ETAL ESX10-103-DC24V-10AE Selective load protection, electronic trip characteristic Datasheet

Electronic Circuit Protector ESX10
Description
Electronic circuit protector type ESX10 is designed to ensure selective
disconnection of DC 24 V load systems.
DC 24 V power supplies, which are widely used in industry today, will
shut down the output in the event of an overload with the result that
one faulty load in the system can lead to complete disconnection of
all loads. As well as an unidentified failure this also means stoppage
of the whole system.
Through selective disconnection the ESX10 responds much faster
to overload or short circuit conditions than the switch-mode power
supply. This is achieved by active current limitation. The ESX10 limits
the highest possible current to values between 1.3 to 1.8 times the
selected rated current of the circuit protector. Thus it is possible to
switch on capacitive loads of up to 75,000 µF lamp loads, but they
are disconnected only in the event of an overload or short circuit.
For optimal alignment with the characteristics of the application the
current rating of the ESX10 can be selected in fixed values from
0.5 A...12 A. Failure and status indication are provided by a multicolour
LED and an integral short-circuit-proof status output or a potential-free
signal contact.
The ESX10, with a width of only 12.5 mm, can be plugged into the
E-T-A power distribution socket Module 17plus ensuring ease of
installation and saving space in control cabinets.
Upon detection of overload or short circuit in the load circuit, the
MOSFET of the load output will be blocked to interrupt the
current flow. The MOSFET and the load circuit may be re-activated
via the remote electronic reset input or manually by means of the
ON/OFF button. When starting up the system, the load circuit may
also be manually disconnected.
US patent number: US 6,490,141 B2
Features
l
l
l
l
l
l
l
l
l
l
l
Selective load protection, electronic trip characteristics.
Active current limitation for safe connection of capacitive loads
up to 75,000 µF and on overload/short circuit.
Current ratings 0.5 A...12 A.
Reliable overload disconnection with 1.1 x IN plus, even with long
load lines or small cable cross sections (see table 3).
Manual ON/OFF button (S1).
Clear status and failure indication through LED, status output SF
or Si contact F.
Electronic reset input RE (option).
Integral fail-safe element.
Width per unit only 12.5 mm.
Plug-in mounting utilising power distribution system Module 17plus
or SVSxx optionally (see product group Power distribution systems)
Additional versions with ATEX approval available.
Marking:
II 3G Ex nA IIB T4 Gc X
ESX10-...-E
Please observe separate operating instructions:
1642
ESX10
Technical data
(Tambient = 25 °C, operating voltage US = DC 24 V)
Operating data
Operating voltage US
DC 24 V (18...32 V)
Current rating IN
fixed current ratings: 0.5 A, 1 A, 2 A, 3 A,
4 A, 6 A, 8 A, 10 A, 12 A
Closed current I0
ON condition: typically 20...30 mA
depending on signal output
l multicolour LED:
Status indication
by means of GREEN:
unit is ON, power-MOSFET is switched on
- status output SF ON, supplies +DC 24 V
ORANGE:
in the event of overload or short circuit
until electronic disconnection
RED:
- unit electronically disconnected
- load circuit/Power-MOSFET OFF
OFF: - manually switched off (S1 = OFF)
or device is dead
- undervoltage (US < 8 V)
- after switch-on till the end of the
delay period
l status output SF (option)
l potential-free signal contact F (option)
l ON/OFF/ condition of switch S1
Load circuit
Load output
Power-MOSFET switching output
(high side switch)
Overload disconnection
typically 1.1 x IN (1.05...1.35 x IN)
