Surge Arrester 2-Electrode-Arrester V13-A800XN Ordering code: B88069X4380C251 Preliminary data DC spark-over voltage 1) 2) 600 … 1000 V Impulse spark-over voltage at 1 kV/µs - for 99 % of measured values - typical values of distribution < 1500 < 1300 V V Insulation resistance at 100 Vdc >1 GΩ < 2.5 pF 20 kA 1 operation 10/350 µs + 1 operation 10/350 µs + 1 operation 10/350 µs + 1 operation 10/350 µs + 1 operation 8/20 µs Max. follow-on current at 255 VRMS 7.6 9 12 12 20 100 kA kA kA kA kA Apeak Weight ~ 6.5 g Operation and storage temperature -40 ... +90 °C Climatic category (IEC 60068-1) 40/ 90/ 21 Capacitance at 1 MHz 2) Impulse discharge current 15 operations 8/20 µs 800 YY O Marking, black 800 YY O 1) 2) - Nominal voltage - Year of production - Non radioactive At delivery AQL 0.65 level II, DIN ISO 2859 In ionized mode AB E / AB PM Issue 03, 26.04.2002 Page 1 of 2 Surge Arrester 2-Electrode-Arrester V13-A800XN Ordering code: B88069X4380C251 Preliminary data Not to scale Dimensions in mm Non controlled document EPCOS AG 2002. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information contained therein without EPCOS' prior express consent is prohibited. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless otherwise agreed. AB E / AB PM Issue 03, 26.04.2002 Page 2 of 2