Surge Arrester 3-Electrode-Arrester T61-C600X Ordering code: B88069X8820B102 DC spark-over voltage 1) 2) 4) 420 ... 700 V Impulse spark-over voltage 4) at 100 V/µs - for 99 % of measured values - typical values of distribution < 900 < 800 V V < 1000 < 900 V V Nominal impulse discharge current (wave 8/20 µs) 5) Single impulse discharge current (wave 8/20 µs) 5) 20 30 kA kA Nominal alternating discharge current (50 Hz, 1 s) 5) Alternating discharge current (50 Hz, 9 cycles) 5) 20 130 A A Insulation resistance at 100 Vdc 4) > 10 GΩ Capacitance at 1 MHz 4) < 1.5 pF Transverse delay time 3) < 0.2 µs Arc voltage at 1 A Glow to arc transition current Glow voltage ~ 35 ~1 ~ 200 V A V Weight ~ 3.5 g Operation and storage temperature -40 ... +90 °C Climatic category (IEC 60068-1) 40/ 90/ 21 at 1 kV/µs - for 99 % of measured values - typical values of distribution Marking, green 600 YY O 600 YY O - Nominal voltage - Year of production - Non radioactive 1) At delivery AQL 0.65 level II, DIN ISO 2859 In ionized mode 3) Test according to ITU-T Rec. K.12 4) Tip or ring electrode to center electrode 5) Total current through center electrode, half value through tip respectively ring electrode. Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845 2) AB E / AB PM Issue 02, 23.05.2002 Page 1 of 2 Surge Arrester 3-Electrode-Arrester T61-C600X Ordering code: B88069X8820B102 Not to scale Dimensions in mm Non controlled document EPCOS AG 2002. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information contained therein without EPCOS' prior express consent is prohibited. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless otherwise agreed. AB E / AB PM Issue 02, 23.05.2002 Page 2 of 2