MACOM CSL-38-60010 Solid state hybrid voltage sensor Datasheet

Catalog 1308242
Issued 3-03
P&B
CS series
Solid State Hybrid Voltage Sensor
• Close differential
• Choice of two types
– Fixed pick-up and knob adjustable drop-out
– Knob adjustable pick-up and drop-out
• Internal 2 Form C (DPDT) output relay
Fixed Pick-up and
Adjustable Drop-out
Adjustable Pick-up
and Drop-out
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Sensing Modes
Engineering Data
The CS can be used as an over or undervoltage sensor, depending upon
whether the load is connected to the normally closed (NC) or normally open
(NO) contacts of the sensor’s output relay.
Power Requirement: Typically less than 3VA or 3W.
Duty Cycle: Continuous.
Repeatability: ± 1%, max.
Response Time: 10-25 ms, typ.
Internal Relay Contact Arrangement: 2 Form C (DPDT).
Internal Relay Contact Rating: 10A @ 28VDC , res., or 120VAC, 80% p.f.
Reverse Polarity Protection: On DC types.
Temperature Range: -10°C to +55°C.
Temperature Coefficient: 0.2%/°C, max.
Enclosure: Plastic dust cover.
Mounting: 8-pin octal style plug. Fits either 27E122 or 27E891 (snap-on)
screw terminal sockets.
Weight: 8 oz. (227g) approximately.
Overvoltage sensor – The NC contacts are used. The relay remains deenergized until an overvoltage is sensed.
Undervoltage sensor – The NO contacts are used. The relay remains energized until the voltage decreases to the preset level, where the sensor
de-energizes the relay.
Adjustable Voltage Sensor Operation
Note 1 – As voltage increases, the
relay will pick-up at its selected
point and remain energized while
voltage is maintained at that level or
higher.
VOLTAGE
RELAY
ENERGIZED
Note 2 – As voltage decreases, after pick-up, the relay will drop-out at
its selected point.
HYSTERISIS
2 VOLTS
RELAY
DE-ENERGIZED
NOTE 1
Ordering Information –
Distributors are more likely to stock boldface items.
Note 3 – Minimum hysterisis, the
voltage differential between pick-up
and drop-out, is typically 2% of
pick-up.
.560
(14.22)
2.406 MAX.
(61.11)
Dimensions are shown for
Pick-Up
(Volts)
Drop-Out Range
(Volts)
Maximum
Voltage
CSJ-38-71010
CSL-38-31010
105
22
90-103
16-21
140VAC (50/60 Hz.)
32VDC
Adjustable Pick-Up and Adjustable Drop-Out
Part Number
CSJ-38-70010
CSL-38-30010
CSL-38-40010
CSL-38-60010
Pick-Up Range Drop-Out Range*
(Volts)
(Volts)
92-140
20-30
40-58
92-140
90-138
18-28
38-56
90-138
Maximum
Voltage
150VAC (50/60 Hz.)
32VDC
60VDC
150VDC
Wiring Diagrams – Bottom Views
(pins numbered clockwise from keyway)
Outline Dimensions
1302 reference purposes only.
Part Number
* Actual maximum drop-out voltage is the selected pick-up voltage less the hysterisis
voltage.
NOTE 2
.600 MAX.
(15.24)
2.937 MAX.
(76.60)
Fixed Pick-Up and Adjustable Drop-Out
1.781 MAX.
(42.24)
.875
(22.23)
1.187
(30.15)
Dimensions are in inches over
(millimeters) unless otherwise
specified.
AC
INPUT
Specifications and availability
subject to change.
+
DC INPUT
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Similar pages