’ to the appropriate bit in the flag register. Unlike the fault signals sent
to the fault outputs, these bits are masked by the critical
fault enable bits (see Table 18). The fault flag is only set
when the matching enable bit in the critical fault enable
register is also set.
An overvoltage event occurs when the voltage at a monitored input exceeds the overvoltage threshold for that
input. An undervoltage event occurs when the voltage
at a monitored input falls below the undervoltage threshold. Fault thresholds are set in registers r48h to r6Ch as
shown in Table 15. Disabled inputs are not monitored for
fault conditions and are skipped over by the input mul-
If a fault occurs during the secondary sequence group,
the slot number where the failure occurred is stored
in r1Dh.
If a GPIO_ is configured as an open-drain EXTFAULT
input/output, and EXTFAULT is pulled low by an external
circuit, bit r1Ch[5] is set.
The SMBus Alert bit is set if the MAX16065/MAX16066
have asserted the SMBus Alert output. Clear by writing a
‘1’. See the SMBALERT section for more details.
26 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER
ADDRESS
FLASH
ADDRESS
BIT RANGE
48h
248h
[7:0]
MON1 secondary threshold
49h
249h
[7:0]
MON1 overvoltage threshold
4Ah
24Ah
[7:0]
MON1 undervoltage threshold
4Bh
24Bh
[7:0]
MON2 secondary threshold
4Ch
24Ch
[7:0]
MON2 overvoltage threshold
4Dh
24Dh
[7:0]
MON2 undervoltage threshold
4Eh
24Eh
[7:0]
MON3 secondary threshold
4Fh
24Fh
[7:0]
MON3 overvoltage threshold
50h
250h
[7:0]
MON3 undervoltage threshold
51h
251h
[7:0]
MON4 secondary threshold
52h
252h
[7:0]
MON4 overvoltage threshold
53h
253h
[7:0]
MON4 undervoltage threshold
54h
254h
[7:0]
MON5 secondary threshold
55h
255h
[7:0]
MON5 overvoltage threshold
56h
256h
[7:0]
MON5 undervoltage threshold
57h
257h
[7:0]
MON6 secondary threshold
58h
258h
[7:0]
MON6 overvoltage threshold
DESCRIPTION
59h
259h
[7:0]
MON6 undervoltage threshold
5Ah
25Ah
[7:0]
MON7 secondary threshold
5Bh
25Bh
[7:0]
MON7 overvoltage threshold
5Ch
25Ch
[7:0]
MON7 undervoltage threshold
5Dh
25Dh
[7:0]
MON8 secondary threshold
5Eh
25Eh
[7:0]
MON8 overvoltage threshold
5Fh
25Fh
[7:0]
MON8 undervoltage threshold
60h
260h
[7:0]
MON9 secondary threshold
61h
261h
[7:0]
MON9 overvoltage threshold
62h
262h
[7:0]
MON9 undervoltage threshold
63h
263h
[7:0]
MON10 secondary threshold
64h
264h
[7:0]
MON10 overvoltage threshold
65h
265h
[7:0]
MON10 undervoltage threshold
66h
266h
[7:0]
MON11 secondary threshold
67h
267h
[7:0]
MON11 overvoltage threshold
68h
268h
[7:0]
MON11 undervoltage threshold
69h
269h
[7:0]
MON12 secondary threshold
6Ah
26Ah
[7:0]
MON12 overvoltage threshold
6Bh
26Bh
[7:0]
MON12 undervoltage threshold
6Ch
26Ch
[7:0]
Secondary overcurrent threshold
______________________________________________________________________________________ 27
MAX16065/MAX16066
Table 15. Fault Threshold Registers
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 16. Deglitch Configuration
REGISTER
ADDRESS
FLASH
ADDRESS
73h
273h
74h
274h
BIT RANGE
DESCRIPTION
[6:5]
Overcurrent Comparator Deglitch Time:
00 = No deglitch
01 = 4ms
10 = 15ms
11 = 60ms
[6:5]
Voltage Comparator Deglitch Configuration:
00 = 2 cycles
01 = 4 cycles
10 = 8 cycles
11 = 16 cycles
Critical Faults
During normal operation, a fault condition can be configured to shut down all the EN_OUT_s and store fault
information in the flash memory by setting the appropriate critical fault enable bits. During power-up and power-down, all sequenced MON_ inputs are considered
critical. Faults during power-up and power-down always
cause the EN_OUT_s to turn off and can store fault information in the flash memory, depending on the contents
of r6Dh[1:0]. Set the appropriate critical fault enable bits
in registers r6Eh to r72h (see Table 18) for a fault condition to trigger a critical fault.
Logged fault information is stored in flash registers r200h
to r20Fh (see Table 19). After fault information is logged,
the flash is locked and must be unlocked to enable a
new fault log to be stored. Write a ‘0’ to r8Ch[1] to unlock
the FAULT flash. Fault information can be configured to
store ADC conversion results and/or fault flags in registers. Select the critical fault configuration in r6Dh[1:0].
Set r6Dh[1:0] to ‘11’ to turn off the fault logger. All stored
ADC results are 8 bits wide.
Power-Up/Power-Down Faults
All EN_OUT_s deassert when an overvoltage or undervoltage fault is detected during power-up/power-down
and the MAX16065/MAX16066 return to the poweroff condition. Fault information can be stored to flash
depending on r6D[1:0], see Table 18. GPIO3 and
GPIO8 can be configured as power-up fault outputs
(ANY_FAULT).
Autoretry/Latch Mode
The MAX16065/MAX16066 can be configured for one
of two fault management methods: autoretry or latchon fault. Set r74h[4:3] to ‘00’ to select the latch-on-fault
mode. In this configuration, EN_OUT_s deassert after
a critical fault event. The device does not reinitiate the
power-up sequence until EN is toggled or the Software
Enable bit is toggled. See the Enable section for more
information on setting the software enable bit.
Table 17. Fault Flags
REGISTER
ADDRESS
1Bh
BIT RANGE
DESCRIPTION
[0]
MON1
[1]
MON2
[2]
MON3
[3]
MON4
[4]
MON5
[5]
MON6
[6]
MON7
[7]
MON8
28 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER
ADDRESS
BIT RANGE
1Ch
1Dh
DESCRIPTION
[0]
MON9
[1]
MON10
[2]
MON11
[3]
MON12
[4]
Overcurrent
[5]
External fault (EXTFAULT)
[6]
SMB alert
[4:0]
Slot where failure occurred during secondary sequence
[7:5]
Reserved
Table 18. Critical Fault Configuration
REGISTER
ADDRESS
FLASH
ADDRESS
BIT
RANGE
[1:0]
6Dh
26Dh
[2]
[7:3]
6Eh
6Fh
26Eh
26Fh
DESCRIPTION
Fault Information to Log:
00 = Save failed line flags and ADC values in flash
01 = Save only failed line flags in flash
10 = Save only ADC values in flash
11 = Do not save anything
1 = Fault log triggered when EXTFAULT is pulled low externally
Not used
[0]
1 = Fault log triggered when MON1 is below its undervoltage threshold
[1]
1 = Fault log triggered when MON2 is below its undervoltage threshold
[2]
1 = Fault log triggered when MON3 is below its undervoltage threshold
[3]
1 = Fault log triggered when MON4 is below its undervoltage threshold
[4]
1 = Fault log triggered when MON5 is below its undervoltage threshold
[5]
1 = Fault log triggered when MON6 is below its undervoltage threshold
[6]
1 = Fault log triggered when MON7 is below its undervoltage threshold
[7]
1 = Fault log triggered when MON8 is below its undervoltage threshold
[0]
1 = Fault log triggered when MON9 is below its undervoltage threshold
[1]
1 = Fault log triggered when MON10 is below its undervoltage threshold
[2]
1 = Fault log triggered when MON11 is below its undervoltage threshold
[3]
1 = Fault log triggered when MON12 is below its undervoltage threshold
[4]
1 = Fault log triggered when MON1 is above its overvoltage threshold
[5]
1 = Fault log triggered when MON2 is above its overvoltage threshold
[6]
1 = Fault log triggered when MON3 is above its overvoltage threshold
[7]
1 = Fault log triggered when MON4 is above its overvoltage threshold
______________________________________________________________________________________ 29
MAX16065/MAX16066
Table 17. Fault Flags (continued)
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 18. Critical Fault Configuration (continued)
REGISTER
ADDRESS
70h
FLASH
ADDRESS
270h
71h
271h
72h
272h
BIT
RANGE
DESCRIPTION
[0]
1 = Fault log triggered when MON5 is above its overvoltage threshold
[1]
1 = Fault log triggered when MON6 is above its overvoltage threshold
[2]
1 = Fault log triggered when MON7 is above its overvoltage threshold
[3]
1 = Fault log triggered when MON8 is above its overvoltage threshold
[4]
1 = Fault log triggered when MON9 is above its overvoltage threshold
[5]
1 = Fault log triggered when MON10 is above its overvoltage threshold
[6]
1 = Fault log triggered when MON11 is above its overvoltage threshold
[7]
1 = Fault log triggered when MON12 is above its overvoltage threshold
[0]
1 = Fault log triggered when MON1 is above/below the early threshold warning
[1]
1 = Fault log triggered when MON2 is above/below the early threshold warning
[2]
1 = Fault log triggered when MON3 is above/below the early threshold warning
[3]
1 = Fault log triggered when MON4 is above/below the early threshold warning
[4]
1 = Fault log triggered when MON5 is above/below the early threshold warning
[5]
1 = Fault log triggered when MON6 is above/below the early threshold warning
[6]
1 = Fault log triggered when MON7 is above/below the early threshold warning
[7]
1 = Fault log triggered when MON8 is above/below the early threshold warning
[0]
1 = Fault log triggered when MON9 is above/below the early threshold warning
[1]
1 = Fault log triggered when MON10 is above/below the early threshold warning
[2]
1 = Fault log triggered when MON11 is above/below the early threshold warning
[3]
1 = Fault log triggered when MON12 is above/below the early threshold warning
[4]
1 = Fault log triggered when overcurrent early threshold is exceeded
[5]
1 = EXTFAULT pulled low externally causes sequencer to enter fault state, turning off
all EN_OUT_s
0 = EXTFAULT pulled low externally does not cause sequencer to enter fault state
[7:6]
Reserved
Table 19. Nonvolatile Fault Log Registers
FLASH ADDRESS
200h
201h
BIT RANGE
DESCRIPTION
[4:0]
Sequencer state where the fault has happened (see Table 1 for state codes)
[7:5]
Not used
[0]
Fault log triggered on MON1
[1]
Fault log triggered on MON2
[2]
Fault log triggered on MON3
[3]
Fault log triggered on MON4
[4]
Fault log triggered on MON5
[5]
Fault log triggered on MON6
[6]
Fault log triggered on MON7
[7]
Fault log triggered on MON8
30 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
FLASH ADDRESS
BIT RANGE
202h
DESCRIPTION
[0]
Fault log triggered on MON9
[1]
Fault log triggered on MON10
[2]
Fault log triggered on MON11
[3]
Fault log triggered on MON12
[4]
Fault log triggered on overcurrent
[5]
Fault log triggered on EXTFAULT
[7:6]
Not used
203h
[7:0]
MON1 ADC output bits 9–2
204h
[7:0]
MON2 ADC output bits 9–2
205h
[7:0]
MON3 ADC output bits 9–2
206h
[7:0]
MON4 ADC output bits 9–2
207h
[7:0]
MON5 ADC output bits 9–2
208h
[7:0]
MON6 ADC output bits 9–2
209h
[7:0]
MON7 ADC output bits 9–2
20Ah
[7:0]
MON8 ADC output bits 9–2
20Bh
[7:0]
MON9 ADC output bits 9–2
20Ch
[7:0]
MON10 ADC output bits 9–2
20Dh
[7:0]
MON11 ADC output bits 9–2
20Eh
[7:0]
MON12 ADC output bits 9–2
20Fh
[7:0]
Current-sense ADC output bits 9–2
Table 20. Autoretry Configuration
REGISTER
ADDRESS
74h
FLASH
ADDRESS
BIT RANGE
DESCRIPTION
[2:0]
Retry Delay:
000 = 20ms
001 = 40ms
010 = 80ms
011 = 150ms
100 = 280ms
101 = 540ms
110 = 1s
111 = 2s
[4:3]
Autoretry/Latch Mode:
00 = Latch
01 = Retry 1 time
10 = Retry 3 times
11 = Always retry
274h
______________________________________________________________________________________ 31
MAX16065/MAX16066
Table 19. Nonvolatile Fault Log Registers (continued)
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Set r74h[4:3] to a value other than ‘00’ to select autoretry
mode (see Table 20). In this configuration, the device
shuts down after a critical fault event then restarts
following a configurable delay. Use r74h[2:0] to select an
autoretry delay from 20ms to 1.6s. See Table 20 for more
information on setting the autoretry delay.
