DALLAS DS1621

DS1621
Digital Thermometer and Thermostat
www.dalsemi.com
PIN ASSIGNMENT
FEATURES
§ Temperature measurements require no
external components
§ Measures temperatures from –55°C to
+125°C in 0.5°C increments. Fahrenheit
equivalent is –67°F to 257°F in 0.9°F
increments
§ Temperature is read as a 9–bit value (2byte transfer)
§ Wide power supply range (2.7V to 5.5V)
§ Converts temperature to digital word in 1
second
§ Thermostatic settings are user definable
and nonvolatile
§ Data is read from/written via a two–wire
serial interface (open drain I/O lines)
§ Applications include thermostatic
controls, industrial systems, consumer
products, thermometers, or any thermal
sensitive system
§ 8–pin DIP or SOIC package (150-MIL and
208-MIL)
SDA
1
8
VDD
SCL
2
7
A0
TOUT
3
6
A1
GND
4
5
A2
DS1621S 8-PIN SOIC (150-MIL)
DS1621V 8-PIN SOIC (208-MIL)
See Mech Drawings Section
SDA
1
8
VDD
SCL
2
7
A0
TOUT
3
6
A1
GND
4
5
A2
DS1621 8-PIN DIP (300-MIL)
See Mech Drawings Section
PIN DESCRIPTION
SDA
SCL
GND
TOUT
A0
A1
A2
VDD
- 2-Wire Serial Data Input/Output
- 2-Wire Serial Clock
- Ground
- Thermostat Output Signal
- Chip Address Input
- Chip Address Input
- Chip Address Input
- Power Supply Voltage
DESCRIPTION
The DS1621 Digital Thermometer and Thermostat provides 9–bit temperature readings which indicate
the temperature of the device. The thermal alarm output, TOUT, is active when the temperature of the
device exceeds a user–defined temperature TH. The output remains active until the temperature drops
below user defined temperature TL, allowing for any hysteresis necessary.
User-defined temperature settings are stored in nonvolatile memory so parts may be programmed prior to
insertion in a system. Temperature settings and temperature readings are all communicated to/from the
DS1621 over a simple two–wire serial interface.
1 of 16
102299
DS1621
DETAILED PIN DESCRIPTION Table 1
PIN
1
2
3
SYMBOL
SDA
SCL
TOUT
4
5
6
7
8
GND
A2
A1
A0
VDD
DESCRIPTION
Data input/output pin for 2-wire serial communication port.
Clock input/output pin for 2-wire serial communication port.
Thermostat output. Active when temperature exceeds TH; will reset when
temperature falls below TL.
Ground pin.
Address input pin.
Address input pin.
Address input pin.
Supply voltage input power pin. (2.7V – 5.5V)
OPERATION
Measuring Temperature
A block diagram of the DS1621 is shown in Figure 1. The DS1621 measures temperatures through the
use of an onboard proprietary temperature measurement technique. A block diagram of the temperature
measurement circuitry is shown in Figure 2.
The DS1621 measures temperature by counting the number of clock cycles that an oscillator with a low
temperature coefficient goes through during a gate period determined by a high temperature coefficient
oscillator. The counter is preset with a base count that corresponds to –55°C. If the counter reaches 0
before the gate period is over the temperature register, which is also preset to the –55°C value, is
incremented indicating that the temperature is higher than –55°C.
At the same time, the counter is preset with a value determined by the slope accumulator circuitry. This
circuitry is needed to compensate for the parabolic behavior of the oscillators over temperature. The
counter is then clocked again until it reaches 0. If the gate period is still not finished, then this process
repeats.
The slope accumulator is used to compensate for the nonlinear behavior of the oscillators over
temperature, yielding a high resolution temperature measurement. This is done by changing the number
of counts necessary for the counter to go through for each incremental degree in temperature. To obtain
the desired resolution, both the value of the counter and the number of counts per °C (the value of the
slope accumulator) at a given temperature must be known.
This calculation is done inside the DS1621 to provide 0.5°C resolution. The temperature reading is
provided in a 9–bit, two’s complement reading by issuing the READ TEMPERATURE command. Table
2 describes the exact relationship of output data to measured temperature. The data is transmitted through
the 2–wire serial interface, MSB first. The DS1621 can measure temperature over the range of –55°C to
+125°C in 0.5°C increments. For Fahrenheit usage a lookup table or conversion factor must be used.