Short-circuit current IK
active current limitation (see table 1)
Trip time
see time/current characteristics
for electronic disconnection typically 3 s at ILoad > 1.1 x IN
typically 3 s...100 ms at ILoad > 1.8 x IN
(or 1.5 x IN/1.3 x IN)
Temperature disconnection internal temperature monitoring with
electronic disconnection
Low voltage monitoring
load output
with hysteresis, no reset necessary
load “OFF” at US < 8 V
Starting delay tstart typically 0.5 sec after every switch-on
and after applying US
Disconnection of load circuit electronic disconnection
Free-wheeling circuit
external free-wheeling diode recommended with inductive load
Several load outputs must not be connected in parallel
www.e-t-a.de
1
4
Electronic Circuit Protector ESX10
Technical data
Technical data
(Tambient = 25°C, operating voltage US = DC 24 V)
Status output SF
Electrical data
Status OUT
Status OUT
OFF condition
4
ESX10-104/-124
plus-switching signal output, connects US to terminal 12 of module 17plus
nominal data: DC 24 V / max. 0.2 A (short
circuit proof)
status output is internally connected to
GND with a 10 kOhm resistor
ESX10-104/-106/ -124 (signal status OUT),
at US = +24 V
+24 V = S1 is ON, load output connected
through 0V = S1 is ON, load output
blocked and/or switch S1 is OFF
ESX10-127 (signal status OUT inverted),
at US = +24 V
+24 V = S1 is ON, load output blocked,
red LED lighted
0 V = S1 is ON, load output connected
through and/or switch S1 is in OFF position
0 V level at status output when:
l switch S1 is in ON position, but device is
still in switch-on delay
l switch S1 is OFF, or control signal OFF,
device is switched off
l no operating voltage US
Signal output F
ESX10-103/-115/-125
Electrical data
potential-free signal contact max. DC 30 V/0.5 A, min. 10 V/10 mA
ON condition LED green voltage US applied, switch S1 is in ON
position
no overload, no short circuit
l device switched off OFF condition LED off
(switch S1 is in OFF position)
l no voltage US applied
Fault condition LED orange overload condition > 1.1 x IN up to
electronic disconnection
Fault condition LED red electronic disconnection upon
overload or short circuit
device switched off with control signal
(switch S1 is in ON position)
ESX10-101
single signal, make contact
contact SC/SO-SI open
ESX10-102
single signal, break contact
contact SC/SO-SI closed
ESX10-103
group signal change-over contact
contact SC-SO open, SC-SI closed
ESX10-115/-125
group signal, make contact
contact SC-SO open
Fault
signal output fault conditions:
l no operating voltage US
l ON/OFF switch S1 is in OFF position
l red LED lighted (electronic disconnection)
Table 1: voltage drop, current limitation, max. load current
current
rating IN
typically voltage
drop UON at IN
active current limitation (typically)
max. load current at
100 % ON duty
TU = 40 °C
TU = 50 °C
0.5 A
70 mV
1.8 x IN
0.5 A
0.5 A
1A
80 mV
1.8 x IN
1A
1A
2A
130 mV
1.8 x IN
2A
2A
3A
80 mV
1.8 x IN
3A
3A
4A
100 mV
1.8 x IN
4A
4A
6A
130 mV
1.8 x IN
6A
5A
8A
120 mV
1.5 x IN
8A
7A
10 A
150 mV
1.5 x IN
10 A
9A
12 A
180 mV
1.3 x IN
12 A
10.8 A
(Tambient = 25°C, operating voltage US = DC 24 V)
Reset input RE
ESX10-124/-125
Electrical data
voltage: max. + DC 32 V
high > DC 8 V ≤ DC 32 V
low ≤ DC 3 V > 0 V
power consumption typically 2.6 mA
(+DC 24 V)
min. pulse duration typically 10 ms
Reset signal RE
The electronically blocked ESX10-124/-127
(= terminal 13,14 or 12
may remotely be reset via an external
of Module 17plus)
momentary switch due to the falling edge of
a +24 V pulse.
Caution: unused slots
The reset signal will be fed in terminal 13, 14
have to be fitted with
or 12 of Module 17plus and is internally
jumpers
pre-wired.