When fault information is stored in flash (see the Critical
Faults section) and autoretry mode is selected, set an
autoretry delay greater than the time required for the
storing operation. When fault information is stored in
flash and latch-on-fault mode is chosen, toggle EN or
reset the software enable bit only after the completion of
the storing operation. When saving information about the
failed lines only, ensure a delay of at least 150ms before
the restart procedure. Otherwise, ensure a minimum
280ms timeout, to ensure that ADC conversions are completed and values are stored correctly in flash.
Programmable Ouputs
(EN_OUT1–EN_OUT12)
The MAX16065 includes twelve programmable outputs, and the MAX16066 includes eight programmable
outputs. These outputs are capable of connecting to
either the enable (EN) inputs of a DC-DC or LDO power
supply, or to drive the gate of an n-channel MOSFET in
charge-pump mode. Selectable output configurations
include: active-low or active-high, open drain or pushpull. EN_OUT1–EN_OUT8 can act as charge-pump
outputs, EN_OUT9–EN_OUT12 can be configured as
general-purpose inputs or general-purpose outputs. Use
registers r30h to r33h to configure outputs. See Table
21 for detailed information on configuring EN_OUT1–
EN_OUT12.
In charge-pump configuration, EN_OUT1–EN_OUT8 act
as high-voltage charge-pump outputs to drive up to eight
external n-channel MOSFETs. During sequencing, an EN_
OUT_ output set to the charge-pump configuration outputs
11V relative to GND. See the Sequencing section for more
detailed information on power-supply sequencing.
In open-drain output configuration, connect an external pullup resistor from the output to an external voltage
up to 5.5V (EN_OUT9–EN_OUT12) or 14V (EN_OUT1–
EN_OUT8). Choose the pullup resistor depending on the
number of devices connected to the open-drain output
and the allowable current consumption. The open-drain
output configuration allows wire-ORed connection.
In push-pull configuration, the MAX16065/MAX16066’s
programmable outputs are referenced to VDBP.
Table 21. EN_OUT1–EN_OUT12 Configuration
REGISTER ADDRESS
30h
FLASH ADDRESS
BIT RANGE
DESCRIPTION
[1:0]
EN_OUT1 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[3:2]
EN_OUT2 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[5:4]
EN_OUT3 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[7:6]
EN_OUT4 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
230h
32 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER ADDRESS
31h
FLASH ADDRESS
BIT RANGE
[1:0]
EN_OUT5 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[3:2]
EN_OUT6 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[5:4]
EN_OUT7 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[7:6]
EN_OUT8 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[1:0]
EN_OUT9 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[3:2]
EN_OUT10 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[5:4]
EN_OUT11 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
[7:6]
EN_OUT12 Configuration:
00 = Active-low, open drain
01 = Active-high, open drain
10 = Active-low, push-pull
11 = Active-high, push-pull
231h
32h (MAX16065 Only)
DESCRIPTION
232h
______________________________________________________________________________________ 33
MAX16065/MAX16066
Table 21. EN_OUT1–EN_OUT12 Configuration (continued)
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 21. EN_OUT1–EN_OUT12 Configuration (continued)
REGISTER ADDRESS
33h
FLASH ADDRESS
BIT RANGE
DESCRIPTION
[0]
EN_OUT1 Charge-Pump Output Configuration:
0 = Charge-pump output disabled
1 = Charge-pump output enabled (active-high)
[1]
EN_OUT2 Charge-Pump Output Configuration:
0 = Charge-pump output disabled
1 = Charge-pump output enabled (active-high)
[2]
EN_OUT3 Charge-Pump Output Configuration:
0 = Charge-pump output disabled
1 = Charge-pump output enabled (active-high)
[3]
EN_OUT4 Charge-Pump Output Configuration:
0 = Charge-pump output disabled
1 = Charge-pump output enabled (active-high)
[4]
EN_OUT5 Charge-Pump Output Configuration:
0 = Charge-pump output disabled
1 = Charge-pump output enabled (active-high)
[5]
EN_OUT6 Charge-Pump Output Configuration:
0 = Charge-pump output disabled
1 = Charge-pump output enabled (active-high)
[6]
EN_OUT7 Charge-Pump Output Configuration:
0 = Charge-pump output disabled
1 = Charge-pump output enabled (active-high)
[7]
EN_OUT8 Charge-Pump Output Configuration:
0 = Charge-pump output disabled
1 = Charge-pump output enabled (active-high)
233h
EN_OUT_s as GPIO_ (MAX16065 Only)
EN_OUT9 to EN_OUT12 can be configured as GPIO_
by setting the sequencing slot assignments in r88h
and r89h to ‘1101’ and ‘1110’, see Tables 5 and 6. If an
EN_OUT_ is configured as a general-purpose input, the
state of the pin can be read from r1Fh (see Table 22). If
an EN_OUT_ is configured as a general-purpose output,
it is controlled by r34h.
EN_OUT_ State During Power-Up
When VCC is ramped from 0 to the operating supply voltage, the EN_OUT_ output is high impedance until VCC
reaches UVLO and then EN_OUT_ goes into the configured deasserted state after the boot-up relay. See Figures
6 and 7. Configure RESET as an active-low push-pull or
open-drain output pulled up to VCC through a 10kI resistor
for Figures 6 and 7.
Reset Output
The reset output, RESET, indicates the status of the primary sequence. It asserts during power-up/power-down
and deasserts following the reset timeout period once
the power-up sequence is complete. The power-up
sequence is complete when any MON_ inputs assigned
to the final slot exceed the undervoltage thresholds and
final sequence delay expires. When no MON_ inputs
are assigned to the final slot, the power-up sequence is
complete after the slot sequence delay expires.
During normal monitoring, RESET can be configured to
assert when any combination of MON_ inputs violates
configurable combinations of thresholds: undervoltage,
overvoltage, or early warning. Select the combination of
thresholds using r3Bh[1:0], and select the combination
of MON_ inputs using r3Ch[7:1] and r3Dh[4:0]. Note
that MON_ inputs configured as critical faults will always
cause RESET to assert regardless of these configuration bits.
RESET can be configured as push-pull or open drain
using r3Bh[3], and active-high or active-low using
r3Bh[2]. Select the reset timeout by loading a value from
Table 23 into r3Bh[7:4]. RESET can be forced to assert
by writing a ‘1’ into r3Ch[0]. RESET remains asserted
for the reset timeout period after a ‘0’ is written into
r3Ch[0]. See Table 23. The current state of RESET can
be checked by reading r20h[0].
34 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER
ADDRESS
FLASH
ADDRESS
1Fh
BIT RANGE
—
34h
234h
DESCRIPTION
[0]
EN_OUT9 input state
[1]
EN_OUT10 input state
[2]
EN_OUT11 input state
[3]
EN_OUT12 input state
[0]
1 = Assert EN_OUT9
[1]
1 = Assert EN_OUT10
[2]
1 = Assert EN_OUT11
[3]
1 = Assert EN_OUT12
MAX16065 fig06
MAX16065 fig07
VCC
2V/div
UVLO
VCC
2V/div
0V
0V
RESET
2V/div
0V
RESET
2V/div
0V
EN_OUT_
2V/div
0V
20ms/div
ASSERTED
LOW
HIGH-Z
EN_OUT_
2V/div
0V
10ms/div
Figure 6. RESET and EN_OUT_ During Power-Up, EN_OUT_ in
Open-Drain Active-Low Configuration
Figure 7. RESET and EN_OUT_ During Power-Up, EN_OUT_ in
Push-Pull Active-High Configuration
Watchdog Timer
Dependent Watchdog Timer Operation
Use the watchdog timer to monitor FP activity in two
modes. Flexible timeout architecture provides an adjustable watchdog startup delay of up to 300s, allowing complicated systems to complete lengthy boot-up routines.