2 of 16
102299
DS1621
DS1621 FUNCTIONAL BLOCK DIAGRAM Figure 1
STATUS REGISTER &
CONTROL LOGIC
SCL
SDA
TEMPERATURE SENSOR
ADDRESS
AND
I/O CONTROL
HIGH TEMP TRIGGER, TH
A0
A1
A2
LOW TEMP TRIGGER, TL
DIGITAL COMPARATOR/LOGIC
3 of 16
TOUT
102299
DS1621
TEMPERATURE MEASURING CIRCUITRY Figure 2
SLOPE ACCUMULATOR
PRESET
COMPARE
LOW TEMPERATURE
COEFFICIENT OSCILLATOR
COUNTER
SET/CLEAR
LSB
PRESET
INC
TEMPERATURE REGISTER
=0
HIGH TEMPERATURE
COEFFICIENT OSCILLATOR
COUNTER
STOP
=0
TEMPERATURE/DATA RELATIONSHIPS Table 2
TEMPERATURE
DIGITAL OUTPUT
(Binary)
01111101 00000000
00011001 00000000
00000001 00000000
00000000 00000000
11111111 10000000
11100111 00000000
11001001 00000000
+125°C
+25°C
+½°C
+0°C
-½°C
-25°C
-55°C
DIGITAL OUTPUT
(Hex)
7B00h
1900h
0080h
0000h
FF80h
E700h
C900h
Since data is transmitted over the 2–wire bus MSB first, temperature data may be written to/read from the
DS1621 as either a single byte (with temperature resolution of 1°C) or as two bytes. The second byte
would contain the value of the least significant (0.5°C) bit of the temperature reading as shown in Table
1. Note that the remaining 7 bits of this byte are set to all "0"s.
Temperature is represented in the DS1621 in terms of a ½°C LSB, yielding the following 9–bit format:
MSB
1
LSB
1
1
0
0
1
1
1
0
0
T = -25°C
4 of 16
0
0
0
0
0
0
102299
DS1621
Higher resolutions may be obtained by reading the temperature and truncating the 0.5°C bit (the LSB)
from the read value. This value is TEMP_READ. The value left in the counter may then be read by
issuing a READ COUNTER command. This value is the count remaining (COUNT_REMAIN) after the
gate period has ceased. By loading the value of the slope accumulator into the count register (using the
READ SLOPE command), this value may then be read, yielding the number of counts per degree C
(COUNT_PER_C) at that temperature. The actual temperature may be then be calculated by the user
using the following:
TEMPERATURE=TEMP_READ-0.25 +
(COUNT _ PER _ C − COUNT _ REMAIN )
COUNT _ PER _ C
Thermostat Control
In its operating mode, the DS1621 functions as a thermostat with programmable hysteresis as shown in
Figure 3. The thermostat output updates as soon as a temperature conversion is complete.
When the DS1621’s temperature meets or exceeds the value stored in the high temperature trip register
(TH), the output becomes active and will stay active until the temperature falls below the temperature
stored in the low temperature trigger register (TL). In this way, any amount of hysteresis may be
obtained.
The active state for the output is programmable by the user so that an active state may either be a logic
"1" (VDD) or a logic "0" (0V).
THERMOSTAT OUTPUT OPERATION Figure 3
DQ (Thermostat output, Active=High)
TL
TH
T (°C)
OPERATION AND CONTROL
The DS1621 must have temperature settings resident in the TH and TL registers for thermostatic
operation. A configuration/status register also determines the method of operation that the DS1621 will
use in a particular application, as well as indicating the status of the temperature conversion operation.
The configuration register is defined as follows:
DONE
THF
TLF
NVB
1
0
POL
1SHOT
where
DONE = Conversion Done bit. “1” = Conversion complete, “0” = Conversion in progress.
5 of 16
102299
DS1621
THF
= Temperature High Flag. This bit will be set to “1” when the temperature is greater than or
equal to the value of TH. It will remain “1” until reset by writing “0” into this location or removing power
from the device. This feature provides a method of determining if the DS1621 has ever been subjected to
temperatures above TH while power has been applied.
TLF
= Temperature Low Flag. This bit will be set to “1” when the temperature is less than or equal
to the value of TL. It will remain “1” until reset by writing “0” into this location or removing power from
the device. This feature provides a method of determining if the DS1621 has ever been subjected to
temperatures below TL while power has been applied.