The reset simultaneously affects all blocked
ESX10-124/-127 channels of the power
distribution system, all switched on
ESX10-124/-127 channels remain
unaffected. With type ESX10-125 the reset
only affects the device concerned. By
connecting the individual terminals 12 of
the Module 17plus a joint reset signal for
all ESX10-125 may be generated.
Control input IN+
ESX10-115
Electrical data
see reset input RE
Control signal IN+
+24 V level (HIGH): device will be switched
on by a remote ON/OFF signal
0 V level (LOW): device will be switched
off by a remote ON/OFF signal
Switch S1 ON/OFF
unit can only be switched on with S1 if a
HIGH level is applied to IN+
General data
Fail-safe element:
backup fuse for ESX10 not required because of the integral redundant fail-safe element
Blade terminals
6.3 mm to DIN 46244-A6.3-0.8
Housing moulded
Mounting plug-in mounting utilising power distribution
system Module 17plus or SVSxx
Ambient temperature
0...+50 °C (without condensation, see EN 60204-1)
Storage temperature
-40...+70 °C
Humidity
96 hrs/95 % RH/40 °C to
IEC 60068-2-78, test Cab.
climate class 3K3 to EN 60721
Vibration
3 g, test to IEC 60068-2-6 test Fc
Degree of protection
housing: IP30 DIN 40050
terminals: IP00 DIN 40050
EMC
emission: EN 61000-6-3
(EMC directive, CE logo) susceptibility: EN 61000-6-2
Insulation co-ordination 0.5 kV/2 pollution degree 2
(IEC 60934)
re-inforced insulation in operating area
dielectric strength
max. DC 32 V (load circuit)
Insulation resistance
(OFF condition)
n/a, only electronic disconnection
ApprovalsCE logo
UL 2367, File # E306740
Solid State Overcurrent Protectors
cURus: UL 508, CSA C22.2 No. 14,
File # E322549
UL 1604, File # E320024
(class I, division 2, groups A, B, C, D)
CSA C22.2 No. 142, File # 16186
CSA C22.2 No. 213 (class I, division 2)
Dimensions (W x H x D) 12.5 x 70 x 60 mm
Mass
approx. 40 g
Attention: when mounted side-by-side without convection the ESX10-0.. should not
carry more than 80 % of its rated load with 100 % ON duty due to thermal effects.
2
www.e-t-a.de
1642
Electronic Circuit Protector ESX10
Approvals
Ordering configuration for ATEX versions: ...-E
Type No.
ESX10 Electronic Circuit Protector for DC 24 V applications
Version
1 standard, without physical isolation in the event of a failure
Signal input
0 without signal input
1 with control input IN+
2 with reset input RE
Signal outputs
0
without
3
signal output F (group signal, change-over)
4
status output SF
5signal output F (group signal, N/O
only ESX10-115 and ESX10-125)
Operating voltage
DC 24 V rated voltage DC 24 V
Current rating
0.5...12 A
Approvals
E ATEX
0
3 - DC 24 V -6 A
E
Standard
Voltage
ratings
Current
ratings
UL
UL 2367
DC 24 V
0.5...12 A
UL
UL 1604
DC 24 V
0.5...12 A
UL cURus
UL 508
CSA C22.2 No. 14
DC 24 V
0.5...16 A
CSA
C22.2 No. 142
C22.2 No. 213
(class I, division 2)
DC 24 V
0.5...12 A
TÜV Süd
ATEX 94/9/EC
Annex VIII
EN 60079-0
EN 60079-11
EN 60079-15
DC 24 V
GL
Rules VI, part 7,
GL 2012, category
C, EMC1
DC 24 V
ordering example
Ordering information
Type No.