An adjustable watchdog timeout allows the supervisor to
provide quick alerts when processor activity fails. After
each reset event (VCC drops below UVLO then returns
above UVLO, software reboot, manual reset (MR), EN
input going low then high, or watchdog reset) and once
sequencing is complete, the watchdog startup delay
provides an extended time for the system to power up
and fully initialize all FP and system components before
assuming responsibility for routine watchdog updates.
Set r76h[6:4] to a value other than ‘000’ to enable the
watchdog startup delay. Set r76h[6:4] to ‘000’ to disable
the watchdog startup delay.
The watchdog timer operates together with or independently of the MAX16065/MAX16066. When operating in
dependent mode, the watchdog is not activated until the
sequencing is complete and RESET is deasserted. When
operating in independent mode, the watchdog timer is
independent of the sequencing operation and activates
immediately after VCC exceeds the UVLO threshold and
the boot phase is complete. Set r73h[4] to ‘0’ to configure the watchdog in dependent mode. Set r73h[4] to ‘1’
to configure the watchdog in independent mode. See
Table 24 for more information on configuring the watchdog timer in dependent or independent mode.
______________________________________________________________________________________ 35
MAX16065/MAX16066
Table 22. EN_OUT_ GPIO_ State Registers
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 23. Reset Output Configuration
REGISTER
ADDRESS
FLASH
ADDRESS
BIT RANGE
[1:0]
3Bh
0 = Active-low
1 = Active-high
[3]
0 = Push-pull
1 = Open drain
23Bh
3Dh
23Ch
23Dh
Reset Output Depends On:
00 = Undervoltage threshold violations
01 = Early warning threshold violations
10 = Overvoltage threshold violations
11 = Undervoltage or overvoltage threshold violations
[2]
[7:4]
3Ch
DESCRIPTION
Reset Timeout Period:
0000 = 25Fs
0001 = 1.5ms
0010 = 2.5ms
0011 = 4ms
0100 = 6ms
0101 = 10ms
0110 = 15ms
0111 = 25ms
1000 = 40ms
1001 = 60ms
1010 = 100ms
1011 = 150ms
1100 = 250ms
1101 = 400ms
1110 = 600ms
1111 = 1s
[0]
Reset Soft Trigger:
0 = Normal RESET behavior
1 = Force RESET to assert
[1]
1 = RESET depends on MON1
[2]
1 = RESET depends on MON2
[3]
1 = RESET depends on MON3
[4]
1 = RESET depends on MON4
[5]
1 = RESET depends on MON5
[6]
1 = RESET depends on MON6
[7]
1 = RESET depends on MON7
[0]
1 = RESET depends on MON8
[1]
1 = RESET depends on MON9
[2]
1 = RESET depends on MON10
[3]
1 = RESET depends on MON11
[4]
1 = RESET depends on MON12
[7:5]
Reserved
36 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
The watchdog can be configured to control the RESET
output as well as the WDO output. RESET asserts for
the reset timeout, tRP, when the watchdog timer expires
and the Watchdog Reset Output Enable bit (r76h[7]) is
set to ‘1.’ When RESET is asserted, the watchdog timer
is cleared and WDO is deasserted, therefore, WDO
pulses low for a short time (approximately 1Fs) when
the watchdog timer expires. RESET is not affected by
the watchdog timer when the Watchdog Reset Output
Enable bit (r76h[7]) is set to ‘0.’ If a RESET is asserted
by the watchdog timeout, the WDRESET bit is set to ‘1.’ A
connected processor can check this bit to see the reset
was due to a watchdog timeout. See Table 24 for more
information on configuring watchdog functionality.
While EN is low, the watchdog timer is in reset. The
watchdog timer does not begin counting until the poweron mode is reached and RESET is deasserted. The
watchdog timer is reset and WDO deasserts any time
RESET is asserted (Figure 10). The watchdog timer will
be held in reset while RESET is asserted.
VTH
LAST MON_
< tWDI
tWDI_STARTUP
WDI
< tWDI
tRP
RESET
Figure 8. Normal Watchdog Startup Sequence
VCC
WDI
< tWDI
< tWDI
> tWDI
< tWDI
< tWDI
< tWDI
< tWDI
0V
tWDI
VCC
WDO
0V
Figure 9. Watchdog Timer Operation
______________________________________________________________________________________ 37
MAX16065/MAX16066
The normal watchdog timeout period, tWDI, begins after
the first transition on WDI before the conclusion of the
long startup watchdog period, tWDI_STARTUP (Figures 7
and 8). During the normal operating mode, WDO asserts
if the FP does not toggle WDI with a valid transition
(high-to-low or low-to-high) within the standard timeout
period, tWDI. WDO remains asserted until WDI is toggled
or RESET is asserted (Figure 9).
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
VCC
< tWDI
WDI
tWDI
tRP
< tWDI_STARTUP
0V
VCC
RESET
0V
VCC
WDO
0V
1µs
Figure 10. Watchdog Startup Sequence with Watchdog Reset Enable Bit Set to ‘1’
Table 24. Watchdog Configuration
REGISTER
ADDRESS
FLASH
ADDRESS
BIT RANGE
73h
273h
[4]
1 = Independent mode
0 = Dependent mode
[7]
1 = Watchdog affects RESET output
0 = Watchdog does not affect RESET output
76h
DESCRIPTION
[6:4]
Watchdog Startup Delay:
000 = No initial timeout
001 = 30s
010 = 40s
011 = 80s
100 = 120s
101 = 160s
110 = 220s
111 = 300s
[3:0]
Watchdog Timeout:
0000 = Watchdog disabled
0001 = 1ms
0010 = 2ms
0011 = 4ms
0100 = 8ms
0101 = 14ms
0110 = 27ms
0111 = 50ms
1000 = 100ms
1001 = 200ms
1010 = 400ms
1011 = 750ms
1100 = 1.4s
1101 = 2.7s
1110 = 5s
1111 = 10s
276h
38 �������������������������������������������������������������������������������������
< tWDI
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER
ADDRESS
8Ch
FLASH ADDRESS
BIT RANGE
DESCRIPTION
0
Configuration Register Lock:
1 = Locked
0 = Unlocked
1
Flash Fault Register Lock:
1 = Locked
0 = Unlocked
2
Flash Configuration Lock:
1 = Locked
0 = Unlocked
3
User Flash Lock:
1 = Locked
0 = Unlocked
28Ch
Independent Watchdog Timer Operation
When r73h[3] is ‘1’ the watchdog timer operates in independent mode. In independent mode, the watchdog
timer operates as if it were a separate device. The watchdog timer is activated immediately upon VCC exceeding
UVLO and once the boot-up sequence is finished. When
RESET is asserted by the sequencer state machine, the
watchdog timer and WDO are not affected.
There will be a startup delay if r76h[6:4] is set to a value
different than ‘000.’ If r76h[6:4] is set to ‘000,’ there will
not be a startup delay. See Table 24 for delay times.
In independent mode, if the Watchdog Reset Output
Enable bit r76h[7] is set to ‘1,’ when the watchdog timer
expires, WDO asserts then RESET asserts. WDO will then
deassert. WDO will be low for approximately 1Fs. If the
Watchdog Reset Output Enable bit (r76h[7]) is set to ‘0,’
when the WDT expires, WDO asserts but RESET is not
affected.
User-Defined Register
Register r8Ah provides storage space for a user-defined
configuration or firmware version number. Note that this
register controls the contents of the JTAG USERCODE
register bits 7:0. The user-defined register is stored at
r28Ah in the flash memory.
Memory Lock Bits
Register r8Ch contains the lock bits for the configuration
registers, configuration flash, user flash and fault register
lock. See Table 25 for details.
SMBus-Compatible Interface
The MAX16065/MAX16066 feature an SMBuscompatible, 2-wire serial interface consisting of a serial
data line (SDA) and a serial clock line (SCL). SDA and
SCL facilitate bidirectional communication between the
MAX16065/MAX16066 and the master device at clock
rates up to 400kHz. Figure 1 shows the 2-wire interface
timing diagram. The MAX16065/MAX16066 are transmit/
receive slave-only devices, relying upon a master device
to generate a clock signal. The master device (typically
a microcontroller) initiates a data transfer on the bus and
generates SCL to permit that transfer.
A master device communicates to the MAX16065/
MAX16066 by transmitting the proper address followed
by a command and/or data words. The slave address
input, A0, is capable of detecting four different states,
allowing multiple identical devices to share the same
serial bus. The slave address is described further in
the Slave Address section. Each transmit sequence is
framed by a START (S) or REPEATED START (SR) condition and a STOP (P) condition. Each word transmitted
______________________________________________________________________________________ 39
MAX16065/MAX16066
Table 25. Memory Lock Bits
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
SDA
SDA
SCL
SCL
DATA LINE STABLE, CHANGE OF
DATA ALLOWED
DATA VALID
S
P
START
CONDITION
STOP
CONDITION
Figure 11. Bit Transfer
Figure 12. START and STOP Conditions
over the bus is 8 bits long and is always followed by an
acknowledge pulse. SCL is a logic input, while SDA is
an open-drain input/output. SCL and SDA both require
external pullup resistors to generate the logic-high voltage. Use 4.7kI for most applications.
Acknowledge
The acknowledge bit (ACK) is the 9th bit attached to any
8-bit data word. The receiving device always generates
an ACK. The MAX16065/MAX16066 generate an ACK
when receiving an address or data by pulling SDA low
during the 9th clock period (Figure 14). When transmitting data, such as when the master device reads data
back from the MAX16065/MAX16066, the device waits for
the master device to generate an ACK. Monitoring ACK
allows for detection of unsuccessful data transfers. An
unsuccessful data transfer occurs if the receiving device
is busy or if a system fault has occurred. In the event of an
unsuccessful data transfer, the bus master can reattempt
communication at a later time. The MAX16065/MAX16066
generate a NACK after the command byte received during a software reboot, while writing to the flash, or when
receiving an illegal memory address.