NVB
= Nonvolatile Memory Busy flag. “1” = Write to an E2 memory cell in progress, “0” =
nonvolatile memory is not busy. A copy to E2 may take up to 10 ms.
POL
= Output Polarity Bit. “1” = active high, “0” = active low. This bit is nonvolatile.
1SHOT = One Shot Mode. If 1SHOT is “1”, the DS1621 will perform one temperature conversion upon
receipt of the Start Convert T protocol. If 1SHOT is “0”, the DS1621 will continuously perform
temperature conversions. This bit is nonvolatile.
For typical thermostat operation the DS1621 will operate in continuous mode. However, for applications
where only one reading is needed at certain times or to conserve power, the one–shot mode may be used.
Note that the thermostat output (TOUT) will remain in the state it was in after the last valid temperature
conversion cycle when operating in one–shot mode.
2–WIRE SERIAL DATA BUS
The DS1621 supports a bidirectional 2–wire bus and data transmission protocol. A device that sends data
onto the bus is defined as a transmitter, and a device receiving data as a receiver. The device that controls
the message is called a “master." The devices that are controlled by the master are “slaves." The bus must
be controlled by a master device which generates the serial clock (SCL), controls the bus access, and
generates the START and STOP conditions. The DS1621 operates as a slave on the 2–wire bus.
Connections to the bus are made via the open–drain I/O lines SDA and SCL.
The following bus protocol has been defined (See Figure 4):
• Data transfer may be initiated only when the bus is not busy.
• During data transfer, the data line must remain stable whenever the clock line is HIGH. Changes in
the data line while the clock line is high will be interpreted as control signals.
Accordingly, the following bus conditions have been defined:
Bus not busy: Both data and clock lines remain HIGH.
Start data transfer: A change in the state of the data line, from HIGH to LOW, while the clock is HIGH,
defines a START condition.
Stop data transfer: A change in the state of the data line, from LOW to HIGH, while the clock line is
HIGH, defines the STOP condition.
6 of 16
102299
DS1621
Data valid: The state of the data line represents valid data when, after a START condition, the data line
is stable for the duration of the HIGH period of the clock signal. The data on the line must be changed
during the LOW period of the clock signal. There is one clock pulse per bit of data.
Each data transfer is initiated with a START condition and terminated with a STOP condition. The
number of data bytes transferred between START and STOP conditions is not limited and is determined
by the master device. The information is transferred byte–wise and each receiver acknowledges with a
ninth–bit.
Within the bus specifications a regular mode (100 kHz clock rate) and a fast mode (400 kHz clock rate)
are defined. The DS1621 works in both modes.
Acknowledge: Each receiving device, when addressed, is obliged to generate an acknowledge after the
reception of each byte. The master device must generate an extra clock pulse which is associated with this
acknowledge bit.
A device that acknowledges must pull down the SDA line during the acknowledge clock pulse in such a
way that the SDA line is stable LOW during the HIGH period of the acknowledge related clock pulse. Of
course, setup and hold times must be taken into account. A master must signal an end of data to the slave
by not generating an acknowledge bit on the last byte that has been clocked out of the slave. In this case,
the slave must leave the data line HIGH to enable the master to generate the STOP condition.
DATA TRANSFER ON 2–WIRE SERIAL BUS Figure 4
Figure 4 details how data transfer is accomplished on the 2–wire bus. Depending upon the state of the
R/W bit, two types of data transfer are possible:
1. Data transfer from a master transmitter to a slave receiver. The first byte transmitted by the
master is the slave address. Next follows a number of data bytes. The slave returns an acknowledge
bit after each received byte.
2. Data transfer from a slave transmitter to a master receiver. The first byte, the slave address,
is transmitted by the master. The slave then returns an acknowledge bit. Next follows a number of
data bytes transmitted by the slave to the master. The master returns an acknowledge bit after all
received bytes other than the last byte. At the end of the last received byte, a ‘not acknowledge’ is
returned.
7 of 16
102299
DS1621
The master device generates all of the serial clock pulses and the START and STOP conditions. A
transfer is ended with a STOP condition or with a repeated START condition. Since a repeated START
condition is also the beginning of the next serial transfer, the bus will not be released.
The DS1621 may operate in the following two modes:
1. Slave receiver mode: Serial data and clock are received through SDA and SCL. After each byte is
received an acknowledge bit is transmitted. START and STOP conditions are recognized as the
beginning and end of a serial transfer. Address recognition is performed by hardware after reception
of the slave address and direction bit.