ESX10 Electronic Circuit Protector for DC 24 V applications
Version
1 standard, without physical isolation in the event of a failure
Signal input
0 without signal input
1 with control input IN+, only ESX10-115
2 with reset input RE, only ESX10-124
Signal outputs
0
without, only ESX10-100
3
signal output F (group signal, change-over) only ESX10-103
4
status output SF (+24 V = OK),
only ESX10-104, ESX10-124
5signal output F (group signal, N/O
only ESX10-115 and ESX10-125)
Operating voltage
DC 24 V rated voltage DC 24 V Current rating
0.5 A
1A
2A
3A
4A
6A
8A
10 A
12 A
ESX10 - 1
0
0.5...12 A
Schematic diagram ESX10-124
ESX10-124-…
Rsense
Failsafe
LINE (+)
DC 24 V
LOAD (+)
load output
electronic control unit
ESX10 -1
Authority
S1
ON/OFF
status indication
green/orange/red
RE
reset input
RE
reset input
SF
status output
4
GND (-)
3 - DC 24 V - 6 A ordering example
Description of ESX10 signal inputs and outputs (wiring diagrams)
see next page.
Preferred types
Preferred types
ESX10-103-DC24V
Standard current ratings (A)
1
2
3
4
6
8
10
12
x
x
x
x
x
x
x
x
Please note:
l The user should ensure that the cable cross sections of the relvant
load circuit are suitable for the current rating of the ESX10 used.
l Automatic start-up of machinery after shut down must be prevented (Machinery Directive 98/37/EG and EN 60204-1). In the event
of a short circuit or overload the load circuit will be disconnected
electronically by the ESX10.
1642
www.e-t-a.de
3
Electronic Circuit Protector ESX10
Terminal wiring diagram ESX10-124
Information to UL-Approvals/CSA-Approvals
ESX10
UL1604
UL File # E320024
ESX10
Operating Temperature Code T4 A / 0 °C to 50 °C
- This equipment is suitable for use in Class I, Division 2,
Groups A, B, C and D or non-hazardous locations only
Electronic Circuit Protector
ESX10-124-DC 24 V-xxA
WARNING:
- Exposure to some chemicals may degrade the sealing properties
of materials used in the following device: relay
Sealant Material:
Generic Name: Modified diglycidyl ether of bisphenol A
Supplier:
Fine Polymers Corporation
Type:
Epi Fine 4616L-160PK
Casing Material:
Generic Name: Liquid Crystal Polymer
Supplier:
Sumitomo Chemical
Type:
E4008, E4009, or E6008
LOAD +
2
12 SF
Status OUT
14 RE
13 RE
1
11 GND
LINE +
Failsafe
Reset IN
Made in Germany
XXX
RECOMMENDATION:
- Periodically inspect the device named above for any degradation
of properties and replace if degradation is found
Dimensions
WARNING – EXPLOSION HAZARD:
- Do not disconnect equipment unless power has been removed or
the area is known to be non-hazardous
- Substitution of any components may impair suitability for Class I,
Division 2
60
2.36
60
2.36
operating area
ESX10
UL2367
Non-hazardous use - UL File # E306740
70 70
2.75 2.75
operating area
ESX10
UL 508, CSA C22.2 No. 14
Non-hazardous use - UL File # E322549
mounting area
4
10.3 10.3
.405 .405
mounting area
6x6.8=40.8
6x.267=1.60
6x6.8=40.8
50
6x.267=1.60
1.97
50
1.97
6.8
.267
6.8
.267
reverse plug-in
protection
reverse plug-in
protection
blade terminals
DIN 46244-6.3-0.8
blade terminals
DIN 46244-6.3-0.8
ESX10
CSA C22.2 No. 142 - File # 16186
CSA C22.2 No. 213 (Class I, Division 2) - File # 16186
Class 2
Meets requirement for Class 2 current limitation
(ESX10-...-0.5 A/1 A/2 A/3 A)
ok
12.3 12.3
.484 .484
ok
off
on
6A 6A
off
on
UL1604
UL File # E320024
Electronic Circuit Protector
ESX10
C22.2 No.213
CSA File # 16186
This equipment is suitable for use in Class I, Division 2, Groups A,
B, C and D or non-hazardous locations only. T4A / 0° C to 50° C
Warnings:
1. Remove power before disconnecting device
or the area is known to be nonhazardous.