Bit Transfer
Each clock pulse transfers one data bit. The data on
SDA must remain stable while SCL is high (Figure 11);
otherwise the MAX16065/MAX16066 register a START
or STOP condition (Figure 12) from the master. SDA and
SCL idle high when the bus is not busy.
START and STOP Conditions
Both SCL and SDA idle high when the bus is not busy.
A master device signals the beginning of a transmission
with a START condition by transitioning SDA from high to
low while SCL is high. The master device issues a STOP
condition by transitioning SDA from low to high while
SCL is high. A STOP condition frees the bus for another
transmission. The bus remains active if a REPEATED
START condition is generated, such as in the block read
protocol (see Figure 1).
Early STOP Conditions
The MAX16065/MAX16066 recognize a STOP condition
at any point during transmission except if a STOP condition occurs in the same high pulse as a START condition.
This condition is not a legal SMBus format; at least one
clock pulse must separate any START and STOP condition.
REPEATED START Conditions
A REPEATED START can be sent instead of a STOP
condition to maintain control of the bus during a read
operation. The START and REPEATED START conditions
are functionally identical.
Slave Address
Use the slave address input, A0, to allow multiple identical devices to share the same serial bus. Connect A0 to
GND, DBP (or an external supply voltage greater than
2V), SCL, or SDA to set the device address on the bus.
See Table 27 for a listing of all possible 7-bit addresses.
The slave address can also be set to a custom value by
loading the address into register r8Bh[6:0]. See Table
26. If r8Bh[6:0] is loaded with 00h, the address is set by
input A0. Do not set the address to 09h or 7Fh to avoid
address conflicts. The slave address setting takes effect
immediately after writing to the register.
Packet Error Checking (PEC)
The MAX16065/MAX16066 feature a PEC mode that is
useful for improving the reliability of the communication
bus by detecting bit errors. By enabling PEC, an extra
40 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
REGISTER
ADDRESS
FLASH ADDRESS
8Bh
28Bh
BIT RANGE
DESCRIPTION
[6:0]
SMBus Slave Address Register. Set to 00h to use A0
pin address setting.
[7]
1 = Enable PEC (packet error check).
Table 27. Setting the SMBus Slave Address
SLAVE ADDRESSES
A0
SLAVE ADDRESS
0
1010 000R
1
1010 001R
SCL
1010 010R
SDA
1010 011R
R = Read/Write select bit.
Table 28. Command codes
COMMAND
CODE
ACTION
A5h
Block write
A6h
Block read
A7h
Reboot flash in register file
A8h
Trigger emergency save to flash
A9h
Flash page access ON
AAh
Flash page access OFF
ABh
User flash access ON (must be in flash page already)
ACh
User flash access OFF (return to flash page)
CRC-8 error check byte is added in the data string during each read and/or write sequence. Enable PEC by
writing a ‘1’ to r8Bh[7].
as a hardware-initiated power-on reset. During boot-up,
flash configuration data in the range of 230h to 28Ch is
copied to r30h to r8Ch registers in the default page.
The CRC-8 byte is calculated using the polynomial
C = X8 + X2 + X + 1
Send command code A8h to trigger a fault store to flash.
Configure the Critical Fault Log Control register (6Dh) to
store ADC conversion results and/or fault flags.
The PEC calculation includes all bytes in the transmission, including address, command, and data. The PEC
calculation does not include ACK, NACK, START, STOP,
or REPEATED START.
Command Codes
The MAX16065/MAX16066 use eight command codes
for block read, block write, and other commands. See
Table 28 for a list of command codes.
To initiate a software reboot, send A7h using the send byte
format. A software-initiated reboot is functionally the same
While in the flash page, send command code A9h to
access the flash page (addresses from 200h to 28Fh).
Once command code A9h has been sent, all addresses
are recognized as flash addresses only. Send command
code AAh to return to the default page (addresses from
000h to 0FFh). Send command code ABh to access
the user flash-page (addresses from 300h to 3A4h and
3ADh to 3FFh), and send command code ACh to return
to the flash page.
______________________________________________________________________________________ 41
MAX16065/MAX16066
Table 26. SMBus Settings Register
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
5) The addressed slave asserts an ACK (or NACK)
on SDA.
Restrictions When Writing to Flash
Flash must be written to 8 bytes at a time. The initial
address must be aligned to 8-byte boundaries—the 3
LSBs of the initial address must be ‘000’. Write the 8
bytes using a single block-write command or using 8
successive Write Byte commands.
6) The master sends a STOP condition.
Receive Byte
The receive byte protocol allows the master device to
read the register content of the MAX16065/MAX16066
(see Figure 14). The flash or register address must be
preset with a send byte or write word protocol first. Once
the read is complete, the internal pointer increases by
one. Repeating the receive byte protocol reads the contents of the next address. The receive byte procedure
follows:
Send Byte
The send byte protocol allows the master device to
send one byte of data to the slave device (see Figure
14). The send byte presets a register pointer address
for a subsequent read or write. The slave sends a NACK
instead of an ACK if the master tries to send a memory
address or command code that is not allowed. If the
master sends A5h or A6h, the data is ACK, because this
could be the start of the write block or read block. If the
master sends a STOP condition before the slave asserts
an ACK, the internal address pointer does not change.
If the master sends A7h, this signifies a software reboot.
The send byte procedure is the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a read
bit (high).
3) The addressed slave asserts an ACK on SDA.
4) The slave sends 8 data bits.
5 The master asserts a NACK on SDA.
1) The master sends a START condition.
6) The master generates a STOP condition.
2) The master sends the 7-bit slave address and a write
bit (low).
Write Byte
The write byte protocol (see Figure 14) allows the master device to write a single byte in the default page,
extended page, or flash page, depending on which
3) The addressed slave asserts an ACK on SDA.
4) The master sends an 8-bit memory address or command code.
CLOCK PULSE FOR ACKNOWLEDGE
1
SCL
2
8
9
SDA BY
TRANSMITTER
S
NACK
SDA BY
RECEIVER
ACK
Figure 13. Acknowledge
42 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
6)
The master sends a REPEATED START condition.
7)
The master sends the 7-bit slave address and a
read bit (high).
2) The master sends the 7-bit slave address and a write
bit (low).
8)
The addressed slave asserts an ACK on SDA.
9)
The slave sends an 8-bit data byte.
3) The addressed slave asserts an ACK on SDA.
10) The master asserts a NACK on SDA.
4) The master sends an 8-bit memory address.
11) The master sends a STOP condition.
5) The addressed slave asserts an ACK on SDA.
6) The master sends an 8-bit data byte.
If the memory address is not valid, it is NACKed by the
slave at step 5 and the address pointer is not modified.
7) The addressed slave asserts an ACK on SDA.
When PEC is enabled, the Read Byte protocol becomes:
8) The master sends a STOP condition.
1)
The master sends a START condition.
To write a single byte, only the 8-bit memory address
and a single 8-bit data byte are sent. The data byte is
written to the addressed location if the memory address
is valid. The slave asserts a NACK at step 5 if the memory address is not valid.
2)
The master sends the 7-bit slave ID plus a write
bit (low).
3)
The addressed slave asserts an ACK on the data line.
4)
The master sends 8 data bits.
5)
The active slave asserts an ACK on the data line.
6)
The master sends a REPEATED START condition.
7)
The master sends the 7-bit slave ID plus a read
bit (high).
8)
The addressed slave asserts an ACK on the data line.
9)
The slave sends 8 data bits.
1) The master sends a START condition.
When PEC is enabled, the Write Byte protocol becomes:
1)
The master sends a START condition.
2)
The master sends the 7-bit slave ID plus a write
bit (low).
3)
The addressed slave asserts an ACK on the data line.
4)
The master sends an 8-bit command code.
5)
The active slave asserts an ACK on the data line.
6)
The master sends an 8-bit data byte.
7)
The slave asserts an ACK on the data line.
8)
The master sends an 8-bit PEC byte.
13) The master generates a STOP condition.
9)
The slave asserts an ACK on the data line (if PEC is
good, otherwise NACK).
Block Write
The block write protocol (see Figure 14) allows the master device to write a block of data (1 byte to 16 bytes) to
memory. Preload the destination address by a previous
send byte command; otherwise the block write command begins to write at the current address pointer.
After the last byte is written, the address pointer remains
preset to the next valid address. If the number of bytes
to be written causes the address pointer to exceed 8Fh
for configuration registers or configuration flash or FFh
for user flash, the address pointer stays at 8Fh or FFh,
respectively, overwriting this memory address with the
remaining bytes of data. The slave generates a NACK at
step 5 if the command code is invalid or if the device is
busy, and the address pointer is not altered.
10) The master generates a STOP condition.
Read Byte
The read byte protocol (see Figure 14) allows the master
device to read a single byte located in the default page,
extended page, or flash page depending on which page
is currently selected. The read byte procedure is the
following:
1)
The master sends a START condition.
2)
The master sends the 7-bit slave address and a
write bit (low).
3)
The addressed slave asserts an ACK on SDA.
4)
The master sends an 8-bit memory address.
5)
The addressed slave asserts an ACK on SDA.
10) The master asserts an ACK on the data line.
11) The slave sends an 8-bit PEC byte.
12) The master asserts a NACK on the data line.
______________________________________________________________________________________ 43
MAX16065/MAX16066
page is currently selected. The write byte procedure is
the following:
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
The block write procedure is the following:
the configuration register or configuration flash or FFh
in user flash, the address pointer stays at 8Fh or FFh,
respectively. The block read procedure is the following:
1)
The master sends a START condition.
2)
The master sends the 7-bit slave address and a
write bit (low).
3)
The addressed slave asserts an ACK on SDA.
4)
The master sends the 8-bit command code for a
block write (94h).
5)
The addressed slave asserts an ACK on SDA.
4) The master sends 8 bits of the block read command (95h).
6)
The master sends the 8-bit byte count (1 byte to 16
bytes), n.