2. Slave transmitter mode: The first byte is received and handled as in the slave receiver mode.
However, in this mode the direction bit will indicate that the transfer direction is reversed. Serial data
is transmitted on SDA by the DS1621 while the serial clock is input on SCL. START and STOP
conditions are recognized as the beginning and end of a serial transfer.
SLAVE ADDRESS
A control byte is the first byte received following the START condition from the master device. The
control byte consists of a 4-bit control code; for the DS1621, this is set as 1001 binary for read and write
operations. The next 3 bits of the control byte are the device select bits (A2, A1, A0). They are used by
the master device to select which of eight devices are to be accessed. These bits are in effect the 3 least
significant bits of the slave address. The last bit of the control byte (R/ W ) defines the operation to be
performed. When set to a “1” a read operation is selected, when set to a “0” a write operation is selected.
Following the START condition the DS1621 monitors the SDA bus checking the device type identifier
being transmitted. Upon receiving the 1001 code and appropriate device select bits, the slave device
outputs an acknowledge signal on the SDA line.
8 of 16
102299
DS1621
2-WIRE SERIAL COMMUNICATION WITH DS1621 Figure 5
9 of 16
102299
DS1621
COMMAND SET
Data and control information is read from and written to the DS1621 in the format shown in Figure 5. To
write to the DS1621, the master will issue the slave address of the DS1621 and the R/ W bit will be set to
“0”. After receiving an acknowledge, the bus master provides a command protocol. After receiving this
protocol, the DS1621 will issue an acknowledge and then the master may send data to the DS1621. If the
DS1621 is to be read, the master must send the command protocol as before and then issue a repeated
START condition and the control byte again, this time with the R/ W bit set to “1” to allow reading of the
data from the DS1621. The command set for the DS1621 as shown in Table 3 is as follows:
Read Temperature [AAh]
This command reads the last temperature conversion result. The DS1621 will send 2 bytes, in the format
described earlier, which are the contents of this register.
Access TH [A1h]
If R/ W is “0” this command writes to the TH (HIGH TEMPERATURE) register. After issuing this
command, the next 2 bytes written to the DS1621, in the same format as described for reading
temperature, will set the high temperature threshold for operation of the TOUT output. If R/ W is “1” the
value stored in this register is read back.
Access TL [A2h]
If R/ W is “0” this command writes to the TL (LOW TEMPERATURE) register. After issuing this
command, the next 2 bytes written to the DS1621, in the same format as described for reading
temperature, will set the high temperature threshold for operation of the TOUT output. If R/ W is “1” the
value stored in this register is read back.
Access Config [ACh]
If R/ W is “0” this command writes to the configuration register. After issuing this command, the next
data byte is the value to be written into the configuration register. If R/ W is “1” the next data byte read is
the value stored in the configuration register.
Read Counter [A8h]
This command reads the value of the counter byte. This command is valid only if R/ W is “1”.
Read Slope [A9h]
This command reads the value of the slope counter byte from the DS1621. This command is valid only if
R/ W is “1”.
Start Convert T [EEh]
This command begins a temperature conversion. No further data is required. In one–shot mode the
temperature conversion will be performed and then the DS1621 will remain idle. In continuous mode this
command will initiate continuous conversions.
Stop Convert T [22h]
This command stops temperature conversion. No further data is required. This command may be used to
halt a DS1621 in continuous conversion mode. After issuing this command, the current temperature
10 of 16
102299
DS1621
measurement will be completed and the DS1621 will remain idle until a Start Convert T is issued to
resume continuous operation.
DS1621 COMMAND SET Table 3
2-WIRE BUS DATA
AFTER ISSUING
PROTOCOL
INSTRUCTION
DESCRIPTION
PROTOCOL
TEMPERATURE CONVERSION COMMANDS
Read Temperature Read last converted temperature
AAh
<read 2 bytes data>
value from temperature register.
Read Counter
Reads value of count remaining
A8h
<read data>
from counter.
Read Slope
Reads value of the slope
A9h
<read data>
accumulator.
Start Convert T
Initiates temperature
EEh
idle
conversion.
Stop Convert T
Halts temperature conversion.
22h
idle
THERMOSTAT COMMANDS
Access TH
Reads or writes high
A1h
<write data>
temperature limit value into TH
register.