2. Components substitutions may impair suitability of Class I, Div 2.
3. Chemical exposure may degrade internal relay's sealing property.
This is a metric design and millimeter dimensions take precedence ( mm )
inch
UL2367
Non-hazardous use
UL File # E306740
UL508
CSA C22.2 No.14
Non-hazardous use
UL File # E322549
Refer to data sheet / installation guidelines for installation
and safety instructions.
E-T-A Elektrotechnische Apparate GmbH
Industriestraße 2-8 · D-90518 ALTDORF
GERMANY
Phone: +49 9187 10-0 · Fax +49 9187 10-397
E-Mail: [email protected] · www.e-t-a.de
4
www.e-t-a.de
1642
Electronic Circuit Protector ESX10
EG-declaration of Conformity for ATEX-version ESX10-TA/-TB-...-E
4
Accessories
Module 17plus
For technical data see section Power Distribution Systems
70
2.75
slot for fitting labels from
Phoenix, Weidmüller, Wieland
on / off
57
2.24
LOAD (+)
SI
RE
RE
Control unit
Gnd
LINE (+)
Failsafe
I>
ok
47
1.85
42.5
1.67
17 plus
63
2.48
115
4.53
G-profile
EN 50035-G32
symmetrical rail
EN 50022-35x7.5
6
.236
25
.984
25
.984
max. 38
max. 1.50
right-side terminal block
14
14
11
12
2
12
2
1 Line 1 Line
11
slot for busbar
left-side terminal block
module
1642
www.e-t-a.de
5
Electronic Circuit Protector ESX10
Time/Current characteristic curve (TA = 25 °C)
disconnection
typically 1.1 x IN 1.8 x IN
10000
l
The trip time is typically 3 s in the range between 1.1 and 1.8 x IN*1).
l
Electronic current limitation occurs at typically 1.8 x IN*1) which
means that under all overload conditions (independent of the
power supply and the resistance of the load circuit) the max.
overload before disconnection will not exceed 1.8 x IN*1) times
the current rating. Trip time is between 100 ms (short circuit
current IK) and 3 sec (at overload with high line attenuation).
l
Without this current limitation a considerably higher overload
current would flow in the event of an overload or short circuit.
1000
trip time in seconds
100
current limitation
typically 1.8 x IN
10
5
1
0. 1
*1) current
limitation typically 1.8 x IN times
rated current at IN = 0.5 A...6 A
current limitation typically 1.5 x IN times
rated current at IN = 8 A or 10 A
current limitation typically 1.3 x IN times
rated current at IN = 12 A
0.01
0
1
2
5 IK
4
3
...times rated current
Table 3: Reliable trip of ESX10
Reliable trip of ESX10 with different cable lengths and cross sections
Resistivity of copper ρ0 = 0.0178 (Ohm x mm2) / m
US = DC 19.2 V (= 80 % v. 24 V)
voltage drop of ESX10 and tolerance of trip point (typically 1.1 x IN = 1.05 ... 1.35 x IN)
have been taken into account.