5) The slave asserts an ACK on SDA, unless busy.
7)
The addressed slave asserts an ACK on SDA.
8)
The master sends 8 bits of data.
7) The master sends the 7-bit slave address and a read
bit (high).
9)
The addressed slave asserts an ACK on SDA.
8) The slave asserts an ACK on SDA.
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a write
bit (low).
3) The addressed slave asserts an ACK on SDA.
6) The master generates a REPEATED START condition.
10) Repeat steps 8 and 9 n - 1 times.
9) The slave sends the 8-bit byte count (16).
11) The master sends a STOP condition.
10) The master asserts an ACK on SDA.
When PEC is enabled, the Block Write protocol becomes:
11) The slave sends 8 bits of data.
1)
The master sends a START condition.
12) The master asserts an ACK on SDA.
2)
The master sends the 7-bit slave ID plus a write
bit (low).
13) Repeat steps 11 and 12 up to fifteen times.
3)
The addressed slave asserts an ACK on the data line.
15) The master sends a STOP condition.
4)
The master sends 8 bits of the block write command code.
When PEC is enabled, the Block Read protocol becomes:
5)
The slave asserts an ACK on the data line.
1)
The master sends a START condition.
6)
The master sends an 8-bit byte count (min 1, max
16) N.
2)
The master sends the 7-bit slave ID plus a write
bit (low).
7)
The slave asserts an ACK on the data line.
3)
The addressed slave asserts an ACK on the data line.
8)
The master sends 8 bits of data.
4)
9)
The slave asserts an ACK on the data line.
The master sends 8 bits of the block read command
code.
5)
The slave asserts an ACK on the data line unless
busy.
6)
The master sends a REPEATED START condition.
7)
The master sends the 7-bit slave ID plus a read
bit (high).
8)
The slave asserts an ACK on the data line.
9)
The slave sends an 8-bit byte count (16).
10) Repeat 8 and 9 n - 1 times.
11) The master sends an 8-bit PEC byte.
12) The slave asserts an ACK on the data line (if PEC is
good, otherwise NACK).
13) The master generates a STOP condition.
Block Read
The block read protocol (see Figure 14) allows the
master device to read a block of up to 16 bytes from
memory. Read fewer than 16 bytes of data by issuing
an early STOP condition from the master, or by generating a NACK with the master. The destination address
should be preloaded by a previous send byte command;
otherwise the block read command begins to read at
the current address pointer. If the number of bytes to
be read causes the address pointer to exceed 8Fh for
14) The master asserts a NACK on SDA.
10) The master asserts an ACK on the data line.
11) The slave sends 8 bits of data.
12) The master asserts an ACK on the data line.
13) Repeat 11 and 12 up to 15 times.
14) The slave sends an 8-bit PEC byte.
15) The master asserts a NACK on the data line.
16) The master generates a STOP condition.
44 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
JTAG Serial Interface
The MAX16065/MAX16066 feature a JTAG port that
complies with a subset of the IEEE 1149.1 specification.
Either the SMBus or the JTAG interface can be used to
access internal memory; however, only one interface is
allowed to run at a time. The MAX16065/MAX16066 do
not support IEEE 1149.1 boundary-scan functionality.
The MAX16065/MAX16066 contain extra JTAG instructions and registers not included in the JTAG specification that provide access to internal memory. The extra
instructions include LOAD ADDRESS, WRITE, READ,
REBOOT, SAVE.
Test Access Port (TAP)
Controller State Machine
The TAP controller is a finite state machine that responds
to the logic level at TMS on the rising edge of TCK. See
Figure 16 for a diagram of the finite state machine. The
possible states are described in the following:
Test-Logic-Reset: At power-up, the TAP controller
is in the test-logic-reset state. The instruction register
contains the IDCODE instruction. All system logic of the
device operates normally. This state can be reached
from any state by driving TMS high for five clock cycles.
Run-Test/Idle: The run-test/idle state is used between
scan operations or during specific tests. The instruction
register and test data registers remain idle.
Select-DR-Scan: All test data registers retain their previous state. With TMS low, a rising edge of TCK moves the
controller into the capture-DR state and initiates a scan
sequence. TMS high during a rising edge on TCK moves
the controller to the select-IR-scan state.
Capture-DR: Data can be parallel-loaded into the test
data registers selected by the current instruction. If the
instruction does not call for a parallel load or the selected
test data register does not allow parallel loads, the test
data register remains at its current value. On the rising
edge of TCK, the controller goes to the shift-DR state if
TMS is low or it goes to the exit1-DR state if TMS is high.
Shift-DR: The test data register selected by the current
instruction connects between TDI and TDO and shifts
data one stage toward its serial output on each rising
edge of TCK while TMS is low. On the rising edge of TCK,
the controller goes to the exit1-DR state if TMS is high.
Exit1-DR: While in this state, a rising edge on TCK puts
the controller in the update-DR state. A rising edge on TCK
with TMS low puts the controller in the pause-DR state.
Table 29. SMBus Alert Configuration
REGISTER
ADDRESS
35h
FLASH
ADDRESS
235h
BIT RANGE
[1:0]
DESCRIPTION
SMBus Alert Configuration:
00 = Disabled
01 = Fault1 is SMBus ALERT
10 = Fault2 is SMBus ALERT
11 = Any_Fault is SMBus ALERT
______________________________________________________________________________________ 45
MAX16065/MAX16066
SMBALERT
The MAX16065/MAX16066 support the SMBus alert
protocol. To enable the SMBus alert output, set r35h[1:0]
according to Table 29, which configures a Fault1, Fault2,
or Any_Fault output to act as the SMBus alert. This
output is open-drain and uses the wired-OR configuration with other devices on the SMBus. During a fault,
the MAX16065/MAX16066 assert ALERT low, signaling
the master that an interrupt has occurred. The master
responds by sending the ARA (Alert Response Address)
protocol on the SMBus. This protocol is a read byte with
09h as the slave address. The slave acknowledges the
ARA (09h) address and sends its own SMBus address to
the master. The slave then deasserts ALERT. The master
can then query the slave and determine the cause of the
fault. By checking r1C[6], the master can confirm that
the MAX16065/MAX16066 triggered the SMBus alert.
The master must send the ARA before clearing r1Ch[6].
Clear r1Ch[6] by writing a ‘1.’
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Send Byte Format
S
ADDRESS
Receive Byte Format
R/W ACK
7 bits
0
COMMAND
ACK
8 bits
0
0
Slave Address: Address
of the slave on the serial
interface bus.
S
P
ADDRESS
Data Byte: Presets the internal
address pointer or represents
a command.
ADDRESS
7 bits
SLAVE
ADDRESS
0
DATA
NACK
8 bits
1
P
Data Byte: Data is read from
the location pointed to by the
internal address pointer.
SMBALERT#
R/W ACK
0
ACK
8 bits
0
0
COMMAND
ACK
8 bits
0
0
Slave Address: Address
of the slave on the serial
interface bus.
DATA
ACK
8 bits
0
P
S
SR
SLAVE
ADDRESS
R/W ACK
7 bits
ADDRESS
R/W ACK
0001100
D.C.
0
Alert Response Address:
Only the device that
interrupted the master
responds to this address.
Data Byte: Data is written to
the locations set by the
internal address pointer.
Command Byte:
Sets the internal
address pointer.
R/W ACK
7 bits
COMMAND
0
Slave Address: Address
of the slave on the serial
interface bus.
Read Byte Format
S
1
Slave Address: Address
of the slave on the serial
interface bus.
Write Byte Format
S
R/W ACK
7 bits
1
0
DATA BYTE NACK
8 bits
DATA
NACK
8 bits
1
P
Slave Address: Slave places
its own address on the
serial bus.
P
1
Data Byte: Data is written to
the locations set by the
internal address pointer.
Command Byte:
Sets the internal
address pointer.
Block Write Format
S
ADDRESS
R/W ACK
7 bits
0
COMMAND
ACK
BYTE
COUNT = N
8 bits
0
8 bits
0
Slave Address: Address
of the slave on the
serial interface bus.
ACK DATA BYTE 1 ACK DATA BYTE … ACK DATA BYTE N ACK
8 bits
0
Command Byte:
FAh
8 bits
0
0
8 bits
Slave to master
P
0
Master to slave
Data Byte: Data is written to the locations
set by the internal address pointer.
Block Read Format
S
ADDRESS
R/W ACK
7 bits
0
COMMAND
ACK
8 bits
0
0
Slave Address: Address
of the slave on the
serial interface bus.
SR
ADDRESS
R/W ACK
7 bits
1
0
Slave Address: Address
of the slave on the
serial interface bus.
Command Byte:
FBh
BYTE
COUNT = N
ACK DATA BYTE N ACK DATA BYTE … ACK DATA BYTE N NACK
8 bits
0
8 bits
0
8 bits
0
8 bits
P
1
Data Byte: Data is read from the locations
set by the internal address pointer.
Write Byte Format with PEC
S
ADDRESS
R/W ACK
7 BITS
0
COMMAND
ACK
DATA
ACK
PEC
ACK
8 BITS
0
8 BITS
0
8 BITS
0
0
P
Read Byte Format with PEC
S
ADDRESS
R/W ACK
7 BITS
0
COMMAND
0
8 BITS
ACK SR
0
ADDRESS
R/W ACK
1
7 BITS
0
DATA
ACK
PEC
ACK
8 BITS
0
8 BITS
0
P
Block Write with PEC
S
ADDRESS
R/W ACK
7 BITS
0
COMMAND
8 BITS
0
ACK BYTE COUNT N ACK DATA BYTE 1 ACK
0
8 BITS
0
8 BITS
0
DATA BYTE ACK
8 BITS
0
DATA N
ACK
PEC
ACK
8 BITS
0
8 BITS
0
DATA BYTE
ACK
DATA N
ACK
PEC
NACK
8 BITS
0
8 BITS
0
8 BITS
1
P
Block Read with PEC
S
ADDRESS
7 BITS
R/W ACK
0
COMMAND
0
8 BITS
ACK SR
0
ADDRESS
7 BITS
R/W ACK BYTE COUNT N ACK DATA BYTE 1 ACK
1
0
8 BITS
S = START Condition
ACK = Acknowledge, SDA pulled low during rising edge of SCL.
