ETC IC693MDL760

Solenoid Valve Output Module
IC693MDL760
Product Description
GFK-1881A
November 2000
Description
The module is accessed from the logic program as a
standard 16-point output module. When using VersaPro
version 2.0 (or later version) programming software, it
should be configured by its catalog number. When using
programming software other than VersaPro version 2.0
(or later version), the module must be configured as a
standard 16-point generic output module.
The module is enclosed in a standard IC693 plastic
housing.
4
5
6
7
8
9
10
11
1
2
3
4
5
Solenoid Valves
3
DC Outputs
The five 24VDC outputs can each drive up to a maximum
0.5A, with a limit of 2.0A total for all five points. Field
wiring is connected to these outputs via a 10-pin
connector located on the front panel. The user must
provide 24VDC to this connector to power the positive
logic outputs, which source current to the field
connections. This group of five discrete outputs is
electrically isolated from the PLC backplane; however,
the outputs are not individually isolated from each other.
2
1
2
3
4
5
6
7
8
9
10
Pendent
A 12-pin connector, located on the module’s front panel,
allows the user to connect the optional IC693ACC760
Solenoid Forcing Pendent, described later.
PWR
1
DC Outputs
This IC693MDL760 output module provides eleven
pneumatic outputs and five 24VDC sourcing outputs. For
each pneumatic output, the module contains an internal 3way solenoid-actuated valve and an associated output
fitting, which is located on the front panel. When an
output is turned ON, its internal valve connects a usersupplied pressure source (100 psi maximum) to the output
fitting. The pressure source is connected to the fitting on
the bottom of the module. When the output is turned
OFF, the valve’s output port is vented to atmosphere
inside the module. Solenoid power is supplied from an
external 24VDC source to the “DC Outputs” connector on
the front panel.
Figure 1. IC693MDL760 Module
2
Solenoid Valve Output Module
GFK-1881A
Module Specifications
Table 1. Module Specifications
Module Specifications
Pneumatic Outputs
Outputs per Module
11 (grouped)
Thermal Derating
Refer to Table 2
Supply Pressure
100 psi max.
Pressure Drop
25 psi max.@ 0.25scfm
External Solenoid Power
21.6-26.4VDC, 24VDC nominal
Isolation
1500 volts between field side and logic side; 500 volts between
groups
Solenoid Inrush Current
33mA/valve @ 24VDC
Solenoid Holding Current
13mA/valve @ 24VDC
ON Response Time
12ms max.
OFF Response Time
12ms max.
Maximum Solenoid ON Time
30 days max. (must be turned OFF at least once every 30 days)
Output Fitting
Threaded for 10-32 adapter, 1/16″ hose barb provided
Supply Fitting
Threaded for 10-32 adapter, 1/8″ hose barb provided
LED Indicators for output points
One LED per output point indicates ON/OFF state
LED “PWR” Indicator
LED indicates solenoid power is present
DC Outputs
Outputs per Module
5 (grouped)
Thermal Derating
None
Output Voltage
18-30VDC, 24VDC nominal
Isolation
1500 volts between field side and logic side; 500 volts between
groups
Continuous Load Current
0.5A @ 30VDC per point, 2.0A total for all five points
Inrush Current
2.0A for 100ms
Voltage Drop
0.5V max
Leakage Current
1mA @ 30VDC max
ON Response Time
2ms max.
OFF Response Time
2ms max.
Protection (each output)
No internal fuse
LED Indicators
One LED per output shows on/off state
Module Characteristics
Operational Ambient
Temperature
45°C (113° F) max.
Backplane Current
75mA from 5V bus (solenoid LEDs are powered from external
power source)
Solenoid Valve Output Module
3
GFK-1881A
Environmental Requirements and Solenoid Valve Output Thermal Derating
Table 2. Environmental Requirements
Parameter
Min.
−40
0
Storage Temperature
Operational Ambient temperature
Max.
85
45
Units
Degrees C
Degrees C
Note
This module has a lower operating temperature rating than standard IC693 I/O
modules.
Table 3. Solenoid Valve Output Thermal Derating
Ambient
Temperature
30° C (86° F)
40° C (104° F)
45° C (113° F)
Solenoid Valve Output Rating (with DC Outputs
Operating at “Continuous Load Current” Rating)
All pneumatic outputs may be on continuously
Six pneumatic outputs may be on continuously
Four pneumatic outputs may be on continuously
Note
•
IC693MDL760A does not have CE or UL approvals/listings.
•
IC693MDL760B (and later versions), when available, will have CE and UL
approvals/listings.
Optional IC693ACC760 Solenoid Forcing Pendent
The IC693ACC760 Solenoid Forcing Pendent is an optional system maintenance tool. This pendent is a small hand-held unit
containing eleven switches, one for each valve. Each switch is labeled to allow the user to easily establish a correlation
between any given switch and its corresponding valve. The pendent is attached to the Solenoid Valve Output Module via the
12-pin connector, labeled “Pendent,” on the module’s front panel.
With solenoid power applied (to the DC Outputs connector), the user may turn the solenoids ON and OFF with the pendent
switches. This pendent is intended to allow maintenance personnel to operate the valves during shut down periods when the
main power to PLC system has been turned off. If the pendent is attached during normal operation (with the PLC system
running), a command from the PLC can turn a valve ON even if the pendent switch for that valve is in the OFF position, and
a pendant switch can turn a valve ON even if the PLC is commanding it to be OFF.
LED Operation
This module has 17 LED indicators (see Figure 1):
• Solenoid Power - 1 LED, labeled PWR, indicates presence of solenoid power.
• Point Status
- 16 LEDs, labeled 1-11 and 1-5, indicate individual I/O point ON/OFF status.