Access TL
Reads or writes low
A2h
<write data>
temperature limit value into TL
register.
Access Config
Reads or writes configuration
ACh
<write data>
data to configuration register.
NOTES
1
1
2
2
2
NOTES:
1. In continuous conversion mode a Stop Convert T command will halt continuous conversion. To
restart the Start Convert T command must be issued. In one–shot mode a Start Convert T command
must be issued for every temperature reading desired.
2. Writing to the E2 typically requires 10ms at room temperature. After issuing a write command, no
further writes should be requested for at least 10 ms.
11 of 16
102299
DS1621
MEMORY FUNCTION EXAMPLE
Example: Bus master sets up DS1621 for continuous conversion and thermostatic function.
BUS MASTER
MODE
TX
TX
RX
TX
RX
TX
DS1621
MODE
RX
RX
TX
RX
TX
RX
DATA (MSB
FIRST)
START
<address,0>
ACK
ACh
ACK
02h
RX
TX
TX
RX
TX
RX
TX
TX
RX
RX
TX
RX
TX
RX
ACK
START
<address,0>
ACK
A1h
ACK
28h
RX
TX
TX
RX
ACK
00h
RX
TX
TX
RX
TX
RX
TX
TX
RX
RX
TX
RX
TX
RX
ACK
START
<address,0>
ACK
A2h
ACK
0Ah
RX
TX
TX
RX
ACK
00h
RX
TX
TX
RX
TX
RX
TX
TX
RX
RX
TX
RX
TX
RX
ACK
START
<address,0>
ACK
EEh
ACK
STOP
COMMENTS
Bus Master initiates a START condition.
Bus Master sends DS1621 address; R/ W = 0.
DS1621 generates acknowledge bit.
Bus Master sends Access Config command protocol.
DS1621 generates acknowledge bit.
Bus Master sets up DS1621 for output polarity active
high, continuous conversion.
DS1621 generates acknowledge bit.
Bus Master generates a repeated START condition.
Bus Master sends DS1621 address; R/ W = 0.
DS1621 generates acknowledge bit.
Bus Master sends Access TH command.
DS1621 generates acknowledge bit.
Bus Master sends first byte of data for TH limit of
+40°C.
DS1621 generates acknowledge bit.
Bus Master sends second byte of data for TH limit of
+40°C.
DS1621 generates acknowledge bit.
Bus Master generates a repeated START condition.
Bus Master sends DS1621 address; R/ W = 0.
DS1621 generates acknowledge bit.
Bus Master sends Access TL command.
DS1621 generates acknowledge bit.
Bus Master sends first byte of data for TL limit of
+10°C.
DS1621 generates acknowledge bit.
Bus Master sends second byte of data for TL limit of
+10°C.
DS1621 generates acknowledge bit.
Bus Master generates a repeated START condition.
Bus Master sends DS1621 address; R/ W = 0.
DS1621 generates acknowledge bit.
Bus Master sends Start Convert T command protocol.
DS1621 generates acknowledge bit.
Bus Master initiates STOP condition.
12 of 16
102299
DS1621
ABSOLUTE MAXIMUM RATINGS*
Voltage on Any Pin Relative to Ground
Operating Temperature
Storage Temperature
Soldering Temperature
–0.5V to +7.0V
–55°C to +125°C
–55°C to +125°C
260°C for 10 seconds
* This is a stress rating only and functional operation of the device at these or any other conditions above
those indicated in the operation sections of this specification is not implied. Exposure to absolute
maximum rating conditions for extended periods of time may affect reliability.
