EPCOS B84299K0039

EMC Filters
Series/Type:
B84299K0033
The following products presented in this data sheet are being withdrawn.
Ordering Code
Substitute Product
B84299K00330000
B84144A*R120,
B84131
B84144A*R120,
B84131
B84144A*R120,
B84131
B84299K00350000
B84299K00360000
Date of
Withdrawal
2010-03-26
Deadline Last
Orders
2010-06-30
Last Shipments
2010-03-26
2010-06-30
2010-09-30
2010-03-26
2010-06-30
2010-09-30
2010-09-30
For further information please contact your nearest EPCOS sales office, which will also support
you in selecting a suitable substitute. The addresses of our worldwide sales network are
presented at www.epcos.com/sales.
4-line filters
B84299K0033 … K0039
for installations and systems
Power line filters for 3-phase systems
with additional VHF suppression
Rated voltage 440/250 V AC, 50/60 Hz
Rated current 6 to 75 A
Construction
■ 4-line filter
■ Metal case
■ Screw-type cable fitting for strain relief
on line side, edge protector on load side
■ Feedthrough capacitors
Features
■ High insertion loss up to the GHz range
■ UL approval
Applications
■ Power supplies for industrial installations
■ Medical equipment
■ Packaging machines
Terminals
■ Finger-safe terminal blocks inside case
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
4-line filters
B84299K0033 … K0039
for installations and systems
Circuit diagram
L1
L1’
L2
L2’
L3
L3’
N
N’
LINE
LOAD
SSB0543-U-E
Typical circuit taking the example of filters for 16 A
Technical data and measuring conditions
Rated voltage VR
440/250 V AC, 50/60 Hz
Rated current IR
Referred to 40 °C ambient temperature
Test voltage Vtest
1414 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case)
Leakage current lleak
At 400 V AC, 50 Hz
Climatic category (IEC 60068-1)
40/085/21 (–40 °C/+85 °C/21 days damp heat test)
Approvals
UL 1283
Characteristics and ordering codes
VR
AC
V
IR
lleak
A
440/250 6
16
25
50
75
Ordering code
Approvals
mA
Approx.
Terminal
cross section weight
kg
mm2
<5
<5
<5
<5
< 10
4
4
4
16
25
B84299K0033
B84299K0035
B84299K0036
B84299K0037
B84299K0039
×
× (14 A)
× (20 A)
× (40 A)
× (65 A)
1.8
2.1
3.0
7.5
11
× = approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
4-line filters
B84299K0033 … K0039
for installations and systems
Dimensional drawings
B84299K0033 (6 A)
N
L3
L2
L1
L1’
L2’
L3’
N’
38
38
14
LINE
75
50
50
Terminal blocks 4 mm 2
Tightening torque 0.8 ... 1.0 Nm
1.0
Screw-type cable fitting PG 9
(cable diameter 8 ... 12.5 mm)
ø13.5 with edge protector
Hole in case ø15.5±0.4
218
195±0.3
4 x ø6
106
55±0.3
25.5
11.5
SSB1083-X-E
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
4-line filters
B84299K0033 … K0039
for installations and systems
B84299K0035 (16 A)
N
L3
L2
L1
L1’
L2’
L3’
N’
38
38
15
LINE
90
64
64
Terminal blocks 4 mm 2
Tightening torque 0.8 ... 1.0 Nm
1.0
Screw-type cable fitting PG 9
(cable diameter 8 ... 12.5 mm)
ø13.5 with edge protector
Hole in case ø15.5±0.4
218
195±0.3
4 x ø6
106
60±0.3
23
11.5
SSB1100-R-E
Please read Cautions and warnings and
Important notes at the end of this document.
5
01/06
4-line filters
B84299K0033 … K0039
for installations and systems
B84299K0036 (25 A)
37
37
16
N
L3
L2
L1
LINE
Screw-type cable fitting PG 11
(cable diameter 9 ... 15 mm)
73
73
1.0
Terminal blocks 4 mm 2
Tightening torque 0.8 ... 1.0 Nm
102
L1’
L2’
L3’
N’
ø17 with edge protector
Hole in case ø20
236
214±0.3
4 x ø7
130
60±0.3
35
11
SSB1101-Z-E
Please read Cautions and warnings and
Important notes at the end of this document.
6
01/06
4-line filters
B84299K0033 … K0039
for installations and systems
32
32
B84299K0037 (50 A)
LINE
N’ L3’ L2’ L1’
N L3 L2 L1
21
Screw-type cable fitting DIN 46320
PG 21 included in delivery (loosely)
Hole in case ø28.5 mm
Cable diameter 18 ... 23 mm
ø22 with edge protector
Hole in case ø25
1.25
Terminal blocks 16 mm 2
Tightening torque 1.5 ... 1.8 Nm
30
95
35
30
Hole ø37.5
300
270±0.3
46
15
207
115±0.3
ø7
32
28.5
35
35
Matched to cable fitting PG 21
Please read Cautions and warnings and
Important notes at the end of this document.
SSB1084-6-E
7
01/06
4-line filters
B84299K0033 … K0039
for installations and systems
35
70 _ 5
35
B84299K0039 (75 A)
LINE
N’ L3’ L2’ L1’
N L3 L2 L1
Screw-type cable fitting
DIN 46320 PG 29
included in delivery (loosely)
Hole in case ø37 mm
32±2
12±2
2
Terminal blocks 35 mm
Tightening torque 3.2 ... 3.7 Nm
4
23
140
80
80
25
110
1.25
ø35 with edge protector
Hole in case ø37
37
350
320±0.3
50
Matched to cable fitting PG 29
Please read Cautions and warnings and
Important notes at the end of this document.
8
01/06
207
37
157
ø7
123±0.2
42
15
35
SSB1085-E-E
4-line filters
B84299K0033 … K0039
for installations and systems
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Example: filters for 16 A
SSB1578-S
100
dB B84299K0035
α
80
60
40
20
0
10 5
10 6
10 7
10 8
Hz 10 9
f
Please read Cautions and warnings and
Important notes at the end of this document.
9
01/06
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see
). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro­
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low­
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
■
■
■
■
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger­
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen­
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
10
01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As
a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of the customer application or other action taken by the customer (e.g.
installation of protective circuitry or redundancy) that no injury or damage is sustained by third
parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap,
PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
11
01/06