The solenoid valve status LEDs (the top group, labeled 1 to 11) are powered from the 24VDC external Solenoid Power
source; these LEDs will not illuminate unless this power source is present. The “PWR” LED indicates the presence of
external solenoid power. Each valve status LED illuminates while its corresponding valve is open (valve coil is energized),
whether by PLC command or by use of the Solenoid Forcing Pendent. The discrete output LEDs (the bottom group, labeled
1 to 5) are powered from the PLC backplane and can illuminate even if the external DC Output field power (24VDC) is off.
4
Solenoid Valve Output Module
GFK-1881A
Field Wiring
Two AMP brand .025 square double-row .100 X .100 shrouded male pin headers provide the field connection to the five
24VDC discrete outputs and the Solenoid Forcing Pendent. These connectors have detent windows to retain the mating field
connector. The field connectors are not supplied with the module; however, the optional pendent comes with cable and
connector. See the next section, “Field Connectors,” for specifications.
Table 4. Pendent Connector Pin Assignments
Pin
Number*
1
2
3
4
5
6
7
8
9
10
11
12
7
1
8
2
9
3
10
4
11
5
12
6
Connection
Output Point 2 (Solenoid 2)
Output Point 4 (Solenoid 4)
Output Point 6 (Solenoid 6)
Output Point 8 (Solenoid 8)
Output Point 10 (Solenoid 10)
Output Point 11 (Solenoid 11)
Output Point 1 (Solenoid 1)
Output Point 3 (Solenoid 3)
Output Point 5 (Solenoid 5)
Output Point 7 (Solenoid 7)
Output Point 9 (Solenoid 9)
Solenoid Power Common
* Connector numbering was changed in version A of this data sheet
to meet a customer requirement. This did not involve any physical
changes to the module.
View: Looking at
Front of Module
Table 5. DC Output Connector Pin Assignments
Pin
Number*
1
2
3
4
5
6
7
8
9
10
6
1
7
2
8
3
9
4
10
5
Connection
External Solenoid Power COM
Output Point 15 (DC Output 4)
Field Power +24VDC (for DC Outputs)
Output Point 12 (DC Output 1)
Output Point 16 (DC Output 5)
External Solenoid Power +24VDC
N/C
Field Power Common (for DC Outputs)
Output Point 13 (DC Output 2)
Output Point 14 (DC Output 3)
* Connector numbering was changed in version A of this data sheet
to meet a customer requirement. This did not involve any physical
changes to the module.
View: Looking at
Front of Module
Solenoid Valve Output Module
5
GFK-1881A
Field Connectors
The following specifications are for the mating connectors (not supplied with the module) for the
module’s two faceplate connectors (“Pendent” and “DC Output”).
Pendent Connector (Supplied with Optional Pendent)
Item
Vendor
Part Number
Note
Male Housing
AMP
87631-7
12-pin connector housing
Crimp Contacts (12
required)
AMP
1-87523-9
Female pins, rated for AWG 20-24
gauge wire
Crimping Tool
AMP
90202-2
Item
Vendor
Part Number
Notes
Male Housing
AMP
87631-5
10-pin connector housing
Crimp Contacts (10
required)
AMP
1-87523-9
Female pins, rated for AWG 20-24
gauge wire
Crimping Tool
AMP
90202-2
DC Output Connector
Pneumatic Fitting Specifications and Installation Instructions
Module Number
Part
Notes
Vendor
Fitting per Module
Number
Front
11
Clippard 11752-2 10-32 threads, 1/16″ hose barb, 1/4″ hex. shoulder
Bottom
1
Clippard 11752-3 10-32 threads, 1/8″ hose barb, 1/4″ hex. shoulder
Due to limited room in the module’s packing container, it is necessary to ship the module with its fittings
removed. Use the following guidelines to install the fittings on the module:
•
Place the provided gasket over the threaded end of the fitting and carefully push it over the threads
until it stops against the hexagonal shoulder.
•
Carefully thread the fitting into the manifold by hand.
•
Tighten the fitting to a maximum of 7 to 9 inch/pounds.
Caution
Overtightening may cause a fitting to crack or snap off, or could result in thread
damage. Limit tightening torque to 7 to 9 inch/pounds.
6
Solenoid Valve Output Module
GFK-1881A
Pneumatics Installation and Safety Requirements
Since the IC693MDL760 module’s internal valves exhaust inside the module, it is important that you
adhere to the following guidelines:
•
Compressed air or other inert gas used in the module’s valves must be clean and dry. No water, oil,
or other contaminants can be tolerated in the air/gas stream. The presence of these will cause module
failure and possible damage to surrounding components.
•
Only clean, dry, compressed air or inert gas may be used. Use of an explosive or flammable gas will
result in explosion or fire if used with this module.
•
The module should not be used in an airtight, unvented cabinet. Use in an airtight cabinet could
result in the cabinet becoming pressurized, which could lead to personal injury and equipment
failure.
Warning
Failure to follow the above “Pneumatics Installation and Safety
Requirements” can result in personal injury, module failure, and
damage to associated equipment.
Compatibility
Hardware
This module is a standard size IC693 module, compatible with all IC693 series CPUs and baseplates. It
will function in any CPU, Expansion, or Remote baseplate.
Software
When configuring this module with VersaPro version 2.0 (or later version), it should be configured by its
catalog number. When configuring with programming software other than VersaPro version 2.0 (or later
version), the module must be configured as a standard 16-point generic output module.
Scan Time Contribution
This module has the same scan time contribution rating as a standard 16-point output module, as specified
in the I/O Scan Time Contribution tables in Chapter 2 of the IC693 PLC CPU Instruction Set Reference
Manual.