P = STOP Condition
NACK = Not acknowledge, SDA left high during rising edge of SCL.
Sr = REPEATED START Condition
D.C. = Don’t Care
All data is clocked in/out of the device on rising edges of SCL.
0
8 BITS
0
= SDA transitions from high to low during period of SCL.
= SDA transitions from low to high during period of SCL.
Figure 14. SMBus Protocols
46 �������������������������������������������������������������������������������������
P
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
01100
01011
01010
01001
01000
00111
MEMORY WRITE REGISTER
[LENGTH = 8 BITS]
00110
MEMORY READ REGISTER
[LENGTH = 8 BITS]
00101
MEMORY ADDRESS REGISTER
[LENGTH = 8 BITS]
00100
USER CODE REGISTER
[LENGTH = 32 BITS]
00011
IDENTIFICATION REGISTER
[LENGTH = 32 BITS]
BYPASS REGISTER
[LENGTH = 1 BIT]
MUX 1
00000
11111
COMMAND
DECODER
01001
SETFLSHADD
01010
RSTFLSHADD
01011
SETUSRFLSH
01100
RSTUSRFLSH
01000
SAVE
00111
REBOOT
VDB
INSTRUCTION REGISTER
[LENGTH = 5 BITS]
RPU
TDI
MUX 2
TMS
TDO
TEST ACCESS PORT
(TAP) CONTROLLER
TCK
Figure 15. JTAG Block Diagram
Pause-DR: Shifting of the test data registers halts while
in this state. All test data registers retain their previous
state. The controller remains in this state while TMS is
low. A rising edge on TCK with TMS high puts the controller in the exit2-DR state.
changes in the shift register. On the rising edge of TCK,
the controller goes to the run-test/idle state if TMS is low
or goes to the select-DR-scan state if TMS is high.
Exit2-DR: A rising edge on TCK with TMS high while
in this state puts the controller in the update-DR state.
A rising edge on TCK with TMS low enters the shift-DR
state.
Select-IR-Scan: All test data registers retain the previous states. The instruction register remains unchanged
during this state. With TMS low, a rising edge on TCK
moves the controller into the capture-IR state. TMS high
during a rising edge on TCK puts the controller back into
the test-logic-reset state.
Update-DR: A falling edge on TCK while in the updateDR state latches the data from the shift register path of
the test data registers into a set of output latches. This
prevents changes at the parallel output because of
Capture-IR: Use the capture-IR state to load the shift
register in the instruction register with a fixed value.
This value is loaded on the rising edge of TCK. If TMS is
high on the rising edge of TCK, the controller enters the
______________________________________________________________________________________ 47
MAX16065/MAX16066
REGISTERS
AND FLASH
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
exit1-IR state. If TMS is low on the rising edge of TCK, the
controller enters the shift-IR state.
Shift-IR: In this state, the shift register in the instruction
register connects between TDI and TDO and shifts data
one stage for every rising edge of TCK toward the TDO
serial output while TMS is low. The parallel outputs of
the instruction register as well as all test data registers
remain at the previous states. A rising edge on TCK with
TMS high moves the controller to the exit1-IR state. A
rising edge on TCK with TMS low keeps the controller in
the shift-IR state while moving data one stage through
the instruction shift register.
Exit1-IR: A rising edge on TCK with TMS low puts the
controller in the pause-IR state. If TMS is high on the
rising edge of TCK, the controller enters the update-IR
state.
Pause-IR: Shifting of the instruction shift register halts
temporarily. With TMS high, a rising edge on TCK puts
the controller in the exit2-IR state. The controller remains
in the pause-IR state if TMS is low during a rising edge
on TCK.
Exit2-IR: A rising edge on TCK with TMS high puts the
controller in the update-IR state. The controller loops
back to shift-IR if TMS is low during a rising edge of TCK
in this state.
Update-IR: The instruction code that has been shifted
into the instruction shift register latches to the parallel
outputs of the instruction register on the falling edge of
TCK as the controller enters this state. Once latched,
this instruction becomes the current instruction. A rising
edge on TCK with TMS low puts the controller in the runtest/idle state. With TMS high, the controller enters the
select-DR-scan state.
Instruction Register
The instruction register contains a shift register as well
as a latched 5-bit wide parallel output. When the TAP
controller enters the shift-IR state, the instruction shift
register connects between TDI and TDO. While in the
shift-IR state, a rising edge on TCK with TMS low shifts
the data one stage toward the serial output at TDO. A
rising edge on TCK in the exit1-IR state or the exit2-IR
state with TMS high moves the controller to the update-IR
state. The falling edge of that same TCK latches the data
in the instruction shift register to the instruction register
parallel output. Table 30 shows the instructions supported by the MAX16065/MAX16066 and the respective
operational binary codes.
BYPASS: When the BYPASS instruction is latched into
the instruction register, TDI connects to TDO through the
1-bit bypass test data register. This allows data to pass
from TDI to TDO without affecting the device’s operation.
IDCODE: When the IDCODE instruction is latched into
the parallel instruction register, the identification data
register is selected. The device identification code is
loaded into the identification data register on the rising
edge of TCK following entry into the capture-DR state.
Shift-DR can be used to shift the identification code out
serially through TDO. During test-logic-reset, the IDCODE
instruction is forced into the instruction register. The identification code always has a ‘1’ in the LSB position. The
next 11 bits identify the manufacturer’s JEDEC number
and number of continuation bytes followed by 16 bits for
the device and 4 bits for the version. See Table 31.
USERCODE: When the USERCODE instruction latches
into the parallel instruction register, the user-code data
register is selected. The device user-code loads into the
user-code data register on the rising edge of TCK following entry into the capture-DR state. Shift-DR can be
used to shift the user-code out serially through TDO. See
Table 32. This instruction can be used to help identify
multiple MAX16065/MAX16066 devices connected in a
JTAG chain.
LOAD ADDRESS: This is an extension to the standard
IEEE 1149.1 instruction set to support access to the
memory in the MAX16065/MAX16066. When the LOAD
ADDRESS instruction latches into the instruction register,
TDI connects to TDO through the 8-bit memory address
test data register during the shift-DR state.
READ DATA: This is an extension to the standard IEEE
1149.1 instruction set to support access to the memory
in the MAX16065/MAX16066. When the READ instruction
latches into the instruction register, TDI connects to TDO
through the 8-bit memory read test data register during
the shift-DR state.
WRITE DATA: This is an extension to the standard IEEE
1149.1 instruction set to support access to the memory
in the MAX16065/MAX16066. When the WRITE instruction latches into the instruction register, TDI connects to
TDO through the 8-bit memory write test data register
during the shift-DR state.
REBOOT: This is an extension to the standard IEEE
1149.1 instruction set to initiate a software-controlled
reset to the MAX16065/MAX16066. When the REBOOT
instruction latches into the instruction register, the
MAX16065/MAX16066 resets and immediately begins
the boot-up sequence.
48 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
TEST-LOGIC-RESET
0
RUN-TEST/IDLE
MAX16065/MAX16066
1
0
1
SELECT-DR-SCAN
1
SELECT-IR-SCAN
0
1
0
1
CAPTURE-DR
CAPTURE-IR
0
0
SHIFT-DR
1
1
1
1
EXIT1-IR
0
0
PAUSE-DR
PAUSE-IR
0
1
0
1
0
EXIT2-DR
EXIT2-IR
1
1
UPDATE-DR
1
0
SHIFT-IR
0
EXIT1-DR
0
1
UPDATE-IR
1
0
0
Figure 16. Tap Controller State Diagram
Table 30. JTAG Instruction Set
INSTRUCTION
CODE
NOTES
BYPASS
0x1F
Mandatory instruction code
IDCODE
0x00
Load manufacturer ID code/part number
USERCODE
0x03
Load user code
LOAD ADDRESS
0x04
Load address register content
READ DATA
0x05
Read data pointed by current address
WRITE DATA
0x06
Write data pointed by current address
REBOOT
0x07
Reboot FLASH data content into register file
SAVE
0x08
Trigger emergency save to flash
SETFLSHADD
0x09
Flash page access ON
RSTFLSHADD
0x0A
Flash page access OFF
SETUSRFLSH
0x0B
User flash access ON (must be in flash page already)
RSTUSRFLSH
0x0C
User flash access OFF (return to flash page)
Table 31. 32-Bit Identification Code
MSB
LSB
Version (4 bits)
Part number (16 bits)
Manufacturer (11 bits)
Fixed value (1 bit)
0001
1000000000000001
00011001011
1
______________________________________________________________________________________ 49
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Table 32. 32-Bit User-Code Data
MSB
LSB
Don’t Care
00000000000000000
SMBus slave id
See Table 27
SAVE: This is an extension to the standard IEEE 1149.1
instruction set that triggers a fault log. The current ADC
conversion results along with fault information are saved
to flash depending on the configuration of the Critical
Fault Log Control register (r6Dh).
SETFLSHADD: This is an extension to the standard IEEE
1149.1 instruction set that allows access to the flash
page. Flash registers include ADC conversion results,
DACOUT enables, and GPIO_ input/output data. Use
this page to access registers 200h to 2FFh
RSTFLSHADD: This is an extension to the standard
IEEE 1149.1 instruction set. Use RSTFLSHADD to return
to the default page and disable access to the flash page.
SETUSRFLSH: This is an extension to the standard IEEE
1149.1 instruction set that allows access to the user flash
page. When on the configuration flash page, send the
SETUSRFLSH command, all addresses are recognized
as flash addresses only. Use this page to access registers 300h to 3FFh.
RSTUSRFLSH: This is an extension to the standard IEEE
1149.1 instruction set. Use RSTUSRFLSH to return to
the configuration flash page and disable access to the
user flash.
Restrictions When Writing to Flash
Flash must be written to 8 bytes at a time. The initial
address must be aligned to 8-byte boundaries—the 3
LSBs of the initial address must be ‘000’. Write the 8
bytes using eight successive Write Data commands.