RECOMMENDED DC OPERATING CONDITIONS
PARAMETER
Supply Voltage
SYMBOL
VDD
MIN
2.7
DC ELECTRICAL CHARACTERISTICS
PARAMETER
Thermometer Error
Low Level Input
Voltage
High Level Input
Voltage
Pulse width of
spikes which must
be suppressed by
the input filter
Low Level Output
Voltage
SYMBOL
TERR
Active Supply
Current
Standby Supply
Current
Thermostat Output
(TOUT) Output
Voltage
MAX
5.5
UNITS
V
NOTES
1
(-55°C to +125°C; VDD=2.7V to 5.5V)
MIN
TYP
MAX
±½
UNITS
°C
NOTES
11
See Typical Curve
VIL
0.5
0.3 VDD
V
VIH
0.7 VDD
VDD+0.5
V
tSP
Fast Mode
0
50
ns
VOL1
3 mA Sink
Current
6 mA Sink
Current
0.4<VI/O<0.9VDD
0
0.4
V
0
0.6
V
-10
10
µA
10
pF
1000
400
100
µA
3, 4
1
µA
3, 4
0.4
V
V
VOL2
Input Current each
I/O Pin
I/O Capacitance
CONDITION
0°C to 70°C
-55°C to + 0°C
and
70°C to 125°C
TYP
CI/O
ICC
Temperature
Conversion
E2 Write
Communication Only
ISTBY
VOH
VOL
1 mA Source
4 mA Sink
13 of 16
2.4
2
102299
DS1621
AC ELECTRICAL CHARACTERISTICS
PARAMETER
Temperature
Conversion Time
NV Write Cycle
Time
SCL Clock
Frequency
Bus Free Time
Between a STOP
and START
Condition
Hold Time
(Repeated) START
Condition
Low Period of SCL
Clock
High Period of SCL
Clock
Setup Time for a
Repeated START
Condition
Data Hold Time
Data Setup Time
SYMBOL
TTC
CONDITION
tWR
0°C to 70°C
fSCL
Fast Mode
Standard Mode
Fast Mode
Standard Mode
0
0
1.3
4.7
tHD:STA
Fast Mode
Standard Mode
0.6
4.0
µs
TLOW
Fast Mode
Standard Mode
Fast Mode
Standard Mode
Fast Mode
Standard Mode
1.3
4.7
0.6
4.0
0.6
4.7
µs
Fast Mode
Standard Mode
Fast Mode
Standard Mode
Fast Mode
Standard Mode
0
0
100
250
20+0.1CB
tBUF
THIGH
tSU:STA
tHD:DAT
tSU:DAT
Rise Time of Both
tR
SDA and SCL
Signals
Fall Time of both
tF
Fast Mode
SDA and SCL
Standard Mode
Signals
Setup time for
tSU:STO
Fast Mode
STOP Condition
Standard Mode
Capacitative Load
Cb
for each Bus Line
All values referred to VIH=0.9 VDD and VIL=0.1 VDD.
AC ELECTRICAL CHARACTERISTICS
PARAMETER
Input Capacitance
(-55°C to +125°C; VDD=2.7V to 5.5V)
SYMBOL
CI
MIN
14 of 16
MIN
TYP
0.4
MAX
1
UNITS
s
NOTES
10
50
ms
10
400
100
KHz
µs
5
µs
µs
0.9
20+0.1CB
µs
6, 7
ns
8
300
1000
ns
9
300
300
ns
9
0.6
4.0
µs
400
pF
(-55°C to +125°C; VDD=2.7V to 5.5V)
TYP
5
MAX
UNITS
pF
NOTES
102299
DS1621
NOTES:
1. All voltages are referenced to ground.
2. I/O pins of fast mode devices must not obstruct the SDA and SCL lines if VDD is switched off.
3. ICC specified with TOUT pin open.
4. ICC specified with VCC at 5.0V and SDA, SCL = 5.0V, 0°C to 70°C.
5. After this period, the first clock pulse is generated.
6. A device must internally provide a hold time of at least 300 ns for the SDA signal (referred to the
VIH MIN of the SCL signal) in order to bridge the undefined region of the falling edge of SCL.
7. The maximum tHD:DAT has only to be met if the device does not stretch the LOW period (tLOW) of the
SCL signal.
8. A fast mode device can be used in a standard mode system, but the requirement tSU:DAT >250 ns must
then be met. This will automatically be the case if the device does not stretch the LOW period of the
SCL signal. If such a device does stretch the LOW period of the SCL signal, it must output the next
data bit to the SDA line tRMAX+tSU:DAT = 1000+250 = 1250 ns before the SCL line is released.
9. Cb – total capacitance of one bus line in pF.
10. Writing to the nonvolatile memory should only take place in the 0°C to 70°C temperature range.
11. See typical curve for specification limits outside 0°C to 70°C range. Thermometer error reflects
sensor accuracy as tested during calibration.
TIMING DIAGRAM
15 of 16
102299
DS1621
TYPICAL PERFORMANCE CURVE
DS1621 DIGITAL THERMOMETER AND THERMOSTAT
TEMPERATURE READING ERROR
TEMPERATURE (deg. C)
16 of 16
102299