ESX10-selected rating IN (in A) ➞
3
e. g. trip current Iab = 1.25 x IN (in A) ➞
Rmax in Ohm = (US / Iab) - 0.050 ➞
4
6
3.75
7.5
5.07
2.51
➞ ESX10 trips after 3 s
The ESX10 reliably trips from 0 Ohm to max. circuitry resistance Rmax
Cable cross section A in
mm2
➞
0.14
0.25
0.34
0.5
0.75
1
1.5
cable resistance in Ohm = (R0 x 2 x L) / A
cable length L in meter (= single length)
5
1.27
0.71
0.52
0.36
0.24
0.18
0.12
10
2.54
1.42
1.05
0.71
0.47
0.36
0.24
15
3.81
2.14
1.57
1.07
0.71
0.53
0.36
20
5.09
2.85
2.09
1.42
0.95
0.71
0.47
25
6.36
3.56
2.62
1.78
1.19
0.89
0.59
30
7.63
4.27
3.14
2.14
1.42
1.07
0.71
35
8.90
4.98
3.66
2.49
1.66
1.25
0.83
40
10.17
5.70
4.19
2.85
1.90
1.42
0.95
45
11.44
6.41
4.71
3.20
2.14
1.60
1.07
50
12.71
7.12
5.24
3.56
2.37
1.78
1.19
75
19.07
10.68
7.85
5.34
3.56
2.67
1.78
100
25.34
14.24
10.47
7.12
4.75
3.56
2.37
125
31.79
17.80
13.09
8.90
5.93
4.45
2.97
150
38.14
21.36
15.71
10.68
7.12
5.34
3.56
175
44.50
24.92
18.32
12.46
8.31
6.23
4.15
200
50.86
28.48
20.94
14.24
9.49
7.12
4.75
225
57.21
32.04
23.56
16.02
10.68
8.01
5.34
250
63.57
35.60
26.18
17.80
11.87
8.90
5.93
Example 1:
max. length at 1.5
Example 2:
max. length at 1.5 mm2 and 6 A ➞ 106 m
Example 3:
mixed wiring:
mm2
and 3 A ➞ 214 m
R1 = 40 m in 1.5 mm2 and R2 = 5 m in 0.25 mm2:
(Control cabinet – sensor/actuator level) R1 = 0.95 Ohm, R2 = 0.71 Ohm
Total (R1 + R2) = 1.66 Ohm
6
www.e-t-a.de
1642
Electronic Circuit Protector ESX10
Table 2: ESX10 - product version
version
signal output
signal input
signal output F
ESX10 -...
control input ON/OFF
+24 V Control IN+
-100
-103
-104
-115
-124
-125
reset input +24 V
RE
group signal
N/O
status output SF
group signal
change-over
status OUT
+24 V = OK
x
x
x
x
x
x
x
x
ESX10 Signal inputs / outputs (wiring diagram)
ESX10 signal inputs / outputs (wiring diagrams)
Signal contacts are shown in the OFF or fault condition.
Failsafe
SC
SO
SF
LOAD +
13
14
12
2
ESX10-125-...
GND
SC
SO
RE
LOAD +
13
14
12
2
LOAD +
2
11
SF
12
LINE +
RE
14
Signal
Failsafe
with reset input RE ( +DC 24 V↓)
with signal output F (group signal, N/O)
Reset IN
LOAD +
2
GND
SI
12
LINE +
SO
14
RE
13
operating condition: SF +24V = OK
fault condition:
SF 0V
4
operating condition: SF +24 V = OK
fault condition:
SF 0V
Status OUT
GND
LOAD +
2
11
IN +
12
Failsafe
SO
14
LINE +
SC
13
1
GND
11
operating condition: SC-SO closed
fault condition:
SC-SO open
Reset IN
with reset input RE (+DC 24 V↓)
with status output SF (+24V = load output ON)
11
SC
13
ESX10-124-...
Control IN
LINE +
1
Signal
Failsafe
with control input IN+ (+DC 24 V)
with signal output F (group signal, N/O)
without signal input
with status output SF (+24 V = load output ON)
1
GND
11
operating condition: SC/SO closed, SC-SI open
fault condition:
SC/SO open, SC-SI closed
ESX10-115-...
ESX10-104
Signal
LINE +
1
2
14
GND
11
13
LINE +
1
LOAD +
Failsafe
Failsafe
without signal input
with signal output F (group signal, change-over)
Status OUT
ESX10-103
without signal input/output
1
ESX10-100
operating condition: SC-SO closed
fault condition:
SC-SO open
This is a metric design and millimeter dimensions take precedence ( mm )
inch
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications without
notice is reserved. Product markings may not be exactly as the ordering codes. Errors and
omissions excepted.
1642
www.e-t-a.de
7
Electronic Circuit Protector ESX10
4
8
www.e-t-a.de
1642