Applications Information
Unprogrammed Device Behavior
When the flash has not been programmed using the
JTAG or SMBus interface, the default configuration of
the EN_OUT_ outputs is open-drain active-low. This
means that the EN_OUT_ outputs are high impedance.
When it is necessary to hold an EN_OUT_ high or low to
prevent premature startup of a power supply before the
flash is programmed, connect a resistor from EN_OUT_
to ground or the supply voltage. Avoid connecting a
resistor to ground when the output is to be configured as
open-drain with a separate pullup resistor.
User ID (r8A[7:0])
Device Behavior at Power-Up
When VCC is ramped from 0, the RESET output is high
impedance until VCC reaches 1.4V, at which point RESET
goes low. All other outputs are high impedance until VCC
reaches 2.7V, when the flash contents are copied into
register memory. This takes 150Fs (max), after which the
outputs assume their programmed states.
Programming the
MAX16065/MAX16066 in Circuit
The MAX16065/MAX16066 can be programmed in the
application circuit by taking into account the following
points during circuit design:
U The MAX16065/MAX16066 needs to be powered from
an intermediate voltage bus or auxiliary voltage supply so programming can occur even when the board’s
power supplies are off. This could also be achieved by
using ORing diodes so that power can be provided
through the programming connector.
U The SMBus or JTAG bus lines should not connect
through a bus multiplexer powered from a voltage rail
controlled by the MAX16065/MAX16066. If the device
needs to be controlled by an on-board FP, consider
connecting the FP to one bus (such as SMBus) and
use the other bus for in-circuit programming.
U An unprogrammed MAX16065/MAX16066’s EN_OUT_s
go high impedance. Ensure that this does not cause
undesired circuit behavior. If necessary, connect pulldown resistors to prevent power supplies from turning on.
Maintaining Power
During a Fault Condition
Power to the MAX16065/MAX16066 must be maintained
for a specific period of time to ensure a successful flash
fault log operation during a fault that removes power to
the circuit. Table 33 shows the amount of time required
depends on the settings in the fault control register
(r6Dh[1:0]).
Maintain power for shutdown during fault conditions in
applications where the always-on power supply cannot
be relied upon by placing a diode and a large capacitor
between the voltage source, VIN, and VCC (Figure 17).
The capacitor value depends on VIN and the time delay
50 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
R6Dh[1:0]
VALUE
MAXIMUM
WRITE TIME
(ms)
DESCRIPTION
00
Save flags and ADC
readings
244
01
Save flags
77
10
Save ADC readings
153
11
Do not save anything
VIN
VOUT
R
MON_
EN_OUT_
—
MAX16065
MAX16066
VIN
VCC
C
MAX16065
MAX16066
GND
Figure 17. Power Circuit for Shutdown During Fault Conditions
required, tFAULT_SAVE. Use the following formula to calculate the capacitor size:
C = (tFAULT_SAVE x ICC(MAX))/(VIN - VDIODE - VUVLO)
where the capacitance is in Farads and tFAULT_SAVE is in
seconds, ICC(MAX) is 14mA, VDIODE is the voltage drop
across the diode, and VUVLO is 2.7V. For example, with
a VIN of 14V, a diode drop of 0.7V, and a tFAULT_SAVE
of 153ms, the minimum required capacitance is 202FF.
Driving High-Side MOSFET Switches
Up to eight of the programmable outputs (EN_OUT1–
EN_OUT8) of the MAX16065/MAX16066 can be configured as charge-pump outputs to drive the gates of seriespass n-channel MOSFETS. When driving MOSFETs,
these outputs act as simple power switches to turn on
the voltage supply rails. Approximate the slew rate, SR,
using the following formula:
SR = ICP/(CGATE + CEXT)
where ICP is the 4FA (typ) charge-pump source current,
CGATE is the gate capacitance of the MOSFET, and CEXT
is the capacitance connected from the gate to ground.
If more than eight series-pass MOSFETs are required
for an application, additional series-pass p-channel
MOSFETS can be connected to outputs configured as
Figure 18. Connection for a p-Channel Series-Pass MOSFET
active-low open drain (Figure 18). Connect a pullup
resistor from the gate to the source of the MOSFET, and
ensure the absolute maximum ratings of the MAX16065/
MAX16066 are not exceeded.
Configuring the Device
An evaluation kit and a graphical user interface (GUI) is
available to create a custom configuration for the device.
Refer to the MAX16065/MAX16066 Evaluation Kit for
configuration.
Cascading Multiple MAX16065/MAX16066s
Multiple MAX16065/MAX16066s can be cascaded to
increase the number of rails controlled for sequencing
and monitoring. There are many ways to cascade the
devices depending on the desired behavior. In general,
there are several techniques:
U Configure a GPIO_ on each device to be EXTFAULT
(open drain). Externally wire them together with a
single pullup resistor. Set register bits r72h[5] and
r6Dh[2] to ‘1’ so that all faults will propagate between
devices. If a critical fault occurs on one device,
EXTFAULT will assert, triggering the nonvolatile fault
logger in all cascaded devices and recording a snapshot of all system voltages.
U Connect open-drain RESET outputs together to obtain
a master system reset signal.
U Connect all EN inputs together for a master enable signal. Since the internal timings of each cascaded device
are not synchronized, EN_OUT_s placed in the same
______________________________________________________________________________________ 51
MAX16065/MAX16066
Table 33. Maximum Write Time
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Figure 19. Graphical User Interface Screenshot
slot on different devices will not come up in the desired
order even if the sequence delays are identical.
U Consider using an external FP to control the EN inputs
or the software enable bits of cascaded devices,
monitoring the RESET outputs as a power-good signal.
U For a large number of voltage rails, the MAX16065/
MAX16066s can be cascaded hierarchically by using
one master device’s EN_OUT_s to control the EN
inputs of several slave devices.
Controlling Power Supplies Without
Using the Sequencer
A FP may control power supplies manually without
involving the sequencing slot system by controlling
EN_OUT_s configured as GPIO_. The output of a power
supply controlled this way can be monitored using a
MON_ input configured as “Monitoring Only(Primary
Sequence)” or “Monitoring Only(Secondary Sequence)”
(see the Monitoring Inputs while Sequencing section). To
monitor the supply for critical faults, the FP will need to
manually set the critical fault enable bit in r6Eh to r72h
after turning on the EN_OUT_, and manually clear the
critical fault enable bit before turning off the EN_OUT_.
Monitoring Current Using the
Differential Inputs
The MAX16065/MAX16066 can monitor up to seven
currents using the dedicated current-sense amplifier as
well as up to six pairs of inputs configured in differential
mode. The accuracy of the differential pairs is limited by
the voltage range and the 10-bit conversions. Each input
pair uses an odd-numbered MON_ input in combination
with an even-numbered MON_ input to monitor both the
voltage from the odd-numbered MON_ to ground and
the voltage difference between the two MON_ inputs.
52 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Figure 20 shows how to connect a current-sense resistor
to a pair of MON_ inputs for monitoring both current and
voltage.
For best accuracy, set the voltage range on the evennumbered MON_ to 1.4V. Since the ADC conversion
results are 10 bits, the monitoring precision is 1.4/1024
= 1.4mV. For more accurate current measurements, use
larger current-sense resistors. The application requirements should determine the balance between accuracy
and voltage drop across the current-sense resistor.
Layout and Bypassing
RS
POWER
SUPPLY
MONODD
ILOAD
MONEVEN
MAX16065
MAX16066
Figure 20. Current Monitoring Connection
Bypass DBP and ABP each with a 1FF ceramic capacitor
to GND. Bypass VCC with a 10FF capacitor to ground.
Avoid routing digital return currents through a sensitive
analog area, such as an analog supply input return path
or ABP’s bypass capacitor ground connection. Use
dedicated analog and digital ground planes. Connect
the capacitors as close as possible to the device.
______________________________________________________________________________________ 53
MAX16065/MAX16066
This way a single pair of inputs can monitor the voltage
and the current of a power-supply rail. The overvoltage
threshold on the even-numbered MON_ inputs can be
used as an overcurrent flag.
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Register Map
FLASH
ADDRESS
REGISTER
ADDRESS
READ/
WRITE
DESCRIPTION
ADC VALUES, FAULT REGISTERS, GPIO_s AS INPUT PORTS—NOT IN FLASH
—
000
R
MON1 ADC output, MSBs
—
001
R
MON1 ADC output, LSBs
—
002
R
MON2 ADC output, MSBs
—
003
R
MON2 ADC output, LSBs
—
004
R
MON3 ADC output, MSBs
—
005
R
MON3 ADC output, LSBs
—
006
R
MON4 ADC output, MSBs
—
007
R
MON4 ADC output, LSBs
—
008
R
MON5 ADC output, MSBs
—
009
R
MON5 ADC output, LSBs
—
00A
R
MON6 ADC output, MSBs
—
00B
R
MON6 ADC output, LSBs
—
00C
R
MON7 ADC output, MSBs
—
00D
R
MON7 ADC output, LSBs
—
00E
R
MON8 ADC output, MSBs
—
00F
R
MON8 ADC output, LSBs
—
010
R
MON9 ADC output, MSBs
—
011
R
MON9 ADC output, LSBs
—
012
R
MON10 ADC output, MSBs
—
013
R
MON10 ADC output, LSBs
—
014
R
MON11 ADC output, MSBs
—
015
R
MON11 ADC output, LSBs
—
016
R
MON12 ADC output, MSBs
—
017
R
MON12 ADC output, LSBs
—
018
R
Current-sense ADC output
—
019
R
CSP ADC output, MSBs
—
01A
R
CSP ADC output, LSBs
—
01B
R/W
Fault register—failed line flags
—
01C
R/W
Fault register—failed line flags/overcurrent
—
01D
R
Failing slot during secondary sequence
—
01E
R
GPIO data in (read only)
—
01F
R
EN_OUT_ as GPIO data in (read only)
—
020
R/W
—
021
R
Flash status/reset output monitor
Current state of the FSM
54 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
FLASH
ADDRESS
REGISTER
ADDRESS
READ/
WRITE
DESCRIPTION
GPIO AND OUTPUT DEPENDENCIES/CONFIGURATIONS
230
030
R/W
OUT configuration
231
031
R/W
OUT configuration
232
032
R/W
OUT configuration
233
033
R/W
Charge-pump configuration, bits
234
034
R/W
EN_OUT_ as GPIO data out
235
035
R/W
SMBALERT pin configuration
236
036
R/W
Fault1 dependencies
237
037
R/W
Fault1 dependencies
238
038
R/W
Fault2 dependencies
239
039
R/W
Fault2 dependencies
23A
03A
R/W
Fault1/Fault2 secondary overcurrent dependencies
23B
03B
R/W
RESET output configuration
23C
03C
R/W
RESET output dependencies
23D
03D
R/W
RESET output dependencies
23E
03E
R/W
GPIO data out
23F
03F
R/W
GPIO configuration
240
040
R/W
GPIO configuration
241
041
R/W
GPIO configuration
242
042
R/W
GPIO push-pull/open drain
ADC—CONVERSIONS
243
043
R/W
ADCs voltage ranges—MON_ monitoring
244
044
R/W
ADCs voltage ranges—MON_ monitoring
245
045
R/W
ADCs voltage ranges—MON_ monitoring
246
046
R/W
Differential pairs enables
247
047
R/W
Current-sense gain-setting (CSP, HV, or LV)
048
R/W
MON1 secondary selectable UV/OV
INPUT THRESHOLDS
248
249
049
R/W
MON1 primary OV
24A
04A
R/W
MON1 primary UV
24B
04B
R/W
MON2 secondary selectable UV/OV
24C
04C
R/W
MON2 primary OV
24D
04D
R/W
MON2 primary UV
24E
04E
R/W
MON3 secondary selectable UV/OV
24F
04F
R/W
MON3 primary OV
250
050
R/W
MON3 primary UV
251
051
R/W
MON4 secondary selectable UV/OV
252
052
R/W
MON4 primary OV
253
053
R/W
MON4 primary UV
______________________________________________________________________________________ 55
MAX16065/MAX16066
Register Map (continued)
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Register Map (continued)
FLASH
ADDRESS
REGISTER
ADDRESS
READ/
WRITE
254
054
R/W
MON5 secondary selectable UV/OV
255
055
R/W
MON5 primary OV
256
056
R/W
MON5 primary UV
257
057
R/W
MON6 secondary selectable UV/OV
258
058
R/W
MON6 primary OV
259
059
R/W
MON6 primary UV
25A
05A
R/W
MON7 secondary selectable UV/OV
DESCRIPTION
25B
05B
R/W
MON7 primary OV
25C
05C
R/W
MON7 primary UV
25D
05D
R/W
MON8 secondary selectable UV/OV
25E
05E
R/W
MON8 primary OV
25F
05F
R/W
MON8 primary UV
260
060
R/W
MON9 secondary selectable UV/OV
261
061
R/W
MON9 primary OV
262
062
R/W
MON9 primary UV
263
063
R/W
MON10 secondary selectable UV/OV
264
064
R/W
MON10 primary OV
265
065
R/W
MON10 primary UV
266
066
R/W
MON11 secondary selectable UV/OV
267
067
R/W
MON11 primary OV
268
068
R/W
MON11 primary UV
269
069
R/W
MON12 secondary selectable UV/OV
26A
06A
R/W
MON12 primary OV
26B
06B
R/W
MON12 primary UV
26C
06C
R/W
Secondary overcurrent threshold
26D
06D
R/W
26E
06E
R/W
Save after EXTFAULT fault control
Faults causing store in flash
26F
06F
R/W
Faults causing store in flash
270
070
R/W
Faults causing store in flash
271
071
R/W
Faults causing store in flash
272
072
R/W
Faults causing store in flash
273
073
R/W
Overcurrent debounce, watchdog mode, secondary threshold type, software
enables
274
074
R/W
ADC fault deglitch/autoretry configuration
275
075
R/W
WDI toggle, power-up fault timer, reverse sequence
276
076
R/W
Watchdog reset output enable, watchdog timers
277
077
R/W
Sequence delay for Slot 0 and Slot 1
FAULT SETUP
TIMEOUTS
56 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
FLASH
ADDRESS
REGISTER
ADDRESS
READ/
WRITE
278
078
R/W
Sequence delay for Slot 2 and Slot 3
279
079
R/W
Sequence delay for Slot 4 and Slot 5
27A
07A
R/W
Sequence delay for Slot 6 and Slot 7
27B
07B
R/W
Sequence delay for Slot 8 and Slot 9
27C
07C
R/W
Sequence delay for Slot 10 and Slot 11
27D
07D
R/W
Primary sequence final slot, sequence delay for Slot 12
27E
07E
R/W
MON1/MON2 slot assignment
27F
07F
R/W
MON3/MON4 slot assignment
280
080
R/W
MON5/MON6 slot assignment
281
081
R/W
MON7/MON8 slot assignment
282
082
R/W
MON9/MON10 slot assignment
283
083
R/W
MON11/MON12 slot assignment
284
084
R/W
EN_OUT1/EN_OUT2 slot assignment
285
085
R/W
EN_OUT3/EN_OUT4 slot assignment
286
086
R/W
EN_OUT5/EN_OUT6 slot assignment
287
087
R/W
EN_OUT7/EN_OUT8 slot assignment
288
088
R/W
EN_OUT9/EN_OUT10 slot assignment
289
089
R/W
EN_OUT11/EN_OUT12 slot assignment
28A
08A
R/W
Customer use (version)
28B
08B
R/W
PEC enable/SMBus address
28C
08C
R/W
Lock bits
28D
08D
R
DESCRIPTION
MISCELLANEOUS
NONVOLATILE FAULT LOG
—
200
201
202
203
204
205
206
207
208
209
20A
20B
20C
20D
20E
20F
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
—
R/W
Revision code
Sequence state
Fault flags, MON1–MON8
Fault flags, MON9–MON12, OC, EXTFAULT
MON1 ADC output
MON2 ADC output
MON3 ADC output
MON4 ADC output
MON5 ADC output
MON6 ADC output
MON7 ADC output
MON8 ADC output
MON9 ADC output
MON10 ADC output
MON11ADC output
MON12 ADC output
Current-sense ADC output
______________________________________________________________________________________ 57
MAX16065/MAX16066
Register Map (continued)
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
Register Map (continued)
USER FLASH
300
39F
R/W
User flash
3A0
3AF
—
Reserved
3B0
3FF
R/W
User flash
Typical Operating Circuits
VSUPPLY
+3.3V
OUT
IN
DC-DC
GND
VCC
MON1
MAX16065
MAX16066
OUT
IN
MON2–MON11
DC-DC
SCL
SDA
GND
OUT
IN
µC
MON12
RESET
RESET
FAULT
INT
WDI
I/O
WDO
INT
DC-DC
GND
AO
GND
58 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
VSUPPLY
+3.3V
OUT
IN
DC-DC
GND
MON1
VCC
MON2
LOAD
OUT
IN
µC
MAX16065
MAX16066
SDA
MONODD
DC-DC
GND
MONEVEN
LOAD
OUT
IN
SCL
RESET
RESET
FAULT
INT
WDI
I/O
WDO
INT
MON11
DC-DC
GND
AO
MON12
LOAD
GND
NOTE: MONODD = MON1, MON3, MON5, MON7, MON9, MON11
MONEVEN = MON2, MON4, MON6, MON8, MON10, MON12
______________________________________________________________________________________ 59
MAX16065/MAX16066
Typical Operating Circuits (continued)
GPIO6
EN_OUT12
EN_OUT11
EN_OUT10
EN_OUT9
EN_OUT8
EN_OUT7
EN_OUT6
EN_OUT5
EN_OUT4
TOP VIEW
EN_OUT3
EN_OUT2
Pin Configurations
36 35 34 33 32 31 30 29 28 27 26 25
EN_OUT1
37
24
GPIO5
EN
38
23
GPIO4
DBP
39
22
GPIO3
VCC
40
21
GPIO2
ABP
41
20
GPIO1
GND
42
19
GPIO8
MON7
43
18
GPIO7
MON8
44
17
GND
MON9
45
16
SCL
MON10
46
15
AO
14
SDA
13
TDO
9
10 11 12
TDI
8
TCK
7
TMS
6
RESET
MON4
5
CSM
4
CSP
3
MON6
2
MON5
1
MON3
48
MON2
47
MON12
*EP
+
MON1
MON11
MAX16065
GPIO5
GPIO6
EN_OUT8
EN_OUT7
EN_OUT6
EN_OUT5
EN_OUT4
EN_OUT3
EN_OUT2
TOP VIEW
EN_OUT1
THIN QFN
(7mm x 7mm)
30 29 28 27 26 25 24 23 22 21
EN 31
20 GPIO4
DBP 32
19 GPIO3
VCC 33
18 GPIO2
ABP 34
17 GPIO1
16 GND
GND 35
MAX16066
MON7 36
15 SCL
14 AO
MON8 37
MON9 38
13 SDA
*EP
+
MON10 39
12 TDO
11 TCK
5
6
7
8
9
10
CSM
RESET
TMS
TDI
MON4
4
CSP
3
MON6
2
MON5
1
MON3
MON1 40
MON2
MAX16065/MAX16066
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
THIN QFN
(6mm x 6mm)
60 �������������������������������������������������������������������������������������
12-Channel/8-Channel, Flash-Configurable System
Managers with Nonvolatile Fault Registers
PROCESS: BiCMOS
Package Information
For the latest package outline information and land patterns, go
to www.maxim-ic.com/packages.
PACKAGE TYPE
PACKAGE CODE
DOCUMENT NO.
48 TQFN-EP*
T4877-6
21-0144
40 TQFN-EP*
T4066-5
21-0141
Maxim cannot assume responsibility for use of any circuitry other than circuitry entirely embodied in a Maxim product. No circuit patent licenses are implied.
Maxim reserves the right to change the circuitry and specifications without notice at any time.
Maxim Integrated Products, 120 San Gabriel Drive, Sunnyvale, CA 94086 408-737-7600
©
2009 Maxim Integrated Products
61
Maxim is a registered trademark of Maxim Integrated Products, Inc.
MAX16065/MAX16066
Chip Information
Similar pages